| Permit Number |
07050139 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-22 18:11:05 | | | | | | | DENIED | | | | | | 1)THE CITY OF WEST PALM BEACH REQUIRES THE | | | FLORIDA STATE PRODUCT APPROVAL COVER | | | SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON | | | WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT | | | SUBMITTED APPLICATIONS WILL BE DENIED | | | YHS-50 IS COVERED BY FLORIDA STATEWIDE APPROVAL FL# | | | 5845 THE SERIES 35H (MS) IS NOT AND HAS LOCAL PRODUCT | | | APPROVAL | | | | | | 2)NO PRODUCT APPROVALS WERE SUBMITTED FOR THE PGT | | | SINGLE HUNG WINDOW UNITS. | | | | | | 3)PROVIDE A KEY PLAN THAT SHOWS ALL EXISTING DOORS | | | AND WINDOWS AND THEIR SIZES, THE SQUARE FOOTAGE OF THE | | | BUILDING AND THE TYPE OF OCCUPANCY. ALSO PROVIDE THE | | | CORRECT WIND EXPOSURE FOR BUILDING SITUATED ON THE | | | INTERCOASTAL (EXP. C) AND THE DESIGN PRESSURES FOR THE | | | OPENINGS FOR ZONE 4 & 5 | | | | | | 4)STATE ON DRAWINGS WHETHER THE STEEL REINFORCING | | | WILL BE USED IN THE FRAME TO INCREASE THE DESIGN | | | PRESSURE REQUIREMENTS. PLEASE BE AWARE THAT THE STATE | | | OF FLORIDA REQUIRES THAT THE MIAMI-DADE NOA PRESSURE | | | VALUES SHALL BE DIVIDED BY 1.33 TO COMPLY WITH THE 2004 | | | FBC (SEE PAGE 3 OF THE FLORIDA COVER SHEETS) | | | | | | 5)PROVIDE THE TYPE OF GLAZING IN THE 35H DOOR AS THE | | | DESIGN PRESSURES DIFFER WITH THE DIFFERENT TYPES. | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|