| Date |
Text |
| 2007-07-05 16:59:52 | ** UNSAT 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING. |
| | PLEASE ALSO SEE NEW COMMENTS. |
| | |
| | 1) NOTE: PLEASE SEE NEW LOAD CALCULATIONS SUBMITTED |
| | NEED TO MEET 220.83B. |
| | PLEASE ALSO SEE THE WATER HEATER IS REQUIRED TO BE |
| | SHOWN AT 125% PER 422.13. (CHANGEDUNDER THE 2005 |
| | NEC). |
| | |
| | 2) NOTE: PLEASE SEE RISER SUBMITTED ON NEW SHEETS SHOWS |
| | AN *EQUIPMENT GROUNDING CONDUCTOR* FROM THE METER TO |
| | EACH OF THE FIRST MEANS OF DISCONNECTS WHICH IS NOTE |
| | PERMITTED PER 250.6, 250.24. |
| | PLEASE SEE PLANS ATTACHED FOR REFERENCE DOES NOT SHOW |
| | THIS. |
| | |
| | 3) NOTE: PLEASE SEE THE SMOKE DETECTION/ALARM DEVICE IN |
| | EXISTING MASTER BEDROOM IS REQUIRED TO MEET NFPA-72 |
| | 11.8.3. PLEASE SEE CEILING APPEARS TO BE SLOPED OR |
| | TRAY. IF THIS IS A TRAY CEILING AND IS GREATER THAN |
| | 12INCHES FROM THE SURROUNDING FLAT CEILING AREAS, THEN |
| | THE SMOKE ALARM DEVICE IS REQUIRED TO BE INSTALLED |
| | WITHIN 12 INCHES OF THE HIGHEST POINT. |
| | PLEASE CLARIFY, THIS ITEM COULD BE REDLINED. |
| | |
| | 4) NOTE: PLEASE NOTE THE NEW FOOTER WILL BE REQUIRED TO |
| | BE ATTACHED TO THE EXISTING GROUNDING ELECTRODE SYSTEM |
| | PER 250.50. |
| | |
| | 5) NOTE: PLEASE SEE THE 2FT OR MORE OF WALL SPACE IN |
| | BAR AREA REQUIRES A RECEPTACLE PER 210.52. THIS WAS |
| | MISSED ON PREVIOUS REVIEW, HOWEVER PLEASE CORRECT AT |
| | THIS TIME AS PLANS ARE COMING BACK FOR OTHER COMMENTS. |
| | |
| | 6) NOTE: PLEASE DO NOT ATTACH THE PRODUCT APPROVALS AND |
| | OTHER SUPPORTING DOCUMENTS DOWN THE LEFT HAND SIDE OF |
| | PLANS. |
| | PLEASE SEE THESE HAVE BEEN REMOVED BY THIS REVIEWER AND |
| | PLACED INTO TWO PACKAGES. |
| | FBC ADMIN SECTION. 106.1 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |