| Date |
Text |
| 2007-08-31 08:32:39 | *****DENIED***** |
| | |
| | |
| | 01.INDICATE THE OCCUPANCY CLASSIFICATION FOR THIS |
| | PROPOSED STRUCTURE.EXAMPLE:BUSINESS,EDUCATIONAL, |
| | ASSEMBLY, MIXED USE, ETC.THIS INFORMATIOTION WILL |
| | ASSIST REVIEWER(S) IN THE PLAN REVIEW PROCESS.BE |
| | ADVISED THAT ADDITIONAL COMMENTS MAY BE FORTHCOMING |
| | ONCE THIS INFORMATION BECOMES AVAILABLE. |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03.CONSTRUCTION AND OTHER ASSOCIATED SCOPE OF WORKS |
| | SHALL NOT INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS |
| | TO THE PROPERTY OR VICINITY THEREOF (INCLUDING FIRE |
| | LANES). |
| | |
| | 04.WILL THE PROPOSED HYDRANT BE OPERATIONAL BEFORE, |
| | DURING, OR AFTER CONSTRUCTION.IF NOT OPERATIONAL |
| | BEFORE, INDICATE THE NEAREST FIRE HYDRANT(S) TO THE |
| | STRUCTURE THAT WOULD BE AVAILABLE FOR FIRE DEPARTMENT |
| | USE. |
| | |
| | 05. IT IS INDICATED ON SHEET C-4 THAT THE PROPOSED FIRE |
| | HYDRANT ASSEMBLY IS DETAILED ON SHEET C-11.NO SUCH |
| | DETAIL IS SHOWN ON C-11, HOWEVER C-13 AND C-16 |
| | (STANDARD P-9) SHOWS THIS INFORMATION.PLEASE AMEND. |
| | |
| | 06.ON SHEET A-9 FLOOR PLAN NOTE #2 HAS CALL FOR A |
| | BUTTON OPERATED DOOR WITH THE BUTTON LOCATED IN CENTRAL |
| | OFFICE RECEPTION AREA.HOW WILL EGRESS FROM THIS AREA |
| | BE IMPACTED? |
| | |
| | 07.SEE BUILDING REVIEW COMMENTS IN REFERENCE TO DOOR |
| | 146- A AND DOOR 146-B.(SHEET A-9) |
| | |
| | 08.NO EXIT OR EMERGENCY LIGHTS SHOWN ON THE REFLECTED |
| | CEILING SHEETS(A-12, A-13).THE LOCATION OF THESE |
| | DEVICES SHALL CORRELATE WITH OTHER PLAN SHEETS SUCH AS |
| | LIFE SAFETY AND/OR LIGHTING FLOOR PLANS. |
| | |
| | 09. VERIFY THE POSTING OF THE NUMERICAL ADDRESS FOR |
| | CARDINAL NEWMAN HIGH SCHOOL.IF NOT ALREADY POSTED, |
| | DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE |
| | EXTERIOR ELEVATION SO THAT IT IS VISIBLE FROM SPENCER |
| | DRIVE. |
| | |
| | 10.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN |
| | THE EXITS, EXIT ACCESS CORRIDORS, AND ALL OTHER AREAS |
| | IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | 11.SPECIFY INTERIOR FLOOR FINISH IN EXIT ENCLOSURES, |
| | EXIT ACCESS CORRIDORS, AND OTHER SPACES IN TERMS OF |
| | CLASS I OR CLASS II. |
| | |
| | 12.WALL OPENINGS REQUIRED TO HAVE A FIRE PROTECTION |
| | RATING SHALL BE PROTECTED BY FIRE DOORS AND FIRE |
| | WINDOWS IN ACCORDANCE WITH NFPA 80. |
| | |
| | 13.PROVIDE PRESCRIPTIVE STRENGHTS FOR STAIR |
| | GUARDRAILS AND HANDRAILS. |
| | |
| | 14.INCLUDE EXIT LIGHTS, EMERGENCY LIGHTS AND FIRE |
| | EXTINGUISHERS TO THE LIFE SAFETY PLAN SHEETS (A-35 & |
| | 36).THE LOCATION OF THESE DEVICES SHALL CORRELATE |
| | WITH OTHER PLAN SHEETS WHERE SHOWN. |
| | |
| | 15.TRAVEL DISTANCES AND SOME OF THE OCCUPANT LOAD |
| | INFORMATION IS UNCLEAR FOR READING AND REVIEW.SEE |
| | SHEET A-35 |
| | |
| | 16.AS PER LOCAL REQUIREMENTS, DUCT SMOKE DETECTORS |
| | SHALL INITIATE A GENERAL FIRE ALARM.AMEND/INCLUDE IN |
| | FIRE ALARM REQUIREMENTS SYSTEM OPERATIONS (SHEET E-7). |
| | |
| | 17.NFPA 72, NATIONAL FIRE ALARM CODE, 2002 EDITION |
| | SHALL BE REFERENCED. |
| | |
| | 18.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE |
| | FIRE ALARM INSTALLATION AND/OR REMODEL. |
| | |
| | 19.IT IS INDICATED THAT THIS STRUCTURE WILL BE |
| | BUILDING "D".HOW WILL THE ACTIVATION OF AN ALARM IN |
| | BLDG. "D"BE DISTIGUISHABLE FROM THE OTHER BUILDINGS |
| | OR AREAS OF THE CAMPUS? |
| | |
| | 20.ON SHEET E-7 UNDER THE FIRE ALARM SYSTEM LEGEND, |
| | THE SYMBOL OF LETTER H ENCASED INSIDE A SQUARE |
| | REQRESENTS BOTH A HORN/STROBE LIGHT AND THAT OF A KNOX |
| | BOX. PLEASE RECTIFY/AMEND. |
| | |
| | 21.ON SHEET E-7 UNDER GENERAL FIRE ALARM SYSTEM NOTE |
| | #2, PLEASE EXPLAIN THE REFERENCE TO NFPA 3 - |
| | 8.4.1.3.7.6 AND ITS RELEVANCE. |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |