Plan Review Notes
Plan Review Notes For Permit 07050276
Permit Number 07050276
Review Stop E
Sequence Number 1
Notes
Date Text
2007-05-14 12:36:40** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE:PLEASE SEE THAT PLANS ARE REQUIRED TO STATE
 ALL RELEVANT CODES WITH RESPECT TO SCOPE OF WORK.
 PLEASE SEE THIS PROJECT IS UNDER THE FBC 2004 W/2006
 REVISIONS.
 PLEASE ALSO INCLUDE THE 2005 NFPA-70 (NEC) AND THE 2002
 NFPA-72.
  
 2) NOTE: PLEASE SEE THE 2005 NEC 210.8A7 AS ALL
 RECEPTACLES 15/20AMP 125V WITHIN 6FT OF A LAUNDRY TUB
 MUST BE GFI/GFI PROTECTED. THIS REQUIRES EVEN THE
 DEDICATED SINGLE WASHER RECEPTACLE.
  
 3) NOTE: PLEASE SEE THE MISSING DEDICATED BATH CIRCUIT
 PER 210.11C3, 210.52. PLEASE SEE THE PLANS LIST A
 CIRCUIT WHICH PANEL SCHEDULE SHOWS GEN LTS AND
 RECEPTS.
 (MUST BE #12 AND 20AMP.)
  
 4) NOTE: PLEASE SEE FBC R313 AS THE EXISTING DWELLING
 IS REQUIRED TO BE BROUGHT UP TO CODE OR THE EXISTING IS
 TO SHOW MEETING THE CURRENT CODE FOR SMOKE
 DETECTION/SOUNDING DEVICES. PLEASE SHOW A LAYOUT OF THE
 EXISTING DWELLING WHICH WILL REQUIRE SMOKE DEVICES
 INSIDE AND OUTSIDE ALL BEDROOMS AND ON EACH LEVEL IF A
 MULTI-LEVEL BUILDING.
 PLEASE SHOW THE SMOKE DEVICES AS SA OR SD DEPENDING ON
 THE TYPE OF DEVICE.
 NFPA-72 11.5.1.1, 11.8.3
  
 5) NOTE: PLEASE SEE THE EXISTING PANEL *A* WHICH DOES
 NOT FULLY CORRELATE WITH THE LOAD CALCULATIONS. PLEASE
 SEE THERE ARE SOME ITEMS ON LOAD CALCULATIONS WHICH ARE
 NOT LISTED ON PANEL SCHEDULE?
 PLEASE ADJUST.
 NEC 408.4, 220
 FBC 106.3.5.4, 106.1.2
  
 6) NOTE: PLEASE VERIFY THE EXISTING AHU AS THE HEAT
 STRIP IS SHOWN AS 5.5KW, YET THE OVER CURRENT
 PROTECTION IS SHOWN AT 60AMPS WHICH IS TOO HIGH. PLEASE
 ALSO COORDINATE THE LOAD ON THE PANEL AND THE LOAD
 CALCULATIONS. PLEASE SEE THE PANEL SCHEDULE SHOWS BOTH
 5.5 KW AND 1.0 KVA?
 PLEASE ADJUST.
 220, 408.4, 240.4
 FBC 106.1.2, 106.3.5.4
  
 7) NOTE: PLEASE COORDINATE THE FEEDERS FROM THE
 EXISTING PANEL *A* TO EXISTING PANEL *B*. PANEL A SHOWS
 #8 AND ON A 2-POLE 50AMP BREAKER AND A TOTAL LOAD OF
 1.1KVA?
 PLEASE SEE THE LOAD ON PANEL *B* EXCEED THIS LOAD OF
 1.1KVA.
 PLEASE SEE THE RISER SHOWS #6 FOR FEEDERS AND ALSO
 SHOWS 60AMP.
 PLEASE SEE THE PANEL *B* ON RISER AND PANEL SCHEDULE
 SHOW THIS PANEL AS (MLO) MAIN LUG ONLY WHEN IT SHOULD
 INDICATE (MCB) MAIN CIRCUIT BREAKER. 220.31
  
 8) NOTE: PLEASE CLARIFY THE LOAD ON JACUZZI AS THIS IS
 SHOWN ON A 2-POLE 40AMP BREAKER YET THE LOAD IS ONLY AT
 1.1 KVA? PLEASE ADJUST THE CONDUCTOR AND OVER CURRENT
 PROTECTION SIZE OR ADJUST LOAD IF INDEED THE LOAD IS
 HIGHER.
 PLEASE SEE THAT THE CODE DOES LIMIT THE OVER CURRENT
 PROTECTION EITHER BY THE MANUFACTURE, LISTINGS FOR
 MOTOR LOADS AND/OR 150%.
 422.11, 110.3, 240.4, 310.16, 220 ETC.
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE
 CONNECTION TO NEW FOOTER STEEL PER 250.50. PLEASE ALSO
 CLARIFY EXISTING OR NEW CONNECTION TO COLD WATER AND
 GAS LINE BOND.(LOAD SIDE OF METER).
 250.104
  
 10) NOTE: PLEASE SEE PANELS ARE BOTH LISTED AT
 42CIRCUITS, HOWEVER PANEL *A* IS BEING SHOWN AS 30POLES
 AND PANEL *B* IS BEING SHOWN AS 18.
 PLEASE COORDINATE.
 FBC 106.3.5.4, 106.1.2
  
 11) NOTE: PLEASE SEE THE VALUE AS STATED ON PERMIT
 APPLICATION IS LOW AND WILL NEED TO MEET THE MINIMUM
 VALUES AS SET-FORTH IN THE FBC AND ICC TABLES.
 THIS MAY ALSO BE PRESENT IN BUILDING REVIEW COMMENTS.
 FBC 108.3
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717