Plan Review Notes
Plan Review Notes For Permit 07050242
Permit Number 07050242
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-05 07:20:12 
  
  
 PROVISO
  
 . PLEASE RESUBMIT A REVISION SHOWING ACTUAL CONDITIONS
 PRIOR TO CALLING ROUGH ELECTRICAL INSPECTION.
  
 1}SEE REDLINED PLANS. THESE REQUIREMENTS ARE FOR
 SPACING PER ARTICLES LISTED ON THE PLAN.
  
 2} THE "BREAKFAST ROOM RECEPTACLES MUST COMPLY WITH
 ARTICLE 210.52(B)(1), THE OUTSIDE GFI CANNOT BE ON THE
 REQUIRED SMALL APPLIANCE CIRCUIT PER 210.52(B)(3).
  
 3} PER R313.1(3) FBC RESIDENTIAL, A SMOKE ALARM IS
 REQUIRED ON THE FIRST FLOOR, SEE EXCEPTION ALLOWING A
 BATTERY OPERATED, NON-INTERCONNECTED, UNIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718