| Date |
Text |
| 2007-05-15 08:33:05 | ** UNSAT ** |
| | |
| | ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| | BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| | BY THE CITY OF WEST PALM BEACH. |
| | |
| | 1) NOTE:PLEASE SEE THAT PLANS ARE REQUIRED TO STATE |
| | ALL RELEVANT CODES WITH RESPECT TO SCOPE OF WORK. |
| | PLEASE SEE THIS PROJECT IS UNDER THE FBC 2004 W/2006 |
| | REVISIONS. |
| | PLEASE ALSO INCLUDE THE 2005 NFPA-70 (NEC) AND THE 2002 |
| | NFPA-72. |
| | |
| | 2) NOTE: PLEASE INDICATE THE NEW CIRCUITS ON A PANEL |
| | SCHEDULE TO BE PROVIDED SHOWING THE EXISTING |
| | SERVICE/PANEL SIZE WITH NEW LOADS AND CIRCUITS BEING |
| | ADDED. |
| | PLEASE CLARIFY THE REQUIRED DEDICATED CIRCUITS FOR EACH |
| | AS SHOWN ON PLANS ALONG WITH THEIR OVER CURRENT |
| | PROTECTION DEVICES, CONDUCTOR SIZES |
| | 310.16, 240.4.408.4. |
| | FBC 106.3.5.4 |
| | |
| | 3) NOTE: PLEASE BE SURE THE BATH IS CIRCUITED PER |
| | 210.52D, 210.11C3 WHICH REQUIRES 20AMP AND #12 AWG. |
| | |
| | 4) NOTE: PLEASE SEE FBC R313 AS THE EXISTING DWELLING |
| | IS REQUIRED TO BE BROUGHT UP TO CODE OR THE EXISTING IS |
| | TO SHOW MEETING THE CURRENT CODE FOR SMOKE |
| | DETECTION/SOUNDING DEVICES. PLEASE SHOW A LAYOUT OF THE |
| | EXISTING DWELLING WHICH WILL REQUIRE SMOKE DEVICES |
| | INSIDE AND OUTSIDE ALL BEDROOMS AND ON EACH LEVEL IF A |
| | MULTI-LEVEL BUILDING. |
| | PLEASE SHOW THE SMOKE DEVICES AS SA OR SD DEPENDING ON |
| | THE TYPE OF DEVICE. PLEASE SEE THE DEFINITIONS IN |
| | NFPA-72 OR CALL TO GO OVER. |
| | NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |