Plan Review Notes
Plan Review Notes For Permit 07050349
Permit Number 07050349
Review Stop B
Sequence Number 2
Notes
Date Text
2007-06-13 09:47:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)ON THE INSTALLATION SCHEDULE, STATE WHICH WALL
 MOUNT YOU ARE USING (CONNECTION TYPES ARE C1 THROUGH
 C5).NOTE THAT C5 REQUIRES 5" ANCHOR SPACING, BUT YOU
 HAVE SPECIFIED 8".AS YOU HAVE NOT STATED WHICH ANCHOR
 TYPE YOU ARE USING (ONLY THAT IT IS A WALL MOUNT), CODE
 COMPLIANCE CANNOT BE DETERMINED.
  
 2.)SHOW DIMENSIONS FROM THE CORNER FOR THE OPENINGS
 WHICH ARE NEAR THE CORNER OF THE BUILDING.FROM THE
 FLOOR PLAN IT APPEARS THAT SOME OPENINGS ARE IN ZONE 5,
 BUT YOU HAVE USED ZONE 4 PRESSURES.
  