2008-01-11 14:22:43REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THROUGH 6: OK
  
 7: AHU 4 STILL HAS A DESIGN CAPACITY IN EXCESS OF 2000
 CFM. FAN SHUT DOWN BY SMOKE DETECTOR IS REQUIRED PER
 FBC, M 606.2.1.
  
 8. THE CONDITION OF DRAIN LINES HAS NOT CHANGED FROM
 PREVIOUS SUBMITTAL. THE DRAIN CONFIGURATION SHOWN ON
 PLANS IS ACCEPTABLE PENDING FIELD INSPECTOR?S
 APPROVIAL.
  
 9. WHILE FILTER ACCESS IS IMPORTANT, THE PRIMARY
 CONCERN IS ACCESS FOR SERVICE AND REPLACEMENT. VERIFY
 COMPLIANCE WITH FBC, M 306.1 AND 306.2. MANUFACTURER?S
 INSTALLATION INSTRUCTIONS SHALL BE AVAILABLE ON THE JOB
 SITE AT THE TIME OF INSPECTION IN ACCORDANCE WITH FBC,
 M 304.1.
  
 10. SEE COMMENT #7 ABOVE.
  
 11. THE FAN SCHEDULE ON PG M-5 STILL SHOWS EF-2 THROUGH
 EF-6 ON ROOF. PLEASE CLARIFY PER FBC, M 306.5 AND FBC
 106.1.1.
  
 12 THROUGH 14: OK
  
 15. THE NEW ENERGY CALCULATIONS SUBMITTED ARE V2.11
 FORM 400B. ALL APPLICATIONS SUBMITTED AFTER 12/8/2006
 USING METHOD B FORMS ARE REQUIRED TO USE AT LEAST V2.5
 IN ACCORDANCE WITH FBC 13-400.3.B. PLEASE USE THE
 CURRENT VERSION OF THE FLA/COM PROGRAM AND RESUBMIT.
  
 NEW: PAGES M-1 THROUGH M-6 ARE NOT SIGNED, DATED OR
 SEALED BY THE DESIGNER OF RECORD AS REQUIRED BY FS 471
 AND FAC RULE 61G15-23.001. PLEASE MAKE SURE ALL PLANS
 ARE SIGNED, SEALED AND DATED PRIOR TO RESUBMITTAL.
  