| Plan Review Notes For Permit 07050247 |
| Permit Number |
07050247 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-17 07:55:18 | | | | | | | PROVISO | | | | | | 680.26(B)(5) METAL WIRING METHODS AND EQUIPMENT. | | | METAL-SHEATHED CABLES AND RACEWAYS, METAL PIPING, AND | | | ALL FIXED METAL PARTS EXCEPT THOSE SEPARATED FROM THE | | | POOL BY A PERMANENT BARRIER SHALL BE BONDED THAT ARE | | | WITHIN THE FOLLOWING DISTANCES OF THE POOL: | | | EXAMPLES OF FIXED METAL PARTS BOUND BY THIS REQUIREMENT | | | INCLUDE METAL FENCES, METAL AWNINGS, METAL DOOR FRAMES, | | | AND METAL WINDOW FRAMES. | | | (1) WITHIN 1.5 M (5 FT) HORIZONTALLY OF THE INSIDE | | | WALLS OF THE POOL | | | (2) WITHIN 3.7 M (12 FT) MEASURED VERTICALLY ABOVE THE | | | MAXIMUM WATER LEVEL OF THE POOL, OR ANY OBSERVATION | | | STANDS, TOWERS, OR PLATFORMS, OR ANY DIVING | | | STRUCTURES. | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|