Plan Review Notes
Plan Review Notes For Permit 07050239
Permit Number 07050239
Review Stop E
Sequence Number 2
Notes
Date Text
2008-01-01 16:53:322008-01-01 16:53:32
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE FBC CHAPTER 13. PLEASE SEE THE
 CALCULATIONS SUBMITTED ARE NO LONGER IN EFFECT FOR THE
 STATE OF FLORIDA AND FLORIDA BUILDING CODE. PLEASE AS
 OF DECEMBER 6TH, 2006 THE 2004 FBC CHANGED WHICH
 INCLUDED THE 2006 REVISIONS. PLEASE SEE 13-400.0.A,
 13-415.1.A, .1.B, 13-415.2, 13-400.3.A. THE VERSION
 SUBMITTED IS 2.11 AND THE REQUIRED VERSION IS 2.5.
 PLEASE KNOW THE 2.5 WITH ENERGY GAUGE SUMMIT 3.1 IS
 ACCEPTABLE AS LONG AS THE VERSION IS 2.5.
 PLEASE VERIFY A METHOD *B* BEING SUBMITTED. THIS WILL
 BE IN MECHANICAL REVIEW. PLEASE SEE THE TABLES SHOWN ON
 PLANS FOR LIGHTING PERFORMANCE CALCULATIONS STATE
 METHOD *C*.
 THIS IS A NEW WHOLE BUILDING.
 PLEASE SEE THE CALCULATIONS SUBMITTED ARE ALSO NOT
 SIGNED, DATED OR SEALED BY THE RESPONSIBLE LICENSED
 DESIGNER OF RECORD.
 PLEASE SEE 13-103.1.1.1, FS 471.025.
 PLEASE CLARIFY HOW SOME OF THE METHOD OF CONTROLS ARE
 STILL BEING SHOWN AS MANUAL ON/OFF WHEN THE DEVICE ON
 PLANS IS CLEARLY AN AUTOMATED TYPE DEVICE.?
 FOR EXAMPLE: PLEASE SEE JAN 131, STOR. 132 ETC
 FOR EXAMPLE: PLEASE SEE THE LIGHTING ON SHEET ESP-1
 COULD NOT BE LOCATED IN THE INPUT DATA REPORT SUBMITTED
 FOR EXTERIOR LIGHTING?
 PLEASE SUBMIT CALCULATIONS ACCORDINGLY AND ADJUST ALL
 INPUTS.
  
 2) NOTE: PLEASE SEE PREVIOUS COMMENT WITH RESPECT TO
 SERVICE AND 230.2, 22531-225.39, 230.72 ETC. THE
 COMMENT WAS NOT THAT THE NEW STRUCTURE DOES NOT FALL
 UNDER THE DESIGN AND CONSIDERED AS A SEPARATE BUILDING.
 THIS WAS GONE OVER IN A MEETING BEFORE PLANS
 RESUBMITTED.THE CONCERN IS THAT ANY ELECTRICAL
 SYSTEMS OF ANY VOLTAGE WOULD BE FED INTO THIS BUILDING
 FROM THE PRESENT EXISTING STRUCTURE WHICH WOULD PLACE
 NOT ONLY ELECTRICAL FED FROM MULTIPLE SOURCES BUT WOULD
 BE SYSTEMS FROM MORE THAN ONE FPL TRANSFORMER.
 THE ELECTRICAL DESIGNER OF RECORD WAS NOT PRESENT AND
 THE ARCHITECT IN MEETING MENTIONED THE DESIGNER OF
 RECORD WOULD CONTACT THIS OFFICE/REVIEWER TO GO OVER
 COMMENTS AND CONCERNS. NO CONTACT WAS MADE TO THIS
 REVIEWER TO GO OVER ANY OF THE PREVIOUS COMMENTS OR
 ITEMS BROUGHT UP IN THE MEETING PREVIOUSLY HELD. THIS
 IS NOT REQUIRED HOWEVER WILL MANY TIMES HELP ALLEVIATE
 THE NEED TO SOME COMMENTS.
 THIS CONCERN WAS GONE OVER WITH OTHER ELECTRICAL
 REVIEWERS INCLUDING THE CHIEF ELECTRICAL INSPECTOR AND
 THE CONSENSUSWAS THERE IS A POTENTIAL HAZARD OF
 SYSTEM VOLTAGES STILL PRESENT IN BUILDING AND
 DIFFERENCES IN POTENTIAL FROM THE SEPARATE
 TRANSFORMERS, SOURCES AND GROUNDING TO NAME A FEW.
 PLEASE KNOW AS PREVIOUSLY STATED THE SEPARATE SERVICE
 IS STILL IN QUESTION IS A SYSTEM WILL BE CROSSED INTO
 THIS BUILDING FROM EXISTING.
 THE COMMENTS IN MEETING WAS THAT THERE *WOULD* BE
 SYSTEMS FROM EXISTING SOURCES IN THIS NEW STRUCTURE.
  
 3) NOTE: PLEASE ADJUST SYMBOLS AND LEGENDS. PLEASE SEE
 THE LIGHTING PLANS SHOWS A *S* FOR WHAT IS NOTED AS
 SOME SORT OF SENSOR SWITCH, HOWEVER PLEASE SEE THIS
 SAME SYMBOL (*S*) ON E-1 SHOWS THIS AS A STANDARD
 SINGLE POLE WALL SWITCH. PLEASE ADJUST E-1 SO AS NOT TO
 CONFUSE LIGHTING CONTROLS REQUIRED.
  
 4) NOTE: PLEASE CONFIRM E-4EM AND E-5EM ARE THE LEVELS
 UNDER EMERGENCY CONDITIONS. NO CHANGES ARE NEEDED. LS
 101 7.9, 7.8
  
 5) NOTE: PLEASE KNOW PART OF A *PROVISO* WILL BE THAT
 THE PANEL SCHEDULE WILL BE REQUIRED TO UPDATED TO
 SPECIFICALLY INDICATE ALL ROOMS AND AREAS IN WHICH THEY
 FEED.
 408.4
  
 6) NOTE: WHEN RE-SUBMITTING PLANS AND DOCUMENTS DO NOT
 ATTACHED THESE DOWN THE LEFT HAND SIDE OF THE SETS OF
 PLANS.
 THESE SUPPORTING DOCUMENTS WERE REMOVED FROM THE ONE
 SET BEING REVIEWED.
 PLEASE PLACE IN BINDER, FOLDER ETC OF SOME TYPE.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  