| Plan Review Notes For Permit 07050351 |
| Permit Number |
07050351 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-31 10:08:50 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FACFLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)YOU HAVE CIRCLED DETAILS FOR BOTH THE 6.8 AND THE | | | HR SHUTTERS.ALSO THERE ARE NUMBERS CIRCLED FOR 47.2, | | | 31.2, CONCRETE (TWO DIFFERENT ANCHOR TYPES) AND HOLLOW | | | BLOCK.THIS JOB IS DESIGNED TO -77PSF.HAVING ITEMS | | | CIRCLED ON THE PRODUCT APPROVAL EXPEDITES THE PLAN | | | REVIEW PROCESS BUT ONLY IF IT IS CONSISTENT WITH THE | | | INSTALLATION SCHEDULE AND SPECIFIC JOB. | | | | | | 2.)SEE OPENING 1.INSTALLATION SCHEDULE SPECIFIES | | | 90" ANCHOR SPACING FOR C1, BUT THE ANCHOR SCHEDULE ON | | | PAGE 7 OF THE PRODUCT APPROVAL REQUIRES 7"". PLEASE | | | CHECK ALL OPENINGS; THERE MAY BE OTHER ERRORS AS I ONLY | | | "SPOT CHECK". |
|