| Plan Review Notes For Permit 07050354 |
| Permit Number |
07050354 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-16 17:02:47 | BUILDING REVIEW SECOND CHECKLIST: | | | 1- SPECIFY ALL LIVE AND DEAD LOADS. NEED TO INCLUDE THE | | | ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5OF 2004 | | | FLORIDA RESIDENTIAL CODE. | | | | | | 2- ARCHITECT TO SPECIFY ROOF TILE FASTENING AS REQUIRED | | | BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004. NEED TO | | | SPECIFY SIZE AND NUMBER OF NAILS TO VERIFY COMPLIANCE | | | WITH TILE ATTACHMENT RESISTANCE ON PAGE 4 OF NOA | | | 02-0916.11 SUBMITTED. PRODUCT APPROVAL IS TO VERIFY | | | COMPLIANCE WITH ARCHITECT'S DESIGN CRITERIA. | | | NOTE: ATTACHMENT CALCULATIONS SHALL BE DONE AS A MOMENT | | | BASED SYSTEM. SEE ITEM #1 ON PAGE 2 OF 6 OF NOA | | | SUBMITTED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|