2007-05-22 16:29:12 
  
 DENIED
  
 1)PROVIDE WIND DESIGN DATA ON DRAWINGS PER
 1603.1.4 FBC
  
 2)WORK ON EXISTING BUILDINGS IS COVERED UNDER THE FBC
 (EXISTING) AS SUCH A DESIGN PROFESSIONAL OR OWNERMUST
 ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION PER
 301.5 FBC (EXISTING)
  
 3)PER 106.1.3 FBC* THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR
 PLANS AND SPECIFICATIONS "NO WHITE OUT, PENCIL OR INK"
  
 4)PROVIDE DETAIL OF TIE IN FOR INFILL OF DOOR AND
 WINDOW.
  
 5)PLEASE CLARIFY, IS WORK ONLY TO THE FRONT FACADE OF
 BUILDING AND WILL THIS PERMIT COVER INSTALLATION OF NEW
 WINDOW. WINDOWS AND DOORS THAT ARE BEING REPLACED OR
 NEW REQUIRE FLORIDA STATEWIDE PRODUCT APPROVALS
 SUBMITTED.
  
 6)PROVIDE DESIGN CRITERIA SHALL INCLUDE CODE CYCLE,
 TYPE OF CONSTRUCTION, ETC.
  