Plan Review Notes
Plan Review Notes For Permit 07050354
Permit Number 07050354
Review Stop E
Sequence Number 2
Notes
Date Text
2007-07-05 16:59:52** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE NEW COMMENTS.
  
 1) NOTE: PLEASE SEE NEW LOAD CALCULATIONS SUBMITTED
 NEED TO MEET 220.83B.
 PLEASE ALSO SEE THE WATER HEATER IS REQUIRED TO BE
 SHOWN AT 125% PER 422.13. (CHANGEDUNDER THE 2005
 NEC).
  
 2) NOTE: PLEASE SEE RISER SUBMITTED ON NEW SHEETS SHOWS
 AN *EQUIPMENT GROUNDING CONDUCTOR* FROM THE METER TO
 EACH OF THE FIRST MEANS OF DISCONNECTS WHICH IS NOTE
 PERMITTED PER 250.6, 250.24.
 PLEASE SEE PLANS ATTACHED FOR REFERENCE DOES NOT SHOW
 THIS.
  
 3) NOTE: PLEASE SEE THE SMOKE DETECTION/ALARM DEVICE IN
 EXISTING MASTER BEDROOM IS REQUIRED TO MEET NFPA-72
 11.8.3. PLEASE SEE CEILING APPEARS TO BE SLOPED OR
 TRAY. IF THIS IS A TRAY CEILING AND IS GREATER THAN
 12INCHES FROM THE SURROUNDING FLAT CEILING AREAS, THEN
 THE SMOKE ALARM DEVICE IS REQUIRED TO BE INSTALLED
 WITHIN 12 INCHES OF THE HIGHEST POINT.
 PLEASE CLARIFY, THIS ITEM COULD BE REDLINED.
  
 4) NOTE: PLEASE NOTE THE NEW FOOTER WILL BE REQUIRED TO
 BE ATTACHED TO THE EXISTING GROUNDING ELECTRODE SYSTEM
 PER 250.50.
  
 5) NOTE: PLEASE SEE THE 2FT OR MORE OF WALL SPACE IN
 BAR AREA REQUIRES A RECEPTACLE PER 210.52. THIS WAS
 MISSED ON PREVIOUS REVIEW, HOWEVER PLEASE CORRECT AT
 THIS TIME AS PLANS ARE COMING BACK FOR OTHER COMMENTS.
  
 6) NOTE: PLEASE DO NOT ATTACH THE PRODUCT APPROVALS AND
 OTHER SUPPORTING DOCUMENTS DOWN THE LEFT HAND SIDE OF
 PLANS.
 PLEASE SEE THESE HAVE BEEN REMOVED BY THIS REVIEWER AND
 PLACED INTO TWO PACKAGES.
 FBC ADMIN SECTION. 106.1
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved