| 2007-07-26 16:06:35 | 512 SPENCER MEDIA CENTER 070502239 |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07050239 |
| | ADD: 512 SPENCER DR |
| | CONT: ANDERSON- MOORE |
| | TEL: (561)662-1819 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | . |
| | |
| | 3) GROUND FLOOR ENGINEERING CALCULATIONS TO HAVE |
| | ORIGINAL SIGNATURE FORM THE DESIGN PROFESSION, NOT |
| | RUBBER STAMP OR COLOR COPIES OF SIGNATURE. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLICRECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 |
| | |
| | 4) GROUND FLOOR ENGINEERING CALCULATIONS ARE BASED ON |
| | SSCE 7-98, PLEASE SEE THE REFERENCED STANDARD UNDER THE |
| | 2004 FBC CHAPTER 35 IS ASCE 7-02, PLEASE CORRECT . |
| | |
| | 5) SHEET A-1 DESCRIPTION OF PROJECT/ CODE : |
| | 5A) BUILDING TYPE: A UNPROTECTED SEE TABLE 601, EITHER |
| | THE BUILDING CONSIDERED A TYPE I OR TYPE II, IN EITHER |
| | CASE THE A & B DESIGNATION INDICATES THE AMOUNT OF |
| | HOURS OF FIRE RESISTANCE RATING REQUIRED FOR STRUCTURAL |
| | MEMBERS. TABLE 503 WILL PROVIDE THE ALLOWABLE AREAS |
| | UNDER THE OCCUPANCY CLASSIFICATION. EDUCATIONAL USAGE |
| | TYPE II-A WILL ALLOW 14,500 SQ FT. THE PLAN INDICATES |
| | 14,997 SQ FT FOR THE FIRST FLOOR. SEE IF ANY FRONTAGE |
| | INCREASES MAY BE TAKEN, SEE 506.2 IF SO PROVIDE |
| | CALCULATIONS. |
| | |
| | 5B) THE SECOND ISSUE IS THE OCCUPANCY TYPE PLANS |
| | INDICATE **CS** THERE ISN?T ANY TYPE OCCUPANCY |
| | CLASSIFICATION SEE SECTION 302.1 . |
| | |
| | 5C) PLEASE INDICATE THE DESIGN INTENT FOR THIS PERMIT. |
| | PLANS INDICATE FIRE SEPARATION BETWEEN BUILDINGS, 3 HR |
| | SEPARATION, PLEASE INDICATE IF THIS AN ADDITION TO THE |
| | EXISTING BUILDING TO BE CONSIDERED UNDER THE 2004 |
| | EXISTING BUILDING CODE, AN ADDITION OR WITH A **FIRE |
| | WALL** |
| | CONSTITUTING A TOTALLY SEPARATE BUILDING. |
| | NOTE: THIS REVIEW WILL BE CONSTRUED AS A NEW SEPARATE |
| | BUILDING, AND A REMODEL OF EXISTING (2) EDUCATIONAL |
| | BUILDINGS. |
| | |
| | 6) SHEET A-35& A-36 ARE THE LIFE SAFETY SHEETS: 6A) |
| | THEY DO NOT PROVIDE THE OCCUPANT LOAD PER ROOM( PLANS |
| | ARE ILLEGIBLE)PLEASE INDICATE THE OCCUPANT LOAD. 6B) |
| | ALSO PROVIDE THE OCCUPANT LOAD FOR THE EXISTING STAIRS |
| | AND THE OCCUPANT LOADS FOR THE NEW STAIRWAYS. 6C) |
| | PLEASE PROVIDE ADDITIONAL INFORMATION FOR THE EXITING |
| | OF NEW BUILDING, IT APPEARS THAT THE CHILDREN ARE BEING |
| | LEAD BACK INTO SOME TYPE OF COURT OR YARD, PLANS ARE |
| | NOT CLEAR AS TO THE INTENT.1018.1 MINIMUM NUMBER |
| | OF EXITS. |
| | |
| | ALL ROOMS AND SPACES WITHIN EACH STORY SHALL BE |
| | PROVIDED WITH AND HAVE ACCESS TO THE MINIMUM NUMBER OF |
| | APPROVED INDEPENDENT EXITS AS REQUIRED BY TABLE 1018.1 |
| | BASED ON THE OCCUPANT LOAD, EXCEPT AS MODIFIED IN |
| | SECTION 1014.1 OR 1018.2. FOR THE PURPOSES OF THIS |
| | CHAPTER, OCCUPIED ROOFS SHALL BE PROVIDED WITH EXITS AS |
| | REQUIRED FOR STORIES. THE REQUIRED NUMBER OF EXITS FROM |
| | ANY STORY, BASEMENT OR INDIVIDUAL SPACE SHALL BE |
| | MAINTAINED UNTIL ARRIVAL AT GRADE OR THE PUBLIC WAY . |
| | EXCEPTION: A FENCED OUTDOOR ASSEMBLY OCCUPANCY SHALL |
| | HAVE AT LEAST TWO WIDELY SEPARATED MEANS OF EGRESS FROM |
| | THE ENCLOSURE. IF MORE THAN 6,000 PERSONS ARE TO BE |
| | SERVED BY SUCH MEANS OF EGRESS, THERE SHALL BE AT LEAST |
| | THRE E MEANS OF EGRESS; IF MORE THAN 9,000 PERSONS ARE |
| | TO BE SERVED, THERE SHALL BE AT LEAST FOUR MEANS OF |
| | EGRESS. |
| | 1206.3.3 COURT DRAINAGE. |
| | THE BOTTOM OF EVERY COURT SHALL BE PROPERLY GRADED AND |
| | DRAINED TO A PUBLIC SEWER OR OTHER APPROVED DISPOSAL |
| | SYSTEM COMPLYING WITH THE FLORIDA BUILDING CODE, |
| | PLUMBING . |
| | |
| | 1023.6 ACCESS TO A PUBLIC WAY . |
| | THE EXIT DISCHARGE SHALL PROVIDE A DIRECT AND |
| | UNOBSTRUCTED ACCESS TO A PUBLIC WAY . |
| | EXCEPTION: WHERE ACCESS TO A PUBLIC WAY CANNOT BE |
| | PROVIDED, A SAFE DISPERSAL AREA SHALL BE PROVIDED WHERE |
| | ALL OF THE FOLLOWING ARE MET: |
| | 1.THE AREA SHALL BE OF A SIZE TO ACCOMMODATE AT |
| | LEAST 5 SQUARE FEET (0.28 M 2 ) FOR EACH PERSON. 2. THE |
| | AREA SHALL BE LOCATED ON THE SAME PROPERTY AT LEAST 50 |
| | FEET (15 240 MM) AWAY FROM THE BUILDING REQUIRING |
| | EGRESS. |
| | 3.THE AREA SHALL BE PERMANENTLY MAINTAINED AND |
| | IDENTIFIED AS A SAFE DISPERSAL AREA. |
| | 4.THE AREA SHALL BE PROVIDED WITH A SAFE AND |
| | UNOBSTRUCTED PATH OF TRAVEL FROM THE BUILDING. |
| | |
| | 6D) DOOR 146- A THE PLANS DO NOT PROVIDE THE DISTANCE |
| | TO THE OPPOSITE WALL, THE DOOR SCHEDULE DOES NOT |
| | INDICATE ANY DOOR RATING. 1023.5.2 CONSTRUCTION AND |
| | OPENINGS. |
| | WHERE AN EGRESS COURT SERVING A BUILDING OR PORTION |
| | THEREOF IS LESS THAN 10 FEET (3048 MM) IN WIDTH, THE |
| | EGRESS COURT WALLS SHALL BE NOT LESS THAN 1-HOUR |
| | FIRE-RESISTANCE-RATED EXTERIOR WALLS COMPLYING WITH |
| | SECTION 704 FOR A DISTANCE OF 10 FEET (3048 MM) ABOVE |
| | THE FLOOR OF THE COURT, AND OPENINGS THEREIN SHALL BE |
| | EQUIPPED WITH FIXED OR SELF-CLOSING, ?-HOUR OPENING |
| | PROTECTIVE ASSEMBLIES. |
| | |
| | 6E) DOOR 146-B ALSO HAS THE SAME CONFIGURATION BUT THE |
| | SECOND ISSUE IS THERE APPEARS TO BE A SECOND SET OF |
| | DOORS FURTHER OUT THE EXIT DISCHARGE, PLEASE SEE A-9 |
| | DISCREPANCY, PLEASE CORRECT. |
| | |
| | 6F) PLEASE ALSO SHOW THE EXIT LIGHTING; 1006.1 MEANS OF |
| | EGRESS ILLUMINATION. 1006.1.1 |
| | ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED IN |
| | ACCORDANCE WITH THIS SECTION FOR EVERY BUILDING AND |
| | STRUCTURE. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT |
| | ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS AND PASSAGEWAYS LEADING TO |
| | AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT |
| | DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS, WALKWAYS AND EXIT |
| | PASSAGEWAYS LEADING TO A PUBLIC WAY . |
| | |
| | 7) SHEET A-25 PLEASE CORRECT THE DOOR SCHEDULE AS TO |
| | THE RATING FOR FIRE RATED DOORS. PLEASE SEE 715.3 AND |
| | TABLE 715.3 FOR MINUTE AND HOUR RATINGS. |
| | |
| | 8) SHEET A-25 CORRIDORS WITH AN OCCUPANT LOAD > THAN 30 |
| | REQUIREA 1 HR FIRE RATING, PLANS INDICATE WINDOW TYPE |
| | (F) TO BE 1 HR FIRE LITE, PLEASE PROVIDE LITERATURE, |
| | PRODUCT APPROVALS. |
| | |
| | 9) FIRST FLOOR AND SECOND FLOOR THE ELEVATOR SHAFT IS |
| | MISSING THE DOOR AND RATING FOR A SHAFT ENCLOSURE, |
| | TABLE 715.3. |
| | |
| | 10) ELEVATOR MACHINE ROOM IS THROUGH THE OCCUPIED USE |
| | ROOMS.3006.1 ACCESS. |
| | AN APPROVED MEANS OF ACCESS SHALL BE PROVIDED TO |
| | ELEVATOR MACHINE ROOMS AND OVERHEAD MACHINERY SPACES. |
| | THIS AN ACCESSIBLE SPACE, NOT THROUGH THE CLASSROOMS. |
| | |
| | 11)SHEET A-31 NEW STAIRS DO NOT INDICATE WHERE THE |
| | AREA OF RESCUE ASSISTANCE WOULD BE LOCATED. PLEASE |
| | PROVIDE THE INFORMATION AS TO SIZE OF EACH REQUIRED |
| | AREA OF RESCUE ASSISTANCE, TWO-WAY COMMUNICATION AND |
| | IDENTIFICATION. 11-4.3.11. (1-5). |
| | |
| | 12) SHEET A-31 STAIR INDICATES A VOID BENEATH THE |
| | STRINGER SEE 11-4.4.2. HEADROOM. |
| | |
| | 13) SHEET A-12-13 INDICATES REFLECTED CEILING LIGHTING |
| | LEGEND INDICATES EXIT LIGHTS AND DIRECTIONAL?S BUT THE |
| | PLAN IS MISSING THE EXIT LIGHTS AND DIRECTIONAL?S. |
| | 1006.1 MEANS OF EGRESS ILLUMINATION. |
| | |
| | 14) SHEET S-1 INDICATES THAT A SOILS TEST WAS COMPLETED |
| | BY SOILPROBE ENGINEERING, PLEASE SUBMIT (2) ORIGINAL |
| | SIGNED & SEALED DOCUMENTS. 1802.2.1 QUESTIONABLE SOIL. |
| | WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| | DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT |
| | SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION |
| | BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE |
| | PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . |
| | 15) ) 1609.1.4 PROTECTION OF OPENINGS. IN WIND-BORNE |
| | DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | LAZED OPENINGS LOCATED WITHIN 30FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN30 FEET (9.1 M) |
| | ABOVE GRADE SHALL MEETTHE PROVISIONS OF THE SMALL |
| | MISSILE |
| | TEST. |
| | FL BLD CODE 1609.1.4: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT |
| | INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS |
| | ARE AS FOLLOWS: |
| | |
| | 15A) FIXED GLAZING |
| | 15B) STAINED GLASS |
| | 15C) GLAZED SWING DOORS |
| | 15D) HOLLOW CORE EXTERIOR METAL DOORS |
| | 15E) SUNSHADE |
| | 15F) LOUVERS |
| | 15G) ROOFING ASSEMBLIES |
| | |
| | 16)PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. SEE |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 17) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 18)THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE |
| | FOLLOW ITEMS: |
| | |
| | _XXX__ CONTRACTOR DID NOT PROVIDE PRODUCT APPROVAL. |
| | |
| | __XXX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO |
| | BE USED. |
| | |
| | __XXX__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR |
| | ZONE _2&3__ . |
| | |
| | __XXX__ THE SYSTEM PROVIDED STATESLIMITATION# 7, |
| | SHOULD THE FASTENER RESISTANCE BE LESS THAN THAT |
| | REQUIRED, AS DETERMINED BY THE BUILDING OFFICIAL, A |
| | REVISED FASTENER SPACING, PREPARED , SIGNED AND SEALED |
| | BY A FLORIDA REGISTEREDPROFESSIONAL ENGINEER, |
| | REGISTERED |
| | ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE |
| | SUBMITTED. |
| | |
| | ___THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO |
| | ENHANCED FASTENING ALLOWED. |
| | |
| | |
| | 19) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |