| 2007-06-12 10:39:47 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT A-1 OCCUPANCY IS LISTED AS GROUP CS AND WHERE |
| | INDICATED AS MIXED OCCUPANCY "NO" IS STATED. PLANS |
| | INDICATE OTHERWISE AS IT IS INDICATED AS MEDIA CENTER, |
| | CHAPEL & BAND SUITE, (ASSEMBLY), AND ALSO COUNSELING & |
| | OFFICES, (BUSINESS). MAYBE EDUCATION IS TO BE |
| | CONSIDERED FOR THE MEDIA CENTER. PLEASE CLARIFY AND |
| | PLEASE INDICATE WHAT OCCUPANCY "GROUP CS" IS AS IT IS |
| | NOT INDICATED IN THE FBC-2004 BUILDING CODE. |
| | |
| | 2. SHT A-1 SUBMIT CALCULATIONS FOR MINIMUM FACILITIES |
| | PER TABLES 1104.1.2 & 403.1. INDICATE THE TOTAL AREA |
| | FOR EACH OCCUPANCY FOR THE MEDIA CENTER, CHAPEL, BAND |
| | SUITE, COUNSELING & BUSINESS. |
| | |
| | 3. SURVEY SHEET 2 0F 2 SHALL BE SIGNED, SEALED AND |
| | DATED PER SECTION 106.1 AND FAC 61G1-16.003 & FS |
| | 472.025. |
| | |
| | 4. SHTS C-1 THRU C-17 THE FIRM LICENSE NUMBER, |
| | (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE |
| | TITLE BLOCK OF EACH SHEET FOR THE ENGINEERING INC. FAC |
| | 61G15-23.002(2) & FS 471.025. PLEASE ADD TO TITLE |
| | BLOCK. |
| | |
| | 5. SHTS L-1 THRU L-4 THE ADDRESS ON THE FLORIDA STATE |
| | DBPR WEBSITE DOES NOT REFLECT THE ADDRESS IN THE TITLE |
| | BLOCKS. PLEASE UPDATE THE DBPR WEBSITE OR THE TITLE |
| | BLOCK SO THE INFORMATION CORRELATES. (SEE ATTACHED |
| | SHEET). |
| | |
| | 6. SHT A-2 DEMO NOTE #7. SEPARATE GAS PERMIT REQUIRED |
| | WITH PLANS INDICATING CHANGES. SECTION 105.1. |
| | |
| | 7. SHT A-11 ROOF LEGEND #5 IS NOT INDICATED ON 4 ROOF |
| | AREAS. PLEASE CORRELATE LEGEND AND ROOF PLAN. SECTION |
| | 106.1.1. |
| | |
| | 8. SUBMIT CALCULATIONS FOR PRIMARY AND SECONDARY ROOF |
| | DRAINS. SHOW THE SQUARE FOOTAGE OF EACH AREA, AS WELL |
| | AS 1/2 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS |
| | ADDED TO ROOF AREAS PER SECTIONS 1106 & 1107 AS WELL AS |
| | TABLE 1106.3. |
| | |
| | 9. SHT A-27 DETAILS 5 & 6. SHOW THE 5' TURNING AREA IN |
| | THE TOILET ROOMS AS REQUIRED IN SECTION 11-4.22.3. THEY |
| | ARE PRESENTLY INDICATED IN THE ACCESSIBLE STALL. |
| | |
| | 10. SHT A-39 DETAIL FOR THE ACCESSIBLE W/C'S SHOW |
| | COMPLIANCE WITH 11-4.16.5 FLUSH CONTROLS. --THE LAVS |
| | SHOW 35" TO THE FLOOD RIM LEVEL, WHEREAS THE |
| | REQUIREMENT IS MAX. 34" PER SECTION 11-4.19.2. ALSO |
| | SHOW COMPLIANCE WITH 11-4.19.5 FAUCETS.--FOR THE |
| | URINAL SHOW COMPLIANCE WITH 11-4.18.4 FLUSH CONTROLS. |
| | |
| | 11. SHTS S-1 THRU S-8 THE ADDRESS ON THE FLORIDA STATE |
| | DBPR WEBSITE DOES NOT REFLECT THE ADDRESS ON THE TITLE |
| | BLOCKS. (SEE ATTACHED SHEET). PLEASE UPDATE THE DBPR |
| | WEBSITE OR THE TITLE BLOCKS SO THE INFORMATION |
| | CORRELATES. |
| | |
| | 12. SHTS P1 & P4 INDICATES A SINK IN ROOM 114 |
| | CONNECTING TO A DRYWELL. SECTION 301.3 STATES ALL |
| | FIXTURES USED TO RECIEVE OR DISCHARGE LIQUIDS, WASTE OR |
| | SEWAGE SHALL BE DIRECTLY CONNECTED TO THE SANITARY |
| | DRAINAGE SYSTEM. PLEASE CLARIFY. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |