| Plan Review Notes For Permit 07050350 |
| Permit Number |
07050350 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-31 10:05:22 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | | FBC2004 | | | FACFLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)YOU HAVE CIRCLED DETAILS FOR BOTH THE 6.8 AND THE | | | HR SHUTTERS.ALSO THERE ARE NUMBERS CIRCLED FOR 47.2, | | | 31.2, CONCRETE (TWO DIFFERENT ANCHOR TYPES) AND HOLLOW | | | BLOCK.THIS JOB IS DESIGNED TO -77PSF.HAVING ITEMS | | | CIRCLED ON THE PRODUCT APPROVAL EXPEDITES THE PLAN | | | REVIEW PROCESS BUT ONLY IF IT IS CONSISTENT WITH THE | | | INSTALLATION SCHEDULE AND SPECIFIC JOB. | | | | | | 2.)SEE OPENING 3.INSTALLATION SCHEDULE SPECIFIES | | | 8"/7" ANCHOR SPACING FOR C1/C2, BUT THE ANCHOR SCHEDULE | | | ON PAGE 7 OF THE PRODUCT APPROVAL REQUIRES 7"/6". | | | PLEASE CHECK ALL OPENINGS; THERE MAY BE OTHER ERRORS AS | | | I ONLY "SPOT CHECK". |
|