Plan Review Notes
Plan Review Notes For Permit 07050239
Permit Number 07050239
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-06 14:29:32** UNSAT **
  
 *** PLEASE KNOW THAT AS THERE ARE MANY ITEMS WHICH ARE
 NOT SHOWN FOR CODE COMPLIANCE AT THIS TIME OR MISSING
 FOR REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW NOT YET ABLE TO BE MADE.
  
 1) NOTE:PLEASE KNOW THAT PERMIT APPLICATIONS WAS
 SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH WILL
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS,
 ARCHITECTURAL SHEETS AND FIRE ALARM SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE NOW SEE MISSING THE ATTACHED PRINT OUT
 FROM THE STATE WHICH INDICATES LANDSCAPE FIRM WITH A
 DIFFERENT LICENSE NUMBER THAN THAT LISTED ON THE TITLE
 BLOCKS ON PLANS. PLEASE SEE THE ADDRESS WHICH IS ALSO
 LISTED ON THE TITLE BLOCKS WHICH IS DIFFERENT THAN THAT
 OF THE STATE.
 PLEASE LIST THE CORRECTED INFORMATION ON TITLE BLOCKS.
 PLEASE KNOW THAT THE PRIMARY ADDRESS AS LISTED WITH THE
 STATE IS REQUIRED TO BE ON PLANS AND ANY SATELLITE
 OFFICES MAY INCLUDE THEIR ADDRESS IN ADDITION. PLEASE
 ADJUST AND LIST THE LICENSE INFORMATION. 61G1-16.004,
 FS 481.219.
 **PLEASE KNOW THIS INFORMATION IS REQUIRED WHETHER OR
 NOT COMMENT IS MADE BY OTHER REVIEWER(S) OR TRADES.
  
 4) NOTE: PLEASE SEE THE TITLE BLOCKS ON MECHANICAL
 PLANS WHICH IS MISSING THE CERTIFICATE OF AUTHORIZATION
 AS LISTED ON ELECTRICAL AND PLUMBING SHEETS FOR MEP
 FIRM.
 PLEASE SEE FAC 61G15-23.002, FS 471.023.
 **PLEASE KNOW THIS IS REQUIRED WHETHER OR NOT COMMENT
 IS MADE BY OTHER TRADES.
  
 5) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE MISSING
 THE SIGNATURE FROM THE OWNER AGENT.
 13-103.1.1.1 AND AS LISTED ON FLA-COM FORM.
  
 6) NOTE: PLEASE SEE MISSING INFORMATION ON CIVIL PLANS
 FOR ENGINEERING FIRM AND ENGINEER.
 PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER AS REQUIRED PER FAC 61G15-23.002 AND FS
 471.023.
 ** PLEASE KNOW THIS INFORMATION IS REQUIRED FOR SHEETS
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. THIS
 HAS BEEN NOTED TO THE CIVIL ENGINEERING REVIEWER.
  
 7) NOTE: PLEASE SEE THE ATTACHED ENGINEERING REPORTS
 WHICH CONTAIN A *RUBBER-STAMP* IN LIEU OF THE REQUIRED
 *ORIGINAL* SIGNATURE FROM THE ENGINEER OF RECORD. THIS
 IS REQUIRED PER FS 471.025, FAC 61G15-23.002 ** THIS
 WAS NOTED TO THE STRUCTURAL REVIEWER HOWEVER EVEN IF
 COMMENT IS NOT MADE BY THE STRUCTURAL REVIEWER THIS IS
 REQUIRED.
  
 8) NOTE: PLEASE SEE FBC 2004 W/ 2006 REVISIONS FOR
 CHAPTER 13 COMPLIANCE. PLEASE KNOW THAT CHAPTER 13
 CHANGES TO THE 2004 FBC WENT INTO AFFECT OCT. 1ST,2005
 AND HAS BEEN ENFORCED SINCE THAT DATE.
 PLEASE SEE 13-413.1ABC.1 FOR WORST CASE VOLTAGE DROP
 FOR FEEDERS AND BRANCH CIRCUITS TO BE INDICATED. PLEASE
 SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR LIGHTING
 CONTROL SYSTEM(S) TO BE INDICATED. PLEASE INCLUDE
 SCHEDULING, SYSTEM, ZONES FOR SQ FT LIMITS, OVER RIDES
 AND LOCATIONS, SEPARATE SPACE CONTROLS ETC. PLEASE BE
 SURE TO INCLUDE ALL MAXIMUM OVER RIDE TIMES ON DEVICES
 WHICH ARE IN DESIGN.
 NO SYSTEMS, DEVICES OF ANY KIND WERE FOUND ON PLANS OR
 DESIGNED.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO NOT
 CORRELATE WITH PLANS FOR TYPES OF FIXTURES, NUMBER OF
 FIXTURES AND WATTAGE OF FIXTURES AS SHOWN ON PLANS.
 PLEASE COORDINATE ALL OF THESE AS SEVERL ITEMS DO NOT
 MATCH.
 PLEASE SEE THE METHOD OF CONTROL IS BEING SHOWN AS
 *MANUAL ON/OFF* ON ENERGY CALCULATIONS WHICH IS NOT
 POSSIBLE WHEN AUTOMATED LIGHTING CONTROL(S) IS
 REQUIRED.
 PLEASE SEE THE PRINT OUT OF THE LIGHTING COMPLIANCE
 SHEETS SEEMED TO HAVE CUT OFF MANY OF THE ROOM/AREAS
 IDENTIFICATIONS AS LISTED. THESE NEED TO BE CLEAR AND
 VISIBLE FOR REVIEW.
 PLEASE SEE 13-415.1.AB.1.1, 13-415.2,13-415.1.ABC.2,
 13-415.2.ABC.1.2 ETC.
  
 ** PLEASE KNOW AS COMPLIANCE WITH CHAPTER 13 WAS NOT
 DESIGNED INTO THE PROJECT, NO REVIEW OF ANY
 SYSTEMS/DEVICES ETC COULD BE REVIEWED FOR CODE
 COMPLIANCE.
  
 9) NOTE: PLEASE KNOW EVEN AS THE LOW VOLTAGE
 SYSTEMS(EXCLUDING FIRE ALARM, SEE NEXT NOTE FOR FA) ARE
 SHOWN ON PLANS, SEPARATE PERMITS WILL BE REQUIRED FOR
 THESE SYSTEMS. THESE PLANS MAY BE REFERENCED FOR
 PERMITTING.
  
 10) NOTE: PLEASE KNOW EVEN AS THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS ARE REQUIRED TO BE SHOWN ON BASED
 BUILDING PLANS FOR REVIEW, THESE WILL BE REQUIRED TO BE
 UNDER SEPARATE PERMITS WITH PLANS SUBMITTED
 SEPARATELY.
 ** PLEASE INCLUDE ALL REQUIRED LOCATIONS AND LEVELS OF
 HORN, STROBES, AND HORN/STROBES ON PLANS FOR FBC
 CHAPTER 11 ADA COMPLIANCE. THERE ARE MANY DEVICES
 ALREADY SHOWN, HOWEVER SOME LOCATIONS DO NOT MEET
 11-4.28.1 AND NO LEVELS OF ANY STROBE DEVICES COULD BE
 LOCATED PER 11-4.28.3(4).
 THESE ARE MINIMUM LOCATIONS AND LEVELS. PLEASE BE SURE
 TO SEE ANY FIRE REVIEW COMMENTS FROM FIRE MARSHAL WHICH
 MAY ALSO AFFECT THE PLANS.
  
 11) NOTE: PLEASE SEE 230.2 AS A SEPARATE SERVICE IS
 BEING REQUESTED FOR THE NEW BUILDING, HOWEVER IN ORDER
 FOR THE NEW SERVICE TO BE GRANTED AND THIS ADDITION TO
 BE CONSIDERED AS *SEPARATE BUILDING* BY DEFINITION OF
 THE FBC VERIFICATION OF REQUIRED SEPARATION AND RATING
 ON DOORS/OPENINGS NEEDS TO BE PROVIDED. THE EXISTING
 EXIT DOORS APPEAR TO EXIT INTO THIS NEW ADDITION AND
 APPLICATION IS TO BUILD AN *ADDITION TO EXISTING
 BUILDINGS*.
 PLANS DO SEEM TO SHOW COMPLIANCE FOR STRUCTURAL
 COLLAPSE OF EACH WITHOUT AFFECTING THE STRUCTURAL
 INTEGRITY OF THE OTHER STRUCTURE. PLEASE KNOW AS REVIEW
 OF THE SERVICE WILL BE DONE AND NOTED BELOW HOWEVER THE
 SERVICE AS SUBMITTED AND SHOWN IS NOT BEING GRANTED AT
 THIS TIME. THIS EXISTING SERVICE FEEDING EXISTING
 BUILDING WOULD BE REQUIRED TO BE UPGRADED TO FEED THE
 NEW ADDITION.
 FBC 106.1.2.
 230.2, 230.70, 230.71, 230.72 ETC
  
 12) NOTE: PLEASE SEE 620.23 AND 620.24 FOR MISSING
 DEDICATED BRANCH CIRCUITS FOR THE ELEVATOR EQUIPMENT
 ROOM.
 *BRANCH CIRCUITS MAY NOT FEED OTHER AREAS AS SHOWN.
  
 13) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS ON STAIR
 TOWERS AND EXIT PATHS FOR REVIEW. THE MINIMUM LEVELS
 FOR LIGHTING CAN NOT BE REVIEWED AT THIS TIME. PLEASE
 SEE 2003 NFPA-101 (LIFE SAFETY CODE) 7.8.1.3, 7.9.2.2
 FOR MINIMUM LEVELS.
  
 14) NOTE: PLEASE SEE THE TEMPORARY EXIT CORRIDORS BEING
 PROPOSED ARE NOT ON ELECTRICAL PLANS, YET THE
 ARCHITECTURAL SHEETS INDICATE LIGHTING FOR THESE
 AREAS.
 PLEASE ALSO SEE THE ARCHITECTURAL DESIGN INDICATES THIS
 AREA BEING COMPLETELY ENCLOSED AND NO EMERGENCY
 LIGHTING FOR REQUIRED EGRESS PATH UNDER EM CONDITIONS.
 PLEASE SEE NOTE #13 ABOVE WITH RESPECT TO THE MINIMUM
 LIGHTING LEVELS AND PLEASE ADJUST BOTH A AND E SHEETS
 FOR CORRECTIONS AND PHOTO-METRICS TO BE SUBMITTED. LS
 101 7.8 AND 7.9.
 PLEASE SEE 700.12F FOR CIRCUITING.
  
 15) NOTE:PLEASE SEE THE PROPOSED MDP AS SHOWN
 CONTAINS NO MAIN CIRCUIT BREAKER. PLEASE PLACE NOTE ON
 PLANS FOR DEAD-FRONT TO BE PERMANENT FROM MANUFACTURE
 WITH NO MORE THAN 6 SPACES AS PERMITTED PER
 230.70/230.71.
 PLEASE KNOW THIS NOTE WILL NOT APPLY IF MCB IS
 INSTALLED. PLEASE ALSO KNOW NOTE IS ONLY FOR
 INFORMATION PURPOSE AS SERVICE AS SHOWN IS NOT GRANTED
 AT THIS TIME.
  
 16) NOTE: PLEASE SEE THE FEEDERS FROM THE PROPOSED MDP
 TO THE EACH DP PANEL ARE LARGE ENOUGH AND DO NOT MEET
 310.16, 240.4.
 PLEASE SEE THE MDP SHOWS 800AMP RATED BREAKERS ON
 CONDUCTORS ONLY RATED AT 620AMPS.
 110.4
  
 17) NOTE: PLEASE SEE THE DP PANELS ARE NOT RATED FOR
 THE OVER CURRENT PROTECTION FEEDING SAID EQUIPMENT.
 PLEASE SEE MDP SHOWS 800AMP BREAKERS FEEDING 600AMP
 RATED PANELS.
 110.3, 90.7, 408, 240 ETC
  
 18) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS PER
 NEC 220.
 PLEASE SEE NO LOAD SUMMARY WAS SUBMITTED TO INDICATE
 HOW LOADS WERE DERIVED.
 PLEASE SEE LOADS ON A/C UNITS NEED TO BE CLARIFIED FOR
 THE NEXT COMMENT #19.
 PLEASE SEE 215.3, 230.42 AS ALL CONTINUOUS LOADS MUST
 BE FIGURED AT 125%.
 PLEASE SEE 2005 NEC. AS THESE ARE NOT SUBMITTED, NO
 REVIEW CAN BE DONE AT THIS TIME.
  
 19) NOTE: PLEASE SEE 424.3B FOR MINIMUM OVER CURRENT
 PROTECTION FOR A/ C UNITS WITH HEAT.
  
  
 ** PLEASE SEE ONE SET OF PLANS IS REDLINED FOR MANY OF
 THESE ITEMS WHICH MAY HELP TO LOCATE ITEMS AS NOTED.
  
 ** PLEASE KNOW AS STATED ON PREVIOUS REVIEW: PLEASE BE
 SURE TO CALL IF THERE ARE ANY QUESTIONS OR COMMENTS
 WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF THERE ARE
 ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, NOT
 UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE AND THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-05 21:01:28PLANS IN ELEC FOR REVIEW; REVIEW TO COMMENCE 6/6.