| 2007-06-25 13:51:21 | BUILDING REVIEW CHECKLIST: |
| | 1- SPECIFY ALL LIVE AND DEAD LOADS INCLUDINGTHE ATTIC |
| | LIVE LOAD AS REQUIRED BYSEC. R301 AND TABLE R301.5 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 2- SPECIFY BUILDING CONSTRUCTION CLASSIFICATION AS |
| | REQUIRED BY SEC. 602.1 OF FBC 2004. |
| | |
| | 3- ARCHITECT TO SPECIFY ROOF TILEFASTENING AS |
| | REQUIRED BY SEC. 106.1.1.2 OF CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL REQUIRED BY DCA RULE 9B-72 |
| | FOR: |
| | A) SWING DOOR.DESIGN PRESSURES ON PRODUCT APPROVAL |
| | FL2983 SUBMITTED DOESN'T MEET THE ARCHITECT'S |
| | CALCULATED DESIGNED PRESSURES. NEED PRODUCT APPROVAL |
| | THAT EQUALS OR EXCEEDS THE CALCULATED DESIGN |
| | PRESSURES. |
| | |
| | B) WINDOW MULLIONS.SIZE OF MULLION SHOWN ON NOA |
| | 06-0125.06 SUBMITTED DOESN'T MEET THE ARCHITECT'S |
| | CALCULATED DESIGN PRESSURES.NEED PRODUCT APPROVAL |
| | THATEQUALS OR EXCEEDS THE CALCULATED DESIGN |
| | PRESSURES. |
| | |
| | |
| | 5- ARCHITECT NEEDS TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 6- SOIL TEST REPORT NEEDS TO HAVE THE ENGINEERING FIRM |
| | CERTIFICATE OF AUTHORIZATION NUMBER IN THE LETTERHEAD |
| | AS REQUIRED BY SEC. 471.025 FLORIDA STATUTE AND SEC. |
| | 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 7-A) ARCHITECT NEEDS TO UPDATE ALL STRUCTURAL NOTES |
| | REFERENCES SHOWN ON SHEET A-1. SEE CHAPTER 43 OF 2004 |
| | FLORIDARESIDENTIAL CODE FOR PROPER STANDARD AND |
| | EDITION YEAR TO BE USED AS ADOPTED BY THE CODE. |
| | |
| | B) STUCTURAL LUMBER NOTES ARE NOT LEGIBLE. THERE IS |
| | OVERLAPPING INFORMATION. REVISE AS REQUIRED. |
| | |