| 2007-05-14 12:36:40 | ** UNSAT ** |
| | |
| | ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| | BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| | BY THE CITY OF WEST PALM BEACH. |
| | |
| | 1) NOTE:PLEASE SEE THAT PLANS ARE REQUIRED TO STATE |
| | ALL RELEVANT CODES WITH RESPECT TO SCOPE OF WORK. |
| | PLEASE SEE THIS PROJECT IS UNDER THE FBC 2004 W/2006 |
| | REVISIONS. |
| | PLEASE ALSO INCLUDE THE 2005 NFPA-70 (NEC) AND THE 2002 |
| | NFPA-72. |
| | |
| | 2) NOTE: PLEASE SEE THE 2005 NEC 210.8A7 AS ALL |
| | RECEPTACLES 15/20AMP 125V WITHIN 6FT OF A LAUNDRY TUB |
| | MUST BE GFI/GFI PROTECTED. THIS REQUIRES EVEN THE |
| | DEDICATED SINGLE WASHER RECEPTACLE. |
| | |
| | 3) NOTE: PLEASE SEE THE MISSING DEDICATED BATH CIRCUIT |
| | PER 210.11C3, 210.52. PLEASE SEE THE PLANS LIST A |
| | CIRCUIT WHICH PANEL SCHEDULE SHOWS GEN LTS AND |
| | RECEPTS. |
| | (MUST BE #12 AND 20AMP.) |
| | |
| | 4) NOTE: PLEASE SEE FBC R313 AS THE EXISTING DWELLING |
| | IS REQUIRED TO BE BROUGHT UP TO CODE OR THE EXISTING IS |
| | TO SHOW MEETING THE CURRENT CODE FOR SMOKE |
| | DETECTION/SOUNDING DEVICES. PLEASE SHOW A LAYOUT OF THE |
| | EXISTING DWELLING WHICH WILL REQUIRE SMOKE DEVICES |
| | INSIDE AND OUTSIDE ALL BEDROOMS AND ON EACH LEVEL IF A |
| | MULTI-LEVEL BUILDING. |
| | PLEASE SHOW THE SMOKE DEVICES AS SA OR SD DEPENDING ON |
| | THE TYPE OF DEVICE. |
| | NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | 5) NOTE: PLEASE SEE THE EXISTING PANEL *A* WHICH DOES |
| | NOT FULLY CORRELATE WITH THE LOAD CALCULATIONS. PLEASE |
| | SEE THERE ARE SOME ITEMS ON LOAD CALCULATIONS WHICH ARE |
| | NOT LISTED ON PANEL SCHEDULE? |
| | PLEASE ADJUST. |
| | NEC 408.4, 220 |
| | FBC 106.3.5.4, 106.1.2 |
| | |
| | 6) NOTE: PLEASE VERIFY THE EXISTING AHU AS THE HEAT |
| | STRIP IS SHOWN AS 5.5KW, YET THE OVER CURRENT |
| | PROTECTION IS SHOWN AT 60AMPS WHICH IS TOO HIGH. PLEASE |
| | ALSO COORDINATE THE LOAD ON THE PANEL AND THE LOAD |
| | CALCULATIONS. PLEASE SEE THE PANEL SCHEDULE SHOWS BOTH |
| | 5.5 KW AND 1.0 KVA? |
| | PLEASE ADJUST. |
| | 220, 408.4, 240.4 |
| | FBC 106.1.2, 106.3.5.4 |
| | |
| | 7) NOTE: PLEASE COORDINATE THE FEEDERS FROM THE |
| | EXISTING PANEL *A* TO EXISTING PANEL *B*. PANEL A SHOWS |
| | #8 AND ON A 2-POLE 50AMP BREAKER AND A TOTAL LOAD OF |
| | 1.1KVA? |
| | PLEASE SEE THE LOAD ON PANEL *B* EXCEED THIS LOAD OF |
| | 1.1KVA. |
| | PLEASE SEE THE RISER SHOWS #6 FOR FEEDERS AND ALSO |
| | SHOWS 60AMP. |
| | PLEASE SEE THE PANEL *B* ON RISER AND PANEL SCHEDULE |
| | SHOW THIS PANEL AS (MLO) MAIN LUG ONLY WHEN IT SHOULD |
| | INDICATE (MCB) MAIN CIRCUIT BREAKER. 220.31 |
| | |
| | 8) NOTE: PLEASE CLARIFY THE LOAD ON JACUZZI AS THIS IS |
| | SHOWN ON A 2-POLE 40AMP BREAKER YET THE LOAD IS ONLY AT |
| | 1.1 KVA? PLEASE ADJUST THE CONDUCTOR AND OVER CURRENT |
| | PROTECTION SIZE OR ADJUST LOAD IF INDEED THE LOAD IS |
| | HIGHER. |
| | PLEASE SEE THAT THE CODE DOES LIMIT THE OVER CURRENT |
| | PROTECTION EITHER BY THE MANUFACTURE, LISTINGS FOR |
| | MOTOR LOADS AND/OR 150%. |
| | 422.11, 110.3, 240.4, 310.16, 220 ETC. |
| | FBC 106.1.2 |
| | |
| | 9) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE |
| | CONNECTION TO NEW FOOTER STEEL PER 250.50. PLEASE ALSO |
| | CLARIFY EXISTING OR NEW CONNECTION TO COLD WATER AND |
| | GAS LINE BOND.(LOAD SIDE OF METER). |
| | 250.104 |
| | |
| | 10) NOTE: PLEASE SEE PANELS ARE BOTH LISTED AT |
| | 42CIRCUITS, HOWEVER PANEL *A* IS BEING SHOWN AS 30POLES |
| | AND PANEL *B* IS BEING SHOWN AS 18. |
| | PLEASE COORDINATE. |
| | FBC 106.3.5.4, 106.1.2 |
| | |
| | 11) NOTE: PLEASE SEE THE VALUE AS STATED ON PERMIT |
| | APPLICATION IS LOW AND WILL NEED TO MEET THE MINIMUM |
| | VALUES AS SET-FORTH IN THE FBC AND ICC TABLES. |
| | THIS MAY ALSO BE PRESENT IN BUILDING REVIEW COMMENTS. |
| | FBC 108.3 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |