| Date |
Text |
| 2007-06-06 14:29:32 | ** UNSAT ** |
| | |
| | *** PLEASE KNOW THAT AS THERE ARE MANY ITEMS WHICH ARE |
| | NOT SHOWN FOR CODE COMPLIANCE AT THIS TIME OR MISSING |
| | FOR REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING |
| | REVIEW NOT YET ABLE TO BE MADE. |
| | |
| | 1) NOTE:PLEASE KNOW THAT PERMIT APPLICATIONS WAS |
| | SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH WILL |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS, |
| | ARCHITECTURAL SHEETS AND FIRE ALARM SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE NOW SEE MISSING THE ATTACHED PRINT OUT |
| | FROM THE STATE WHICH INDICATES LANDSCAPE FIRM WITH A |
| | DIFFERENT LICENSE NUMBER THAN THAT LISTED ON THE TITLE |
| | BLOCKS ON PLANS. PLEASE SEE THE ADDRESS WHICH IS ALSO |
| | LISTED ON THE TITLE BLOCKS WHICH IS DIFFERENT THAN THAT |
| | OF THE STATE. |
| | PLEASE LIST THE CORRECTED INFORMATION ON TITLE BLOCKS. |
| | PLEASE KNOW THAT THE PRIMARY ADDRESS AS LISTED WITH THE |
| | STATE IS REQUIRED TO BE ON PLANS AND ANY SATELLITE |
| | OFFICES MAY INCLUDE THEIR ADDRESS IN ADDITION. PLEASE |
| | ADJUST AND LIST THE LICENSE INFORMATION. 61G1-16.004, |
| | FS 481.219. |
| | **PLEASE KNOW THIS INFORMATION IS REQUIRED WHETHER OR |
| | NOT COMMENT IS MADE BY OTHER REVIEWER(S) OR TRADES. |
| | |
| | 4) NOTE: PLEASE SEE THE TITLE BLOCKS ON MECHANICAL |
| | PLANS WHICH IS MISSING THE CERTIFICATE OF AUTHORIZATION |
| | AS LISTED ON ELECTRICAL AND PLUMBING SHEETS FOR MEP |
| | FIRM. |
| | PLEASE SEE FAC 61G15-23.002, FS 471.023. |
| | **PLEASE KNOW THIS IS REQUIRED WHETHER OR NOT COMMENT |
| | IS MADE BY OTHER TRADES. |
| | |
| | 5) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE MISSING |
| | THE SIGNATURE FROM THE OWNER AGENT. |
| | 13-103.1.1.1 AND AS LISTED ON FLA-COM FORM. |
| | |
| | 6) NOTE: PLEASE SEE MISSING INFORMATION ON CIVIL PLANS |
| | FOR ENGINEERING FIRM AND ENGINEER. |
| | PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION |
| | NUMBER AS REQUIRED PER FAC 61G15-23.002 AND FS |
| | 471.023. |
| | ** PLEASE KNOW THIS INFORMATION IS REQUIRED FOR SHEETS |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. THIS |
| | HAS BEEN NOTED TO THE CIVIL ENGINEERING REVIEWER. |
| | |
| | 7) NOTE: PLEASE SEE THE ATTACHED ENGINEERING REPORTS |
| | WHICH CONTAIN A *RUBBER-STAMP* IN LIEU OF THE REQUIRED |
| | *ORIGINAL* SIGNATURE FROM THE ENGINEER OF RECORD. THIS |
| | IS REQUIRED PER FS 471.025, FAC 61G15-23.002 ** THIS |
| | WAS NOTED TO THE STRUCTURAL REVIEWER HOWEVER EVEN IF |
| | COMMENT IS NOT MADE BY THE STRUCTURAL REVIEWER THIS IS |
| | REQUIRED. |
| | |
| | 8) NOTE: PLEASE SEE FBC 2004 W/ 2006 REVISIONS FOR |
| | CHAPTER 13 COMPLIANCE. PLEASE KNOW THAT CHAPTER 13 |
| | CHANGES TO THE 2004 FBC WENT INTO AFFECT OCT. 1ST,2005 |
| | AND HAS BEEN ENFORCED SINCE THAT DATE. |
| | PLEASE SEE 13-413.1ABC.1 FOR WORST CASE VOLTAGE DROP |
| | FOR FEEDERS AND BRANCH CIRCUITS TO BE INDICATED. PLEASE |
| | SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR LIGHTING |
| | CONTROL SYSTEM(S) TO BE INDICATED. PLEASE INCLUDE |
| | SCHEDULING, SYSTEM, ZONES FOR SQ FT LIMITS, OVER RIDES |
| | AND LOCATIONS, SEPARATE SPACE CONTROLS ETC. PLEASE BE |
| | SURE TO INCLUDE ALL MAXIMUM OVER RIDE TIMES ON DEVICES |
| | WHICH ARE IN DESIGN. |
| | NO SYSTEMS, DEVICES OF ANY KIND WERE FOUND ON PLANS OR |
| | DESIGNED. |
| | PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO NOT |
| | CORRELATE WITH PLANS FOR TYPES OF FIXTURES, NUMBER OF |
| | FIXTURES AND WATTAGE OF FIXTURES AS SHOWN ON PLANS. |
| | PLEASE COORDINATE ALL OF THESE AS SEVERL ITEMS DO NOT |
| | MATCH. |
| | PLEASE SEE THE METHOD OF CONTROL IS BEING SHOWN AS |
| | *MANUAL ON/OFF* ON ENERGY CALCULATIONS WHICH IS NOT |
| | POSSIBLE WHEN AUTOMATED LIGHTING CONTROL(S) IS |
| | REQUIRED. |
| | PLEASE SEE THE PRINT OUT OF THE LIGHTING COMPLIANCE |
| | SHEETS SEEMED TO HAVE CUT OFF MANY OF THE ROOM/AREAS |
| | IDENTIFICATIONS AS LISTED. THESE NEED TO BE CLEAR AND |
| | VISIBLE FOR REVIEW. |
| | PLEASE SEE 13-415.1.AB.1.1, 13-415.2,13-415.1.ABC.2, |
| | 13-415.2.ABC.1.2 ETC. |
| | |
| | ** PLEASE KNOW AS COMPLIANCE WITH CHAPTER 13 WAS NOT |
| | DESIGNED INTO THE PROJECT, NO REVIEW OF ANY |
| | SYSTEMS/DEVICES ETC COULD BE REVIEWED FOR CODE |
| | COMPLIANCE. |
| | |
| | 9) NOTE: PLEASE KNOW EVEN AS THE LOW VOLTAGE |
| | SYSTEMS(EXCLUDING FIRE ALARM, SEE NEXT NOTE FOR FA) ARE |
| | SHOWN ON PLANS, SEPARATE PERMITS WILL BE REQUIRED FOR |
| | THESE SYSTEMS. THESE PLANS MAY BE REFERENCED FOR |
| | PERMITTING. |
| | |
| | 10) NOTE: PLEASE KNOW EVEN AS THE FIRE ALARM AND FIRE |
| | SPRINKLER SYSTEMS ARE REQUIRED TO BE SHOWN ON BASED |
| | BUILDING PLANS FOR REVIEW, THESE WILL BE REQUIRED TO BE |
| | UNDER SEPARATE PERMITS WITH PLANS SUBMITTED |
| | SEPARATELY. |
| | ** PLEASE INCLUDE ALL REQUIRED LOCATIONS AND LEVELS OF |
| | HORN, STROBES, AND HORN/STROBES ON PLANS FOR FBC |
| | CHAPTER 11 ADA COMPLIANCE. THERE ARE MANY DEVICES |
| | ALREADY SHOWN, HOWEVER SOME LOCATIONS DO NOT MEET |
| | 11-4.28.1 AND NO LEVELS OF ANY STROBE DEVICES COULD BE |
| | LOCATED PER 11-4.28.3(4). |
| | THESE ARE MINIMUM LOCATIONS AND LEVELS. PLEASE BE SURE |
| | TO SEE ANY FIRE REVIEW COMMENTS FROM FIRE MARSHAL WHICH |
| | MAY ALSO AFFECT THE PLANS. |
| | |
| | 11) NOTE: PLEASE SEE 230.2 AS A SEPARATE SERVICE IS |
| | BEING REQUESTED FOR THE NEW BUILDING, HOWEVER IN ORDER |
| | FOR THE NEW SERVICE TO BE GRANTED AND THIS ADDITION TO |
| | BE CONSIDERED AS *SEPARATE BUILDING* BY DEFINITION OF |
| | THE FBC VERIFICATION OF REQUIRED SEPARATION AND RATING |
| | ON DOORS/OPENINGS NEEDS TO BE PROVIDED. THE EXISTING |
| | EXIT DOORS APPEAR TO EXIT INTO THIS NEW ADDITION AND |
| | APPLICATION IS TO BUILD AN *ADDITION TO EXISTING |
| | BUILDINGS*. |
| | PLANS DO SEEM TO SHOW COMPLIANCE FOR STRUCTURAL |
| | COLLAPSE OF EACH WITHOUT AFFECTING THE STRUCTURAL |
| | INTEGRITY OF THE OTHER STRUCTURE. PLEASE KNOW AS REVIEW |
| | OF THE SERVICE WILL BE DONE AND NOTED BELOW HOWEVER THE |
| | SERVICE AS SUBMITTED AND SHOWN IS NOT BEING GRANTED AT |
| | THIS TIME. THIS EXISTING SERVICE FEEDING EXISTING |
| | BUILDING WOULD BE REQUIRED TO BE UPGRADED TO FEED THE |
| | NEW ADDITION. |
| | FBC 106.1.2. |
| | 230.2, 230.70, 230.71, 230.72 ETC |
| | |
| | 12) NOTE: PLEASE SEE 620.23 AND 620.24 FOR MISSING |
| | DEDICATED BRANCH CIRCUITS FOR THE ELEVATOR EQUIPMENT |
| | ROOM. |
| | *BRANCH CIRCUITS MAY NOT FEED OTHER AREAS AS SHOWN. |
| | |
| | 13) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS ON STAIR |
| | TOWERS AND EXIT PATHS FOR REVIEW. THE MINIMUM LEVELS |
| | FOR LIGHTING CAN NOT BE REVIEWED AT THIS TIME. PLEASE |
| | SEE 2003 NFPA-101 (LIFE SAFETY CODE) 7.8.1.3, 7.9.2.2 |
| | FOR MINIMUM LEVELS. |
| | |
| | 14) NOTE: PLEASE SEE THE TEMPORARY EXIT CORRIDORS BEING |
| | PROPOSED ARE NOT ON ELECTRICAL PLANS, YET THE |
| | ARCHITECTURAL SHEETS INDICATE LIGHTING FOR THESE |
| | AREAS. |
| | PLEASE ALSO SEE THE ARCHITECTURAL DESIGN INDICATES THIS |
| | AREA BEING COMPLETELY ENCLOSED AND NO EMERGENCY |
| | LIGHTING FOR REQUIRED EGRESS PATH UNDER EM CONDITIONS. |
| | PLEASE SEE NOTE #13 ABOVE WITH RESPECT TO THE MINIMUM |
| | LIGHTING LEVELS AND PLEASE ADJUST BOTH A AND E SHEETS |
| | FOR CORRECTIONS AND PHOTO-METRICS TO BE SUBMITTED. LS |
| | 101 7.8 AND 7.9. |
| | PLEASE SEE 700.12F FOR CIRCUITING. |
| | |
| | 15) NOTE:PLEASE SEE THE PROPOSED MDP AS SHOWN |
| | CONTAINS NO MAIN CIRCUIT BREAKER. PLEASE PLACE NOTE ON |
| | PLANS FOR DEAD-FRONT TO BE PERMANENT FROM MANUFACTURE |
| | WITH NO MORE THAN 6 SPACES AS PERMITTED PER |
| | 230.70/230.71. |
| | PLEASE KNOW THIS NOTE WILL NOT APPLY IF MCB IS |
| | INSTALLED. PLEASE ALSO KNOW NOTE IS ONLY FOR |
| | INFORMATION PURPOSE AS SERVICE AS SHOWN IS NOT GRANTED |
| | AT THIS TIME. |
| | |
| | 16) NOTE: PLEASE SEE THE FEEDERS FROM THE PROPOSED MDP |
| | TO THE EACH DP PANEL ARE LARGE ENOUGH AND DO NOT MEET |
| | 310.16, 240.4. |
| | PLEASE SEE THE MDP SHOWS 800AMP RATED BREAKERS ON |
| | CONDUCTORS ONLY RATED AT 620AMPS. |
| | 110.4 |
| | |
| | 17) NOTE: PLEASE SEE THE DP PANELS ARE NOT RATED FOR |
| | THE OVER CURRENT PROTECTION FEEDING SAID EQUIPMENT. |
| | PLEASE SEE MDP SHOWS 800AMP BREAKERS FEEDING 600AMP |
| | RATED PANELS. |
| | 110.3, 90.7, 408, 240 ETC |
| | |
| | 18) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS PER |
| | NEC 220. |
| | PLEASE SEE NO LOAD SUMMARY WAS SUBMITTED TO INDICATE |
| | HOW LOADS WERE DERIVED. |
| | PLEASE SEE LOADS ON A/C UNITS NEED TO BE CLARIFIED FOR |
| | THE NEXT COMMENT #19. |
| | PLEASE SEE 215.3, 230.42 AS ALL CONTINUOUS LOADS MUST |
| | BE FIGURED AT 125%. |
| | PLEASE SEE 2005 NEC. AS THESE ARE NOT SUBMITTED, NO |
| | REVIEW CAN BE DONE AT THIS TIME. |
| | |
| | 19) NOTE: PLEASE SEE 424.3B FOR MINIMUM OVER CURRENT |
| | PROTECTION FOR A/ C UNITS WITH HEAT. |
| | |
| | |
| | ** PLEASE SEE ONE SET OF PLANS IS REDLINED FOR MANY OF |
| | THESE ITEMS WHICH MAY HELP TO LOCATE ITEMS AS NOTED. |
| | |
| | ** PLEASE KNOW AS STATED ON PREVIOUS REVIEW: PLEASE BE |
| | SURE TO CALL IF THERE ARE ANY QUESTIONS OR COMMENTS |
| | WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF THERE ARE |
| | ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, NOT |
| | UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE AND THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-06-05 21:01:28 | PLANS IN ELEC FOR REVIEW; REVIEW TO COMMENCE 6/6. |