Plan Review Notes
Plan Review Notes For Permit 07050239
Permit Number 07050239
Review Stop E
Sequence Number 3
Notes
Date Text
2008-03-13 16:04:33** DENIED3RD REVIEW **
  
 ** PLEASE SEE THE NOTES BELOW WHICH ARE FROM THE FIRST
 TWO REVIEWS WHICH STILL NEED TO BE ADDRESSED.
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 SUBMITTED DO NOT CORRELATE WITH THE PLANS. PLEASE SEE
 THERE ARE SEVERAL FIXTURES ON PLANS WHICH ARE NOT IN
 THE INPUT DATA REPORTS OR SUMMARY SHEETS.
  
 A) THE PREVIOUS REVIEWS SPECIFICALLY MENTIONED THERE
 WERE MISSING FIXTURES AND EVEN NOTED SPECIFICALLY THE
 LIGHTING SHOWN ON ESP -1 WAS NOT IN THE INPUT DATA
 REPORT.
 PLEASE SEE THE NEW ENERGY CALCULATIONS SUBMITTED STILL
 DO NOT CORRELATE WITH THE PLANS.
 PLEASE SEE THE LIGHTING ON ESP-1IS NOT PLACED IN THE
 IDR.
 WHERE IS THE 1500WATT UP LIGHTS? THERE ARE 4 1500W
 FIXTURES ON PLANS HOWEVER NONE ARE ON THE IDR.
 WHERE ARE THE 100WATT BOLLARDS?THERE ARE 19 100W
 FIXTURES ON PLANS HOWEVER NONE ARE ON THE IDR.
 WHERE ARE THE WALL-PACKS? SOME 100W FIXTURES APPEAR ON
 THE IDR, HOWEVER IT IS UNCLEAR WHICH FIXTURES ARE ON
 THE IDR.
 PLEASE SEE ESP-1 SHOWS TWO WALL PACKS AND EACH OF THESE
 ON PLANS CALL FOR 100W FIXTURES, HOWEVER SHEET E-4
 INDICATES TWO OTHER OUTSIDE FIXTURES WHICH ARE BOTH
 IDENTIFIED AS *I*, YET THE FIXTURE LEGEND WHICH SHOWS
 THE *I* FIXTURES CALLS FOR THESE AS ELEVATOR PIT
 LIGHTS.
 PLEASE SEE THE COUNT FOR *D* FIXTURES, NOTES 16 TOTAL,
 HOWEVER COULD NOT LOCATE 16 ON PLANS.
 PLEASE EXPLAIN WHERE THE FUTURE SIGN LIGHTING WATTAGE
 IS PART OF THE ASSUMPTIONS. PLEASE SEE 13-415.2.ABC.1.3
 AS ONLY LIGHTING WHICH IS AN INTEGRAL PART OF THE SIGN
 IS EXEMPT. AS NO SIGNAGE INFORMATION IS SHOWN AT THIS
 TIME IT IS NOT KNOWN WHETHER OR NOT THIS IS EXEMPT OR
 REQUIRED.
  
 ** PLEASE GO OVER ALL OF THESE FIXTURES AND COORDINATE
 WITH THE EXTERIOR LIGHTING ON THE INPUT DATA REPORTS
 AND SUMMARY SHEETS.
  
 B) PLEASE SEE SHEET E-4 WHICH NOTES TABLE 13-415.2.C.1
 AND 13-415.2.C.1 TWICE ON THE TOP OF THE LIGHTING
 CALCULATIONS TABLE.HOW IS *C* BEING SHOWN WHEN *B*
 METHOD IS SUBMITTED.
 PLEASE SEE THE INPUT DATA REPORT AND COMPLIANCE SUMMARY
 SHEETS FOR INTERIOR LIGHTING WHICH SHOWS A DIFFERENT
 TOTAL THAN THE LIGHTING WATTAGE TOTALS SHOWN ON E-4.
 ??
 PLEASE SEE FOR EXAMPLE;
 SHEET E-4 SHOWS A TOTAL OF 26, 411 WATTS YET THE
 SUMMARY SHEETS 2 OF 14 AND 7 OF 14 SHOWS A TOTAL OF
 21021 WATTS TOTAL.
 SINCE THE MAXIMUM ALLOWANCE AS LISTED IS 26153 THIS
 WOULD PLACE THE LIGHTING DESIGNED OVER THE ALLOWANCE
 FOR CONSUMPTION.
 PLEASE ALSO SEE 13-415.2.ABC.1.1, .1.2 AND .1.3 AS THE
 LIGHTING WATTAGE WHICH IS REQUIRED TO BE USED IS THE
 MAXIMUM VA/WATTAGE OF THE FIXTURE, NOT THE BULB.
 FOR EXAMPLE: PLEASE SEE THE TRACK FIXTURES WHICH BY THE
 FIXTURE LEGEND, IDR AND CALCULATIONS ON PLANS FIGURE A
 WATTAGE OF 40W PER FIXTURE. PLEASE SEE THE FIXTURE
 LEGEND WHICH INDICATES 150W FIXTURES. THE FIXTURE
 WATTAGE NOT BULB IS TO BE FIGURED.
 THIS IS FOR ALL FIXTURES. IF A FIXTURE EFFICIENCY
 RATING IS HIGHER THEN THE VA/WATTAGE PLACED INTO THE
 IDR MAY BE THAT OF THE LOWER RATING OF THE BALLAST
 OUTPUT. THIS MAY HELP DEPENDING ON THE TYPE OF FIXTURES
 SPECIFIED AS THE TOTALS SHOWN ARE OVER ALLOWANCES.
  
 ** IMPORTANT, PLEASE BE SURE TO GO OVER ALL LIGHTING ON
 PLANS AND COORDINATE WITH THE INPUT DATA REPORTS AND
 SUMMARY SHEETS BEFORE RESUBMITTING PLANS.
 13-415.1.AB.1, 13-415.1.A, 13-415.1.B, 13-415.2,ETC.
  
 2) NOTE: PLEASE SEE NEW SWITCH DESIGNATIONWHICH NOW
 INDICATES OCCUPANCY WHICH IS OK, NEEDS TO SHOW A
 MAXIMUM OF 30MINS.
 13-415.1.ABC.1.1 AND .1.2.
 THIS ITEM COULD HAVE BEEN RED-LINED, HOWEVER PLANS ARE
 COMING BACK FOR OTHER COMMENTS.
  
 3) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE
 SEE SECTIONS OF FBC AND CHAPTER 13 HAVE BEEN GIVEN
 SINCE THE INITIAL REVIEW AND NOTES WERE GIVEN WHICH
 SPECIFICALLY STATED THERE WERE SEVERAL FIXTURES ON
 PLANS WHICH DID NOT CORRELATE WITH THE ENERGY
 CALCULATIONS SUBMITTED. PLEASE SEE NOTES EVEN GAVE
 ENTIRE PAGES WHICH WERE NOT ON THE CALCULATIONS
 SUBMITTED.
 AS REQUIRED BY THE FLORIDA STATUE ABOVE A FEE AS
 REQUIRED UNDER SAID STATUTE HAS NOW BEEN ASSESSED. THE
 FLORIDA STATUTE REQUIRES THIS FEE AND REQUIRES THIS FEE
 TO BE PAID BEFORE THE NEXT RESUBMISSION OF PLANS.
 THE STATUTE ASSESSES THIS FEE TO THE DESIGNER AND NOT
 TO THE CONTRACTOR OR OWNER OF SAID PROJECT.
 THE FEE OF IS THE PORTION OF THE BASE PERMIT FEE
 ATTRIBUTED TOWARDS PLAN REVIEW TIMES FOUR. THE FEE DUE
 WILL BE $54, 600.00 AT NEXT RE-SUBMITTAL. THE 10%
 RE-SUB FEE WOULD NOT BE DUE, ONLY THE STATUTE REQUIRED
 PENALTY.
 ONE SET OF ENERGY CALCULATIONS AND ONE SET OF
 ELECTRICAL LIGHTING PLANS SHEETS ESP-1, E-1, E-4 AND E5
 HAVE NOW BEEN RETAINED BY THIS OFFICE.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  