| Plan Review Notes For Permit 07050139 |
| Permit Number |
07050139 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-06-09 11:34:06 | | | | | | | DENIED | | | | | | 1)THE PERMIT APPLICATION SHALL INCLUDE TWO | | | COPIES OF EACH PRODUCT APPROVAL THAT | | | IS RELEVANT PER 9B-72. | | | | | | 2)THE FLORIDA PRODUCT APPROVAL FL5854 FOR35H DOOR | | | DOES NOT COVER THIS PARTICULAR MODEL "35H (MS)"BUT IT | | | WILL MEET REQUIREMENTS IF THE TYPE OF GLAZING IS | | | CHANGED TO SAF-GLAS AND WILL BE PERMITTED A LOCAL | | | PRODUCT APPROVAL. PLEASE NOTE THAT THE CHOSEN GLAZING | | | (SENTRYGLAS PLUS) DOES NOT MEET THE REQUIRED -66.1 | | | PSF. | | | | | | 3)PROVIDE SPECIFIC TYPE OF 9/16" GLAZING FROM THE | | | PRODUCT APPROVALS AS SOME TYPES DO NOT MEET THE | | | PRESSURE REQUIREMENTS | | | | | | 4)PGT DOES INDEED HAVE FLORIDA STATEWIDE PRODUCT | | | APPROVAL FOR SH-700 WINDOW (FL # 239-R8) | | | | | | 5)FLORIDA COVER SHEET FOR PGT MULLIONS HAS HEAVY WALL | | | HI-LIGHTED BUT STANDARD WALL MIAMI-DADE PLEASE CLARIFY. | | | NOTE STANDARD WILL MEET PRESSURES IN 1X4 MULLION ONLY. | | | | | | 6)PER 106.1.3 FBC* THE BUILDING OFFICIAL MAY | | | ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR | | | PLANS AND SPECIFICATIONS "NO WHITE OUT, PENCIL OR INK" | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | |
|