Plan Review Notes
Plan Review Notes For Permit 07050239
Permit Number 07050239
Review Stop M
Sequence Number 1
Notes
Date Text
2007-06-05 09:53:41FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 ---------------DENIED-----------------
  
 1. PLEASE SHOW ON PLANS THE TYPE OF CONSTRUCTION BASED
 ON FBC CHAPTER 6. "TYPE A: UNPROTECTED" IS NOT A
 RECOGNIZED DESIGNATION. FBC 106.5.3
  
 2. PLEASE SHOW ON PLANS THE OCCUPANCY CLASSIFICATION
 BASED ON FBC CHAPTER 3. "GROUP CS" IS NOT A RECOGNIZED
 DESIGNATION. FBC 106.5.3
  
 3. THERE ARE SEVERAL WALLS WHICH ARE SHOWN TO BE FIRE
 BARRIERS BASED ON THE WALL SCHEDULE (A-23), LIFE SAFETY
 PLAN (A-35,A-36) AND FLOOR PLAN (A-9,A-10). MANY SUCH
 WALLS HAVE UNPROTECTED DUCT PENETRATIONS. PLEASE SHOW
 HOW THESE OPENINGS ARE TO BE PROTECTED PER FBC,M
 607.5.
 NOTE: RATED WALLS FROM LIFE SAFETY PLAN HAVE BEEN
 HIGHLIGHTED ON ONE SET OF MECHANICAL PLANS TO HELP
 DETERMINE THE LOCATIONS IN QUESTION.
  
 4. SMOKE DAMPERS ARE REQUIRED AT DUCT PENETRATIONS INTO
 CORRIDORS PER FBC,M 607.5.4. PLEASE CONSULT THIS CODE
 SECTION FOR EXEMPTIONS TO DETERMINE WHERE SMOKE DAMPERS
 ARE REQUIRED. COMBINATION FIRE/SMOKE DAMPERS MAY BE
 USED WHERE BOTH FIRE AND SMOKE PROTECTION ARE REQUIRED.
 THESE LOCATIONS WERE NOT MARKED ON PLAN DURING THIS
 REVIEW.
  
 5. EXIT ENCLOSURE (CORRIDOR) VENTILATION SYSTEMS SHALL
 BE INDEPENDENT OF OTHER BUILDING VENTILATION SYSTEMS
 AND SHALL BE SEPARATED FROM OTHER BUILDING COMPONENTS
 BY ONE OF THE THREE METHODS LISTED IN FBC,M 401.4:
 (1) SUCH EQUIPMENT AND DUCTWORK SHALL BE LOCATED
 EXTERIOR TO THE BUILDING AND SHALL BE DIRECTLY
 CONNECTED TO THE EXIT ENCLOSURE BY DUCTWORK ENCLOSED IN
 CONSTRUCTION AS REQUIRED BY THE FLORIDA BUILDING CODE,
 BUILDING FOR SHAFTS.
 (2) WHERE SUCH EQUIPMENT AND DUCTWORK IS LOCATED WITHIN
 THE EXIT ENCLOSURE, THE INTAKE AIR SHALL BE TAKEN
 DIRECTLY FROM THE OUTDOORS AND THE EXHAUST AIR SHALL BE
 DISCHARGED DIRECTLY TO THE OUTDOORS, OR SUCH AIR SHALL
 BE CONVEYED THROUGH DUCTS ENCLOSED IN CONSTRUCTION AS
 REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING FOR
 SHAFTS.
 (3) WHERE LOCATED WITHIN THE BUILDING, SUCH EQUIPMENT
 AND DUCTWORK SHALL BE SEPARATED FROM THE REMAINDER OF
 THE BUILDING, INCLUDING OTHER MECHANICAL EQUIPMENT,
 WITH CONSTRUCTION AS REQUIRED BY THE FLORIDA BUILDING
 CODE, BUILDING FOR SHAFTS.
  
 6. AHU 1: EQUIPMENT SCHEDULE CALLS FOR 4500 CFM SUPPLY,
 FLOOR PLAN CALLS FOR 4930 CFM TOTAL SUPPLY. WHICH IS
 CORRECT?
  
 7. AHU 4: FLOOR PLAN SHOWS 2215 CFM OF SUPPLY. A DUCT
 SMOKE DETECTOR IS REQUIRED PER FBC,M 606.2.1.
  
 8. AHU 7 & 8 (USED AS EXAMPLES OF WORT CASE): DRAIN
 LINES WILL BE TRAVELING APPROX. 200' HORIZONTALLY ABOVE
 CORRIDOR CEILING ON 1ST FLOOR. FBC,P 704.1 CALLS FOR
 DRAINS 2 1/2" OR SMALLER TO BE SLOPED AT 1/4" PER FOOT.
 THIS WOULD REQUIRE APPROX. 4' DROP AT A UNIFORM SLOPE
 FROM BEGINNING TO END OF THE HORIZONTAL RUNS. WILL
 FIELD CONDITIONS ALLOW FOR THIS? A HORIZONTAL RUN OF
 THIS LENGTH MAY INCREASE THE FREQUENCY OF CLOGGED
 DRAINS. PERHAPS A MORE SUITABLE LOCATION OF CONDENSATE
 DISPOSAL CAN BE FOUND FOR THE EXTREMELY LONG RUNS.
  
 9. PLEASE PROVIDE EQUIPMENT MANUFACTURER'S SUBMITTAL
 DATE AND INSTALLATION INSTRUCTIONS TO SHOW SERVICE
 CLEARANCE REQUIREMENTS FOR AHU'S IN EQUIPMENT ROOMS.
  
 10. PG M-5: IF DUCT SMOKE DETECTOR IS ADDED TO AHU-4
 (SEE COMMENT #7) PLEASE ADJUST GENERAL NOTE #14
 ACCORDINGLY.
  
 11. WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET, SUCH ACCESS SHALL BE PROVIDED BY A
 PERMANENT APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH
 SHALL BE FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND
 APPLIANCES? LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES HIGH OR WALKING ON ROOFS HAVING A SLOPE GREATER
 THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (33-PERCENT SLOPE). CATWALKS INSTALLED TO PROVIDE THE
 REQUIRED ACCESS SHALL BE NOT LESS THAN 24 INCHES WIDE
 AND SHALL HAVE RAILINGS AS REQUIRED FOR SERVICE
 PLATFORMS.
  
 12. PG M-6 FIRE DAMPER DETAIL: FIRE DAMPERS, SMOKE
 DAMPERS, COMBINATION FIRE/SMOKE DAMPERS AND CEILING
 DAMPERS LOCATED WITHIN AIR DISTRIBUTION AND SMOKE
 CONTROL SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH
 THE REQUIREMENTS OF THIS SECTION, AND THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS AND LISTING.
 FBC,M 607.2.
 NOTE: MANUFACTURER'S INSTRUCTIONS MAY BE SUBSTITUTED
 FOR THIS DETAIL OR A REFERENCE TO MANUFACTURER'S
 INSTRUCTIONS MAY SUFFICE.
  
 13. PLEASE SHOW MEANS OF SECONDARY OR AUXILIARY DRAIN
 PROTECTION ON ALL AHU'S PER FBC,M 307.2.3.
  
 14. M-6: PLEASE INDICATE ON PLANS THE DESIGNED WIND
 LOAD OF THE ATTACHMENTS FOR THE OUTDOOR EQUIPMENT
 (ROOFTOP FANS, CONDENSING UNITS) PER FBC,M 301.13 AND
 FBC CH.16. ALSO, PLEASE SHOW MEANS OF ATTACHMENT FOR
 EXHAUST FANS TO ROOF CURBS.
 NOTE: THE CITY OF WEST PALM BEACH IS IN THE 140 MPH
 ZONE PER FBC CH.16.
  
 15. ENERGY CALCULATIONS: ROOF INSULATION IS SHOWN ON
 CALCULATIONS TO BE R-19 CELLULOSE INSULATION IN
 "ATTIC", PLANS SHOW LIGHTWEIGHT CONCRETE ON ROOF.
 PLEASE COORDINATE DRAWINGS AND ENERGY CALCULATIONS.
 ALSO, PLEASE PROVIDE INFORMATION SHOWING THE THICKNESS
 OF THE LIGHTWEIGHT AND THE R-VALUES ACHIEVED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]
  