| 2007-05-14 16:36:31 | ** UNSAT ** |
| | |
| | ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| | BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| | BY THE CITY OF WEST PALM BEACH. |
| | |
| | 1) NOTE:PLEASE SEE THAT PLANS ARE REQUIRED TO STATE |
| | ALL RELEVANT CODES WITH RESPECT TO SCOPE OF WORK. |
| | PLEASE SEE THIS PROJECT IS UNDER THE FBC 2004 W/2006 |
| | REVISIONS. |
| | PLEASE ALSO INCLUDE THE 2005 NFPA-70 (NEC) AND THE 2002 |
| | NFPA-72. |
| | |
| | 2) NOTE: PLEASE INDICATE THE CORRECT SERVICE SIZE. FBC |
| | 106.3.5.4. |
| | |
| | 3) NOTE: PLEASE SEE THE MISSING GFI PER 210.52D, |
| | 210.8A |
| | |
| | 4) NOTE: PLEASE SEE FBC R313 AS THE EXISTING DWELLING |
| | IS REQUIRED TO BE BROUGHT UP TO CODE OR THE EXISTING IS |
| | TO SHOW MEETING THE CURRENT CODE FOR SMOKE |
| | DETECTION/SOUNDING DEVICES. PLEASE SHOW A LAYOUT OF THE |
| | EXISTING DWELLING WHICH WILL REQUIRE SMOKE DEVICES |
| | INSIDE AND OUTSIDE ALL BEDROOMS AND ON EACH LEVEL IF A |
| | MULTI-LEVEL BUILDING. |
| | PLEASE SHOW THE SMOKE DEVICES AS SA OR SD DEPENDING ON |
| | THE TYPE OF DEVICE. |
| | NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | 5) NOTE: PLEASE SUBMIT A COMPLETED CODE COMPLIANT PANEL |
| | SCHEDULE PER 408.4, 310.16, 240.4. |
| | PLEASE REVISE CIRCUITS AND CIRCUIT NUMBERS ON PANEL |
| | SCHEDULE TO COORDINATE WITH ALL SPECIFIC ROOMS, |
| | CIRCUITS AND AREAS.. |
| | FBC 106.3.5.4, 106.1.2 |
| | |
| | 6) NOTE: PLEASE VERIFY THE EXISTING AHU AS THE HEAT |
| | STRIP IS SHOWN AS 10KW, YET THE OVER CURRENT PROTECTION |
| | IS SHOWN AT 50AMPS WHICH IS TOO LOW. PLEASE SEE 424.3B |
| | FOR MINIMUM OF 125% |
| | 220, 408.4, 240.4 |
| | FBC 106.1.2, 106.3.5.4 |
| | |
| | 7) NOTE: PLEASE SEE 422.13 AS THE MINIMUM LOADS FOR |
| | WATER HEATERS IS THAT OF 125%. |
| | |
| | 8) NOTE: PLEASE SEE THE PLANS INDICATE A NEW AHU, BUT |
| | NO NEW CU? |
| | PLEASE VERIFY WHAT IS NEW, WHAT IS EXISTING, LOCATIONS |
| | ETC. |
| | PLEASE SEE MISSING DISCONNECT FOR AHU. 440.11. |
| | |
| | 9) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE |
| | CONNECTION TO NEW FOOTER STEEL PER 250.50. PLEASE ALSO |
| | CLARIFY EXISTING OR NEW CONNECTION TO COLD WATER. |
| | |
| | 10) NOTE: PLEASE SEE ITEMS ON PANEL SCHEDULE WITH DOES |
| | NOT INCLUDE ANY LOADS ON SCHEDULE OR IN LOAD |
| | CALCULATIONS. |
| | PLEASE SEE 220.87 WHEN ADDING LOADS TO EXISTING |
| | DWELLING. |
| | |
| | 11) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER |
| | HEATER. 422.31, 422.360 |
| | |
| | 12) NOTE: PLEASE CLARIFY SPA, IS THIS ELECTRIC? GFI |
| | PROTECTION?, CIRCUIT ON PANEL ? LOAD? |
| | FBC 106.1.2, 106.3.5.4 |
| | |
| | 13) NOTE: PLEASE SEE MISSING COMPLETED INFORMATION ON |
| | TITLE BLOCK FOR ARCHITECT. PLEASE INCLUDE PHONE # FOR |
| | CONTACTING. |
| | FAC 61G1-16.004. |
| | |
| | 14) NOTE: PLEASE INCLUDE SYMBOL LEGEND FOR ALL DEVICES |
| | ON PLANS AND COORDINATE. |
| | |
| | 15) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS FOR |
| | RECESSED LIGHTS AND INCLUDE INFORMATION AS REQUIRED PER |
| | 13-606.1.ABC.1.2.4. |
| | |
| | 16) NOTE: PLEASE KNOW AS SOME INFORMATION HAS NOT YET |
| | BEEN SUBMITTED, SOME INFORMATION CAN NOT BE REVIEWED AT |
| | THIS TIME. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |