2008-01-02 13:53:22FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE SHOW STORM WATER QUALITY CALCULATIONS, WHAT
 CRITERIA YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER
 ENTIRE SITE OR2.5"CRITERIA, ETC? STORM WATER
 QUALITY CALS MUST BE APPROVED FROM 100045TH STREET,
 ENG SERVICES, BEFORE WE APPROVED.
 RESPONSE TO YOUR LETTER 9/19/07: AS YOU STATED IN YOUR
 LETTER 9/19/07 THAT "WATER QUALITY (2.5") IS BEING
 PROVIDED...." WE WILL REVIEW AGAIN WHEN YOU PROVIDE
 CALS.
  
 2. PLEASE APPLY & GET AN APPROVAL FROM FDEP FOR NOTICE
 OF INTENT (NOI), PROVIDE A COPY OF APPROVAL FROM FDEP
 FOR NOI.
  
 3. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  