Plan Review Notes
Plan Review Notes For Permit 07050239
Permit Number 07050239
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-12 10:39:47DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A-1 OCCUPANCY IS LISTED AS GROUP CS AND WHERE
 INDICATED AS MIXED OCCUPANCY "NO" IS STATED. PLANS
 INDICATE OTHERWISE AS IT IS INDICATED AS MEDIA CENTER,
 CHAPEL & BAND SUITE, (ASSEMBLY), AND ALSO COUNSELING &
 OFFICES, (BUSINESS). MAYBE EDUCATION IS TO BE
 CONSIDERED FOR THE MEDIA CENTER. PLEASE CLARIFY AND
 PLEASE INDICATE WHAT OCCUPANCY "GROUP CS" IS AS IT IS
 NOT INDICATED IN THE FBC-2004 BUILDING CODE.
  
 2. SHT A-1 SUBMIT CALCULATIONS FOR MINIMUM FACILITIES
 PER TABLES 1104.1.2 & 403.1. INDICATE THE TOTAL AREA
 FOR EACH OCCUPANCY FOR THE MEDIA CENTER, CHAPEL, BAND
 SUITE, COUNSELING & BUSINESS.
  
 3. SURVEY SHEET 2 0F 2 SHALL BE SIGNED, SEALED AND
 DATED PER SECTION 106.1 AND FAC 61G1-16.003 & FS
 472.025.
  
 4. SHTS C-1 THRU C-17 THE FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE
 TITLE BLOCK OF EACH SHEET FOR THE ENGINEERING INC. FAC
 61G15-23.002(2) & FS 471.025. PLEASE ADD TO TITLE
 BLOCK.
  
 5. SHTS L-1 THRU L-4 THE ADDRESS ON THE FLORIDA STATE
 DBPR WEBSITE DOES NOT REFLECT THE ADDRESS IN THE TITLE
 BLOCKS. PLEASE UPDATE THE DBPR WEBSITE OR THE TITLE
 BLOCK SO THE INFORMATION CORRELATES. (SEE ATTACHED
 SHEET).
  
 6. SHT A-2 DEMO NOTE #7. SEPARATE GAS PERMIT REQUIRED
 WITH PLANS INDICATING CHANGES. SECTION 105.1.
  
 7. SHT A-11 ROOF LEGEND #5 IS NOT INDICATED ON 4 ROOF
 AREAS. PLEASE CORRELATE LEGEND AND ROOF PLAN. SECTION
 106.1.1.
  
 8. SUBMIT CALCULATIONS FOR PRIMARY AND SECONDARY ROOF
 DRAINS. SHOW THE SQUARE FOOTAGE OF EACH AREA, AS WELL
 AS 1/2 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS
 ADDED TO ROOF AREAS PER SECTIONS 1106 & 1107 AS WELL AS
 TABLE 1106.3.
  
 9. SHT A-27 DETAILS 5 & 6. SHOW THE 5' TURNING AREA IN
 THE TOILET ROOMS AS REQUIRED IN SECTION 11-4.22.3. THEY
 ARE PRESENTLY INDICATED IN THE ACCESSIBLE STALL.
  
 10. SHT A-39 DETAIL FOR THE ACCESSIBLE W/C'S SHOW
 COMPLIANCE WITH 11-4.16.5 FLUSH CONTROLS. --THE LAVS
 SHOW 35" TO THE FLOOD RIM LEVEL, WHEREAS THE
 REQUIREMENT IS MAX. 34" PER SECTION 11-4.19.2. ALSO
 SHOW COMPLIANCE WITH 11-4.19.5 FAUCETS.--FOR THE
 URINAL SHOW COMPLIANCE WITH 11-4.18.4 FLUSH CONTROLS.
  
 11. SHTS S-1 THRU S-8 THE ADDRESS ON THE FLORIDA STATE
 DBPR WEBSITE DOES NOT REFLECT THE ADDRESS ON THE TITLE
 BLOCKS. (SEE ATTACHED SHEET). PLEASE UPDATE THE DBPR
 WEBSITE OR THE TITLE BLOCKS SO THE INFORMATION
 CORRELATES.
  
 12. SHTS P1 & P4 INDICATES A SINK IN ROOM 114
 CONNECTING TO A DRYWELL. SECTION 301.3 STATES ALL
 FIXTURES USED TO RECIEVE OR DISCHARGE LIQUIDS, WASTE OR
 SEWAGE SHALL BE DIRECTLY CONNECTED TO THE SANITARY
 DRAINAGE SYSTEM. PLEASE CLARIFY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]