2007-06-09 11:34:06 
  
 DENIED
  
 1)THE PERMIT APPLICATION SHALL INCLUDE TWO
 COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72.
  
 2)THE FLORIDA PRODUCT APPROVAL FL5854 FOR35H DOOR
 DOES NOT COVER THIS PARTICULAR MODEL "35H (MS)"BUT IT
 WILL MEET REQUIREMENTS IF THE TYPE OF GLAZING IS
 CHANGED TO SAF-GLAS AND WILL BE PERMITTED A LOCAL
 PRODUCT APPROVAL. PLEASE NOTE THAT THE CHOSEN GLAZING
 (SENTRYGLAS PLUS) DOES NOT MEET THE REQUIRED -66.1
 PSF.
  
 3)PROVIDE SPECIFIC TYPE OF 9/16" GLAZING FROM THE
 PRODUCT APPROVALS AS SOME TYPES DO NOT MEET THE
 PRESSURE REQUIREMENTS
  
 4)PGT DOES INDEED HAVE FLORIDA STATEWIDE PRODUCT
 APPROVAL FOR SH-700 WINDOW (FL # 239-R8)
  
 5)FLORIDA COVER SHEET FOR PGT MULLIONS HAS HEAVY WALL
 HI-LIGHTED BUT STANDARD WALL MIAMI-DADE PLEASE CLARIFY.
 NOTE STANDARD WILL MEET PRESSURES IN 1X4 MULLION ONLY.
  
 6)PER 106.1.3 FBC* THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR
 PLANS AND SPECIFICATIONS "NO WHITE OUT, PENCIL OR INK"
  
 BLDG PLAN REVIEW