Notes
Date Text
2007-05-17 13:44:33** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE:PLEASE SEE PLANS MUST REFLECT CURRENT CODES
 IN EFFECT AND ADOPTED BY THE STATE IN THE SCOPE OF WORK
 AS SHOWN.
 PLEASE KNOW HOWEVER AT THIS TIME AND AS OF DECEMBER
 8TH, 2006 THE STATE IS UNDER THE 2004 FBC W/2006
 REVISIONS. THESE ARE ONLY REVISIONS TO THE 2004 FBC.
 SOME OF THESE ARE STATED ON ELECTRICAL HOWEVER SHOULD
 ALSO BE ON COVER SHEETS.
 WE ARE UNDER THE 2005 NFPA-70. (NEC).
 PLEASE ALSO LIST THE FOLLOWING.
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE FBC R313 AS THE EXISTING DWELLING
 IS REQUIRED TO BE BROUGHT UP TO CODE OR THE EXISTING IS
 TO SHOW MEETING THE CURRENT CODE FOR SMOKE
 DETECTION/SOUNDING DEVICES. PLEASE SHOW A LAYOUT OF THE
 EXISTING DWELLING WHICH WILL REQUIRE SMOKE DEVICES
 INSIDE AND OUTSIDE ALL BEDROOMS AND ON EACH LEVEL IF A
 MULTI-LEVEL BUILDING.
 PLEASE SHOW THE SMOKE DEVICES AS SA OR SD DEPENDING ON
 THE TYPE OF DEVICE. PLEASE SEE THE DEFINITIONS IN
 NFPA-72 OR CALL TO GO OVER.
 NFPA-72 11.5.1.1, 11.8.3
  
 3) NOTE: PLEASE SEE 422.13 AS THE MINIMUM LOADS FOR
 WATER HEATERS IS THAT OF 125%.
  
 4) NOTE: PLEASE PROVIDE MORE INFORMATION ON SERVICE AND
 NEW PANEL BEING FED FROM EXISTING.
 PLEASE INDICATE SIZE OF SERVICE.
 PLEASE INDICATE THE OVER CURRENT PROTECTION WHICH IS
 FEEDING THE NEW PANEL FROM WHAT IS BEING SHOWN ON RISER
 AS AN EXISTING MCB PANEL.
 PLEASE INDICATE LOADS ON THIS EXISTING SERVICE AND THE
 MCB PANEL WHICH IS FEEDING THIS NEW PANEL ALONG WITH
 NEW LOADS.
 PLEASE SEE THE RISER SHOWS THE NEW PANEL, HOWEVER IT IS
 SHOWN WITH WHAT APPEARS TO BE A DISCONNECT AND PANEL IS
 SHOWN AS MLO?
 PLEASE COORDINATE AND CLARIFY ALL OF THE ABOVE. 240.4,
 310.16, 215.5, 230, 220 ETC.
 FBC 106.3.5.4, 106.1.2
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]