Plan Review Notes
Plan Review Notes For Permit 07050239
Permit Number 07050239
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-08-31 08:32:39*****DENIED*****
  
  
 01.INDICATE THE OCCUPANCY CLASSIFICATION FOR THIS
 PROPOSED STRUCTURE.EXAMPLE:BUSINESS,EDUCATIONAL,
 ASSEMBLY, MIXED USE, ETC.THIS INFORMATIOTION WILL
 ASSIST REVIEWER(S) IN THE PLAN REVIEW PROCESS.BE
 ADVISED THAT ADDITIONAL COMMENTS MAY BE FORTHCOMING
 ONCE THIS INFORMATION BECOMES AVAILABLE.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.CONSTRUCTION AND OTHER ASSOCIATED SCOPE OF WORKS
 SHALL NOT INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS
 TO THE PROPERTY OR VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 04.WILL THE PROPOSED HYDRANT BE OPERATIONAL BEFORE,
 DURING, OR AFTER CONSTRUCTION.IF NOT OPERATIONAL
 BEFORE, INDICATE THE NEAREST FIRE HYDRANT(S) TO THE
 STRUCTURE THAT WOULD BE AVAILABLE FOR FIRE DEPARTMENT
 USE.
  
 05. IT IS INDICATED ON SHEET C-4 THAT THE PROPOSED FIRE
 HYDRANT ASSEMBLY IS DETAILED ON SHEET C-11.NO SUCH
 DETAIL IS SHOWN ON C-11, HOWEVER C-13 AND C-16
 (STANDARD P-9) SHOWS THIS INFORMATION.PLEASE AMEND.
  
 06.ON SHEET A-9 FLOOR PLAN NOTE #2 HAS CALL FOR A
 BUTTON OPERATED DOOR WITH THE BUTTON LOCATED IN CENTRAL
 OFFICE RECEPTION AREA.HOW WILL EGRESS FROM THIS AREA
 BE IMPACTED?
  
 07.SEE BUILDING REVIEW COMMENTS IN REFERENCE TO DOOR
 146- A AND DOOR 146-B.(SHEET A-9)
  
 08.NO EXIT OR EMERGENCY LIGHTS SHOWN ON THE REFLECTED
 CEILING SHEETS(A-12, A-13).THE LOCATION OF THESE
 DEVICES SHALL CORRELATE WITH OTHER PLAN SHEETS SUCH AS
 LIFE SAFETY AND/OR LIGHTING FLOOR PLANS.
  
 09. VERIFY THE POSTING OF THE NUMERICAL ADDRESS FOR
 CARDINAL NEWMAN HIGH SCHOOL.IF NOT ALREADY POSTED,
 DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE
 EXTERIOR ELEVATION SO THAT IT IS VISIBLE FROM SPENCER
 DRIVE.
  
 10.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN
 THE EXITS, EXIT ACCESS CORRIDORS, AND ALL OTHER AREAS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 11.SPECIFY INTERIOR FLOOR FINISH IN EXIT ENCLOSURES,
 EXIT ACCESS CORRIDORS, AND OTHER SPACES IN TERMS OF
 CLASS I OR CLASS II.
  
 12.WALL OPENINGS REQUIRED TO HAVE A FIRE PROTECTION
 RATING SHALL BE PROTECTED BY FIRE DOORS AND FIRE
 WINDOWS IN ACCORDANCE WITH NFPA 80.
  
 13.PROVIDE PRESCRIPTIVE STRENGHTS FOR STAIR
 GUARDRAILS AND HANDRAILS.
  
 14.INCLUDE EXIT LIGHTS, EMERGENCY LIGHTS AND FIRE
 EXTINGUISHERS TO THE LIFE SAFETY PLAN SHEETS (A-35 &
 36).THE LOCATION OF THESE DEVICES SHALL CORRELATE
 WITH OTHER PLAN SHEETS WHERE SHOWN.
  
 15.TRAVEL DISTANCES AND SOME OF THE OCCUPANT LOAD
 INFORMATION IS UNCLEAR FOR READING AND REVIEW.SEE
 SHEET A-35
  
 16.AS PER LOCAL REQUIREMENTS, DUCT SMOKE DETECTORS
 SHALL INITIATE A GENERAL FIRE ALARM.AMEND/INCLUDE IN
 FIRE ALARM REQUIREMENTS SYSTEM OPERATIONS (SHEET E-7).
  
 17.NFPA 72, NATIONAL FIRE ALARM CODE, 2002 EDITION
 SHALL BE REFERENCED.
  
 18.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE ALARM INSTALLATION AND/OR REMODEL.
  
 19.IT IS INDICATED THAT THIS STRUCTURE WILL BE
 BUILDING "D".HOW WILL THE ACTIVATION OF AN ALARM IN
 BLDG. "D"BE DISTIGUISHABLE FROM THE OTHER BUILDINGS
 OR AREAS OF THE CAMPUS?
  
 20.ON SHEET E-7 UNDER THE FIRE ALARM SYSTEM LEGEND,
 THE SYMBOL OF LETTER H ENCASED INSIDE A SQUARE
 REQRESENTS BOTH A HORN/STROBE LIGHT AND THAT OF A KNOX
 BOX. PLEASE RECTIFY/AMEND.
  
 21.ON SHEET E-7 UNDER GENERAL FIRE ALARM SYSTEM NOTE
 #2, PLEASE EXPLAIN THE REFERENCE TO NFPA 3 -
 8.4.1.3.7.6 AND ITS RELEVANCE.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722