| 2008-03-13 16:04:33 | ** DENIED3RD REVIEW ** |
| | |
| | ** PLEASE SEE THE NOTES BELOW WHICH ARE FROM THE FIRST |
| | TWO REVIEWS WHICH STILL NEED TO BE ADDRESSED. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | SUBMITTED DO NOT CORRELATE WITH THE PLANS. PLEASE SEE |
| | THERE ARE SEVERAL FIXTURES ON PLANS WHICH ARE NOT IN |
| | THE INPUT DATA REPORTS OR SUMMARY SHEETS. |
| | |
| | A) THE PREVIOUS REVIEWS SPECIFICALLY MENTIONED THERE |
| | WERE MISSING FIXTURES AND EVEN NOTED SPECIFICALLY THE |
| | LIGHTING SHOWN ON ESP -1 WAS NOT IN THE INPUT DATA |
| | REPORT. |
| | PLEASE SEE THE NEW ENERGY CALCULATIONS SUBMITTED STILL |
| | DO NOT CORRELATE WITH THE PLANS. |
| | PLEASE SEE THE LIGHTING ON ESP-1IS NOT PLACED IN THE |
| | IDR. |
| | WHERE IS THE 1500WATT UP LIGHTS? THERE ARE 4 1500W |
| | FIXTURES ON PLANS HOWEVER NONE ARE ON THE IDR. |
| | WHERE ARE THE 100WATT BOLLARDS?THERE ARE 19 100W |
| | FIXTURES ON PLANS HOWEVER NONE ARE ON THE IDR. |
| | WHERE ARE THE WALL-PACKS? SOME 100W FIXTURES APPEAR ON |
| | THE IDR, HOWEVER IT IS UNCLEAR WHICH FIXTURES ARE ON |
| | THE IDR. |
| | PLEASE SEE ESP-1 SHOWS TWO WALL PACKS AND EACH OF THESE |
| | ON PLANS CALL FOR 100W FIXTURES, HOWEVER SHEET E-4 |
| | INDICATES TWO OTHER OUTSIDE FIXTURES WHICH ARE BOTH |
| | IDENTIFIED AS *I*, YET THE FIXTURE LEGEND WHICH SHOWS |
| | THE *I* FIXTURES CALLS FOR THESE AS ELEVATOR PIT |
| | LIGHTS. |
| | PLEASE SEE THE COUNT FOR *D* FIXTURES, NOTES 16 TOTAL, |
| | HOWEVER COULD NOT LOCATE 16 ON PLANS. |
| | PLEASE EXPLAIN WHERE THE FUTURE SIGN LIGHTING WATTAGE |
| | IS PART OF THE ASSUMPTIONS. PLEASE SEE 13-415.2.ABC.1.3 |
| | AS ONLY LIGHTING WHICH IS AN INTEGRAL PART OF THE SIGN |
| | IS EXEMPT. AS NO SIGNAGE INFORMATION IS SHOWN AT THIS |
| | TIME IT IS NOT KNOWN WHETHER OR NOT THIS IS EXEMPT OR |
| | REQUIRED. |
| | |
| | ** PLEASE GO OVER ALL OF THESE FIXTURES AND COORDINATE |
| | WITH THE EXTERIOR LIGHTING ON THE INPUT DATA REPORTS |
| | AND SUMMARY SHEETS. |
| | |
| | B) PLEASE SEE SHEET E-4 WHICH NOTES TABLE 13-415.2.C.1 |
| | AND 13-415.2.C.1 TWICE ON THE TOP OF THE LIGHTING |
| | CALCULATIONS TABLE.HOW IS *C* BEING SHOWN WHEN *B* |
| | METHOD IS SUBMITTED. |
| | PLEASE SEE THE INPUT DATA REPORT AND COMPLIANCE SUMMARY |
| | SHEETS FOR INTERIOR LIGHTING WHICH SHOWS A DIFFERENT |
| | TOTAL THAN THE LIGHTING WATTAGE TOTALS SHOWN ON E-4. |
| | ?? |
| | PLEASE SEE FOR EXAMPLE; |
| | SHEET E-4 SHOWS A TOTAL OF 26, 411 WATTS YET THE |
| | SUMMARY SHEETS 2 OF 14 AND 7 OF 14 SHOWS A TOTAL OF |
| | 21021 WATTS TOTAL. |
| | SINCE THE MAXIMUM ALLOWANCE AS LISTED IS 26153 THIS |
| | WOULD PLACE THE LIGHTING DESIGNED OVER THE ALLOWANCE |
| | FOR CONSUMPTION. |
| | PLEASE ALSO SEE 13-415.2.ABC.1.1, .1.2 AND .1.3 AS THE |
| | LIGHTING WATTAGE WHICH IS REQUIRED TO BE USED IS THE |
| | MAXIMUM VA/WATTAGE OF THE FIXTURE, NOT THE BULB. |
| | FOR EXAMPLE: PLEASE SEE THE TRACK FIXTURES WHICH BY THE |
| | FIXTURE LEGEND, IDR AND CALCULATIONS ON PLANS FIGURE A |
| | WATTAGE OF 40W PER FIXTURE. PLEASE SEE THE FIXTURE |
| | LEGEND WHICH INDICATES 150W FIXTURES. THE FIXTURE |
| | WATTAGE NOT BULB IS TO BE FIGURED. |
| | THIS IS FOR ALL FIXTURES. IF A FIXTURE EFFICIENCY |
| | RATING IS HIGHER THEN THE VA/WATTAGE PLACED INTO THE |
| | IDR MAY BE THAT OF THE LOWER RATING OF THE BALLAST |
| | OUTPUT. THIS MAY HELP DEPENDING ON THE TYPE OF FIXTURES |
| | SPECIFIED AS THE TOTALS SHOWN ARE OVER ALLOWANCES. |
| | |
| | ** IMPORTANT, PLEASE BE SURE TO GO OVER ALL LIGHTING ON |
| | PLANS AND COORDINATE WITH THE INPUT DATA REPORTS AND |
| | SUMMARY SHEETS BEFORE RESUBMITTING PLANS. |
| | 13-415.1.AB.1, 13-415.1.A, 13-415.1.B, 13-415.2,ETC. |
| | |
| | 2) NOTE: PLEASE SEE NEW SWITCH DESIGNATIONWHICH NOW |
| | INDICATES OCCUPANCY WHICH IS OK, NEEDS TO SHOW A |
| | MAXIMUM OF 30MINS. |
| | 13-415.1.ABC.1.1 AND .1.2. |
| | THIS ITEM COULD HAVE BEEN RED-LINED, HOWEVER PLANS ARE |
| | COMING BACK FOR OTHER COMMENTS. |
| | |
| | 3) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE |
| | SEE SECTIONS OF FBC AND CHAPTER 13 HAVE BEEN GIVEN |
| | SINCE THE INITIAL REVIEW AND NOTES WERE GIVEN WHICH |
| | SPECIFICALLY STATED THERE WERE SEVERAL FIXTURES ON |
| | PLANS WHICH DID NOT CORRELATE WITH THE ENERGY |
| | CALCULATIONS SUBMITTED. PLEASE SEE NOTES EVEN GAVE |
| | ENTIRE PAGES WHICH WERE NOT ON THE CALCULATIONS |
| | SUBMITTED. |
| | AS REQUIRED BY THE FLORIDA STATUE ABOVE A FEE AS |
| | REQUIRED UNDER SAID STATUTE HAS NOW BEEN ASSESSED. THE |
| | FLORIDA STATUTE REQUIRES THIS FEE AND REQUIRES THIS FEE |
| | TO BE PAID BEFORE THE NEXT RESUBMISSION OF PLANS. |
| | THE STATUTE ASSESSES THIS FEE TO THE DESIGNER AND NOT |
| | TO THE CONTRACTOR OR OWNER OF SAID PROJECT. |
| | THE FEE OF IS THE PORTION OF THE BASE PERMIT FEE |
| | ATTRIBUTED TOWARDS PLAN REVIEW TIMES FOUR. THE FEE DUE |
| | WILL BE $54, 600.00 AT NEXT RE-SUBMITTAL. THE 10% |
| | RE-SUB FEE WOULD NOT BE DUE, ONLY THE STATUTE REQUIRED |
| | PENALTY. |
| | ONE SET OF ENERGY CALCULATIONS AND ONE SET OF |
| | ELECTRICAL LIGHTING PLANS SHEETS ESP-1, E-1, E-4 AND E5 |
| | HAVE NOW BEEN RETAINED BY THIS OFFICE. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |