| 2008-01-11 14:22:43 | REVIEW #: 2ND |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1 THROUGH 6: OK |
| | |
| | 7: AHU 4 STILL HAS A DESIGN CAPACITY IN EXCESS OF 2000 |
| | CFM. FAN SHUT DOWN BY SMOKE DETECTOR IS REQUIRED PER |
| | FBC, M 606.2.1. |
| | |
| | 8. THE CONDITION OF DRAIN LINES HAS NOT CHANGED FROM |
| | PREVIOUS SUBMITTAL. THE DRAIN CONFIGURATION SHOWN ON |
| | PLANS IS ACCEPTABLE PENDING FIELD INSPECTOR?S |
| | APPROVIAL. |
| | |
| | 9. WHILE FILTER ACCESS IS IMPORTANT, THE PRIMARY |
| | CONCERN IS ACCESS FOR SERVICE AND REPLACEMENT. VERIFY |
| | COMPLIANCE WITH FBC, M 306.1 AND 306.2. MANUFACTURER?S |
| | INSTALLATION INSTRUCTIONS SHALL BE AVAILABLE ON THE JOB |
| | SITE AT THE TIME OF INSPECTION IN ACCORDANCE WITH FBC, |
| | M 304.1. |
| | |
| | 10. SEE COMMENT #7 ABOVE. |
| | |
| | 11. THE FAN SCHEDULE ON PG M-5 STILL SHOWS EF-2 THROUGH |
| | EF-6 ON ROOF. PLEASE CLARIFY PER FBC, M 306.5 AND FBC |
| | 106.1.1. |
| | |
| | 12 THROUGH 14: OK |
| | |
| | 15. THE NEW ENERGY CALCULATIONS SUBMITTED ARE V2.11 |
| | FORM 400B. ALL APPLICATIONS SUBMITTED AFTER 12/8/2006 |
| | USING METHOD B FORMS ARE REQUIRED TO USE AT LEAST V2.5 |
| | IN ACCORDANCE WITH FBC 13-400.3.B. PLEASE USE THE |
| | CURRENT VERSION OF THE FLA/COM PROGRAM AND RESUBMIT. |
| | |
| | NEW: PAGES M-1 THROUGH M-6 ARE NOT SIGNED, DATED OR |
| | SEALED BY THE DESIGNER OF RECORD AS REQUIRED BY FS 471 |
| | AND FAC RULE 61G15-23.001. PLEASE MAKE SURE ALL PLANS |
| | ARE SIGNED, SEALED AND DATED PRIOR TO RESUBMITTAL. |
| | |