Plan Review Notes
Plan Review Notes For Permit 07050154
Permit Number 07050154
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-06-01 12:34:19*****DENIED*****
  
  
 1.THE PROJECT LOCATION SHALL BE IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET.
  
 2.PLEASE EXPLAIN THE BUSINESS'S USE OF THIS PRODUCT.
 SPECIFY THE PRODUCT'S HEALTH HAZARD CLASSIFICATION.
  
 3.SIGNS WILL BE POSTED PROHIBITING SMOKING WITHIN 25
 FEET OF OUTDOOR STORAGE, DISPENSING, OR OPEN-USE
 AREAS.
  
 4.THE STORAGE, DISPENSING, USE AND HANDLING AREAS
 SHALL BE SECURED AGAINST UNAUTHORIZED ENTRY AND
 SAFEGUARDED WITH SUCH SUCH PROTECTIVE FACILITIES AS
 PUBLIC SAFETY REQUIRES.
  
 5.GUARD POSTS OR OTHER APPROVED MEANS SHALL PROVIDED
 TO PROTECT THE (1) STORAGE TANK AND CONNECTED PIPING,
 VALVES AND FITTINGS, (2) DISPENSING AREAS,(3) USE
 AREAS .WHEN GUARD POST ARE INSTALLED , THE POST SHALL
 MEET THE CRITERIA AS PER NFPA 1, UNIFORM FIRE CODE,
 2003 EDITION - CHAPTER 60.1.16.2
  
 6.OUTDOOR STORAGE AND USE AREAS SHALL BE LOCATED NOT
 CLOSER THAN 20 FEET FROM A PROPERTY LINE THAT CAN BE
 BUILT UPON, STREET, ALLEY, OR PUBLIC WAY, EXCEPT THAT A
 TWO-HOUR FIRE-BARRIER WALL, WITHOUT OPENINGS AND
 EXTENDING 30 INCHES ABOVE AND TO THE SIDES OF THE
 STORAGE AREA SHALL BE PERMITTED IN LIEU OF SUCH
 DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW