| 2007-06-01 15:45:41 | BUILDING PLAN REVIEW |
| | PERMIT: 07050154 |
| | ADD:7230GEORGIA AVE |
| | CONT: CARLSON/ROSS POOL & SPA |
| | TEL: (561)588-1200 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 1ST |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC*. |
| | |
| | 3)2004 FL. BLD CODE 1603.1.4 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 4)THE DESIGN CRITERIA INDICATED ON THE PLANS IS FROM |
| | THE OLD CODE. SEE THE 2004 FBC PAGE 35.6R FOR THE |
| | CORRECT ASCE STANDRD.ALL PLANS SUBMITTED AFTER |
| | OCTOBER, 1, |
| | 2004 SHALL BE DESIGNED TO THE 2004 FLORIDA BUILDING |
| | CODE. ASTMD 1998-91 HAS BEEN UP-DATED, SO, INDICATE THE |
| | NEW REFERENCE STANDARD. |
| | |
| | 5)61G1-16.004 TITLE BLOCK. |
| | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | |
| | 6)IF BOLLARD WILL BE PLACED AROUND THE TANK FOR |
| | PROTECTION, INDICATE THE LOCATION OF EACH BOLLARD ON |
| | THE PLANS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |
| | |
| | |
| | |
| | |
| | |