| 2007-05-09 11:32:41 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTION/INFORMATION IS REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. THERE ARE ALREADY APPROVED SIGNED AND SEALED GAS |
| | DRAWINGS BY PROFESSIONAL ENGINEER BRUCE M. |
| | CIARLARIELLO, STATE REGISTRATION #62977 ON MASTER |
| | PERMIT #05110655 SHEET P-602, ANY REVISED CHANGES TO |
| | SAID DRAWINGS MUST BE MADE BY SAID DESIGN PROFESSIONAL |
| | OF RECORD PER FLORIDA STATUTES, CHAPTER 471. THERE |
| | ALREADY IS A GAS PERMIT PRINTED (#07030553 TO HYPOLUXO |
| | PLUMBING INC. FOR THE NATURAL GAS)IF IT IS YOUR |
| | INTENT TO ATTAIN A GAS PERMIT FOR THE EXTERIOR LP TANK |
| | AND PIPING TO THE GENERATOR PLEASE REFERENCE THE SAID |
| | MASTER NUMBER ON THE RESUBMITTAL AND MAKE SURE THE |
| | PERMIT CLERK REFLECTS THESE CHANGES ON THE FRONT SCREEN |
| | ON THE RESUBMITTAL. |
| | |
| | NOTE: THERE ARE TWO GAS TYPES INDICATED ON SHEET P-602 |
| | OF THE APPROVED MASTER #05110655 (LP AND NATURAL). IT |
| | IS SUGGESTED THAT YOU CHECK WITH THE CONTRACTOR (WEST |
| | CONSTRUCTION INC.) ON THE MASTER PERMIT #05110655 AND |
| | REVIEW THE APPROVED DRAWINGS TO CORRELATE THIS |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |