| 2007-06-06 11:04:28 | BUILDING PLAN REVIEW |
| | PERMIT: 07050148 |
| | ADD: 62347TH ST. |
| | CONT: TREASURE COAST DESIGN INC. |
| | TEL: (561)478-7488 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 1ST |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) 2004 FL. BLD CODE 1603.1.4 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | NOTE: WEST PALM BEACH IS NOT IN THE 130 MPH ZONE. |
| | |
| | 3)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 4)FBC 108.3*THE CLAIMED VALUATION ON THE PERMIT |
| | APPLICATION IS LOW. FOR PERMITTING PURPOSES, VALUATION |
| | OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT |
| | COST EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS |
| | ICC (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS |
| | SERVICES. |
| | |
| | 5)R319.1 LOCATION REQUIRED. |
| | IN AREAS SUBJECT TO DECAY DAMAGE AS ESTABLISHED BY |
| | TABLE R301.2(1) , THE FOLLOWING LOCATIONS SHALL REQUIRE |
| | THE USE OF AN APPROVED SPECIES AND GRADE OF LUMBER, |
| | PRESSURE TREATED IN ACCORDANCE WITH AWPA C1, C2, C3, |
| | C4, C9, C15, C18, C22, C23, C24, C28, C31, C33, P1, P2 |
| | AND P3, OR DECAY -RESISTANT HEARTWOOD OF REDWOOD, BLACK |
| | LOCUST, OR CEDARS. (5.)WOOD SIDING, SHEATHING AND |
| | WALL FRAMING ON THE EXTERIOR OF A BUILDING HAVING A |
| | CLEARANCE OF LESS THAN 6 INCHES (152 MM) FROM THE |
| | GROUND. |
| | |
| | 6)THE EXTERIOR WALL SECTION ON THE FIRST PAGE DOES |
| | NOT MATCH THE THE FLOOR PLAN ON THE SECOND SHEET. THE |
| | FLOOR PLANS SHALL MATCH THE FRAMING PLAN. ALSO, TABLE |
| | 1705.1 |
| | CANNOT BE FOUND IN THE 2004 FBC. CLARIFY. |
| | |
| | 7) 110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PROJECT WAS DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | ) NUMBER OF BEDROOMS |
| | ) NUMBER OF ROOMS |
| | OK ) SQ. FT. LIV SPACE/ FL |
| | OK) SQ. FT. FOOTPRINT |
| | OK) SQ. FT. UNDER ROOF (TOTAL) |
| | |
| | 8) 106.3.3* PRODUCT APPROVALS- 2004 |
| | THOSE PRODUCTS THAT ARE RGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITTING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL.THE DESIGNER OF RECORD SHALL |
| | APPROVE ALL PRODUCT APPROVALS. |
| | NOTE: ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| | _XX___1.)FOR THE FLAT DECK, SELECT THE APPROVED |
| | ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| | IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. |
| | |
| | _XX___2.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES. |
| | |
| | _XX___ 3.)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| | CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| | FL#1654-R1 DOES MATCH THE NOA REPORT SEE |
| | FLORIDABUILDING.ORG FOR MORE INFORMATION. FL#6571 |
| | SUBMITTED STATES "PENDING FBC APPROVAL" |
| | |
| | FYI, RAS 150 IS A PRESCRIPTIVE BUILT UP ROOF SYSTEM |
| | WHICH IS ALLOWED IN HIGH VELOCITY WHEN ADOPTED BY THE |
| | AHJ (FBC R4402.8) BUT IS NOT ALLOWED OUTSIDE OF HIGH |
| | VELOCITY (FBC R905.11.3, STATES IN ACCORDANCE WITH |
| | MANUFACTURER'S INSTRUCTIONS). |
| | |
| | 9)R401.3 DRAINAGE. |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS |
| | TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO |
| | DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE |
| | GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM |
| | OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 |
| | MM). |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |