| Plan Review Notes For Permit 07050157 |
| Permit Number |
07050157 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-11 16:39:50 | ***************PROVISO**************** | | | A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR | | | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED | | | IMMEDIATELY AHEAD OF EACH MP REGULATOR. | | | | | | B} PER FBC-2004 FUEL GAS, SECTION 404.13.3AN | | | INSULATED COPPER TRACER WIRE SHALL BE INSTALLED | | | ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE | | | TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE | | | INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL. | | | | | | C} PER FBC-2004 FUEL GAS SECTION 408.4 A SEDIMENT TRAP | | | SHALL BE INSTALLED DOWNSTREAM OF THE EQUIPMENT SHUTOFF | | | VALVE AS CLOSE TO THE INLET OF THE EQUIPMENT AS | | | PRACTICAL. | | | | | | | | | |
|