Plan Review Notes
Plan Review Notes For Permit 07050354
Permit Number 07050354
Review Stop B
Sequence Number 2
Notes
Date Text
2007-07-16 17:02:47BUILDING REVIEW SECOND CHECKLIST:
 1- SPECIFY ALL LIVE AND DEAD LOADS. NEED TO INCLUDE THE
 ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 2- ARCHITECT TO SPECIFY ROOF TILE FASTENING AS REQUIRED
 BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004. NEED TO
 SPECIFY SIZE AND NUMBER OF NAILS TO VERIFY COMPLIANCE
 WITH TILE ATTACHMENT RESISTANCE ON PAGE 4 OF NOA
 02-0916.11 SUBMITTED. PRODUCT APPROVAL IS TO VERIFY
 COMPLIANCE WITH ARCHITECT'S DESIGN CRITERIA.
 NOTE: ATTACHMENT CALCULATIONS SHALL BE DONE AS A MOMENT
 BASED SYSTEM. SEE ITEM #1 ON PAGE 2 OF 6 OF NOA
 SUBMITTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER