Plan Review Notes
Plan Review Notes For Permit 07050297
Permit Number 07050297
Review Stop G
Sequence Number 1
Notes
Date Text
2007-05-22 14:39:38DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET #1:
 A} PLEASE INDICATE THE ADDRESS ON THE RESUBMITTED
 SHEET.
  
 B} PLEASE INDICATE THE BUILDING NUMBER ON THE
 RESUBMITTED SHEET.
  
 C} SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE THE
 CORRESPONDING LENGTHS INDICATED ON THIS SHEET. PLEASE
 CORRECT ON THE RESUBMITTAL
  
 D} SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: PLEASE CORRECT THE TOTAL DISTANCE TO CORRELATE
 WITH WHAT IS CORRECTED ON "C" ON THE RESUBMITTAL.
  
 E} THE PIPING TO THE WATER HEATER IS SIZED WRONG PER
 FBC-2004 FUEL GAS TABLE 402.4(2), IT NEEDS TO BE
 INCREASED TO 1" ON THE RESUBMITTAL.
  
 F} PLEASE PRINT THE NAME OF THE PERSON TAKING
 RESPONSIBILITY OF THE DRAWING UNDER THE SIGNED NAME ON
 THE RESUBMITTAL PER FBC-2004 CHAPTER 1, SECTION
 106.3.4.2.
  
 2. SHEET #2, PLEASE REFERENCE SHEET #1 COMMENTS AND
 CORRECT THE FOLLOWING:
 1A}, 1C}, 1D}, 1E} AND 1F}.
  
 3. SHEET #3, PLEASE REFERENCE SHEET #1 COMMENTS AND
 CORRECT THE FOLLOWING:
 1A}, 1C}, 1D}, 1E} AND 1F}.
  
 4. SHEET #4, PLEASE REFERENCE SHEET #1 COMMENTS AND
 CORRECT THE FOLLOWING:
 1A}, 1B}, 1C}, 1D}, 1E} AND 1F}.
  
 5. SHEET #5, PLEASE REFERENCE SHEET#1 COMMENTS AND
 CORRECT THE FOLLOWING:
 1A}, 1B}, 1C}, 1D}, 1E} AND 1F}.
  
 6. SHEET #6, PLEASE REFERENCE SHEET #1 COMMENTS AND
 CORRECT THE FOLLOWING:
 1A}, 1C}, 1D}, 1E} AND 1F}.
  
 7. SHEET #7, PLEASE REFERENCE SHEET #1 COMMENTS AND
 CORRECT THE FOLLOWING:
 1A}, 1C}, 1D}, 1E} AND 1F}.
  
 8. SHEET #8, PLEASE REFERENCE SHEET #1 COMMENTS AND
 CORRECT THE FOLLOWING:
 1A}, 1B}, 1C}, 1D}, 1E} AND 1F}.
  
 9. UPPER AND LOWER BUILDING F-1 FLOOR PLAN: PLEASE
 CLEARLY INDICATE THE UNIT MODEL AND FLOOR NUMBERS BY
 THE INDICATED GAS METERS ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721