| 2008-01-01 16:53:32 | 2008-01-01 16:53:32 |
| | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE FBC CHAPTER 13. PLEASE SEE THE |
| | CALCULATIONS SUBMITTED ARE NO LONGER IN EFFECT FOR THE |
| | STATE OF FLORIDA AND FLORIDA BUILDING CODE. PLEASE AS |
| | OF DECEMBER 6TH, 2006 THE 2004 FBC CHANGED WHICH |
| | INCLUDED THE 2006 REVISIONS. PLEASE SEE 13-400.0.A, |
| | 13-415.1.A, .1.B, 13-415.2, 13-400.3.A. THE VERSION |
| | SUBMITTED IS 2.11 AND THE REQUIRED VERSION IS 2.5. |
| | PLEASE KNOW THE 2.5 WITH ENERGY GAUGE SUMMIT 3.1 IS |
| | ACCEPTABLE AS LONG AS THE VERSION IS 2.5. |
| | PLEASE VERIFY A METHOD *B* BEING SUBMITTED. THIS WILL |
| | BE IN MECHANICAL REVIEW. PLEASE SEE THE TABLES SHOWN ON |
| | PLANS FOR LIGHTING PERFORMANCE CALCULATIONS STATE |
| | METHOD *C*. |
| | THIS IS A NEW WHOLE BUILDING. |
| | PLEASE SEE THE CALCULATIONS SUBMITTED ARE ALSO NOT |
| | SIGNED, DATED OR SEALED BY THE RESPONSIBLE LICENSED |
| | DESIGNER OF RECORD. |
| | PLEASE SEE 13-103.1.1.1, FS 471.025. |
| | PLEASE CLARIFY HOW SOME OF THE METHOD OF CONTROLS ARE |
| | STILL BEING SHOWN AS MANUAL ON/OFF WHEN THE DEVICE ON |
| | PLANS IS CLEARLY AN AUTOMATED TYPE DEVICE.? |
| | FOR EXAMPLE: PLEASE SEE JAN 131, STOR. 132 ETC |
| | FOR EXAMPLE: PLEASE SEE THE LIGHTING ON SHEET ESP-1 |
| | COULD NOT BE LOCATED IN THE INPUT DATA REPORT SUBMITTED |
| | FOR EXTERIOR LIGHTING? |
| | PLEASE SUBMIT CALCULATIONS ACCORDINGLY AND ADJUST ALL |
| | INPUTS. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS COMMENT WITH RESPECT TO |
| | SERVICE AND 230.2, 22531-225.39, 230.72 ETC. THE |
| | COMMENT WAS NOT THAT THE NEW STRUCTURE DOES NOT FALL |
| | UNDER THE DESIGN AND CONSIDERED AS A SEPARATE BUILDING. |
| | THIS WAS GONE OVER IN A MEETING BEFORE PLANS |
| | RESUBMITTED.THE CONCERN IS THAT ANY ELECTRICAL |
| | SYSTEMS OF ANY VOLTAGE WOULD BE FED INTO THIS BUILDING |
| | FROM THE PRESENT EXISTING STRUCTURE WHICH WOULD PLACE |
| | NOT ONLY ELECTRICAL FED FROM MULTIPLE SOURCES BUT WOULD |
| | BE SYSTEMS FROM MORE THAN ONE FPL TRANSFORMER. |
| | THE ELECTRICAL DESIGNER OF RECORD WAS NOT PRESENT AND |
| | THE ARCHITECT IN MEETING MENTIONED THE DESIGNER OF |
| | RECORD WOULD CONTACT THIS OFFICE/REVIEWER TO GO OVER |
| | COMMENTS AND CONCERNS. NO CONTACT WAS MADE TO THIS |
| | REVIEWER TO GO OVER ANY OF THE PREVIOUS COMMENTS OR |
| | ITEMS BROUGHT UP IN THE MEETING PREVIOUSLY HELD. THIS |
| | IS NOT REQUIRED HOWEVER WILL MANY TIMES HELP ALLEVIATE |
| | THE NEED TO SOME COMMENTS. |
| | THIS CONCERN WAS GONE OVER WITH OTHER ELECTRICAL |
| | REVIEWERS INCLUDING THE CHIEF ELECTRICAL INSPECTOR AND |
| | THE CONSENSUSWAS THERE IS A POTENTIAL HAZARD OF |
| | SYSTEM VOLTAGES STILL PRESENT IN BUILDING AND |
| | DIFFERENCES IN POTENTIAL FROM THE SEPARATE |
| | TRANSFORMERS, SOURCES AND GROUNDING TO NAME A FEW. |
| | PLEASE KNOW AS PREVIOUSLY STATED THE SEPARATE SERVICE |
| | IS STILL IN QUESTION IS A SYSTEM WILL BE CROSSED INTO |
| | THIS BUILDING FROM EXISTING. |
| | THE COMMENTS IN MEETING WAS THAT THERE *WOULD* BE |
| | SYSTEMS FROM EXISTING SOURCES IN THIS NEW STRUCTURE. |
| | |
| | 3) NOTE: PLEASE ADJUST SYMBOLS AND LEGENDS. PLEASE SEE |
| | THE LIGHTING PLANS SHOWS A *S* FOR WHAT IS NOTED AS |
| | SOME SORT OF SENSOR SWITCH, HOWEVER PLEASE SEE THIS |
| | SAME SYMBOL (*S*) ON E-1 SHOWS THIS AS A STANDARD |
| | SINGLE POLE WALL SWITCH. PLEASE ADJUST E-1 SO AS NOT TO |
| | CONFUSE LIGHTING CONTROLS REQUIRED. |
| | |
| | 4) NOTE: PLEASE CONFIRM E-4EM AND E-5EM ARE THE LEVELS |
| | UNDER EMERGENCY CONDITIONS. NO CHANGES ARE NEEDED. LS |
| | 101 7.9, 7.8 |
| | |
| | 5) NOTE: PLEASE KNOW PART OF A *PROVISO* WILL BE THAT |
| | THE PANEL SCHEDULE WILL BE REQUIRED TO UPDATED TO |
| | SPECIFICALLY INDICATE ALL ROOMS AND AREAS IN WHICH THEY |
| | FEED. |
| | 408.4 |
| | |
| | 6) NOTE: WHEN RE-SUBMITTING PLANS AND DOCUMENTS DO NOT |
| | ATTACHED THESE DOWN THE LEFT HAND SIDE OF THE SETS OF |
| | PLANS. |
| | THESE SUPPORTING DOCUMENTS WERE REMOVED FROM THE ONE |
| | SET BEING REVIEWED. |
| | PLEASE PLACE IN BINDER, FOLDER ETC OF SOME TYPE. |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |