| 2007-05-22 16:29:12 | | | | | | | DENIED | | | | | | 1)PROVIDE WIND DESIGN DATA ON DRAWINGS PER | | | 1603.1.4 FBC | | | | | | 2)WORK ON EXISTING BUILDINGS IS COVERED UNDER THE FBC | | | (EXISTING) AS SUCH A DESIGN PROFESSIONAL OR OWNERMUST | | | ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION PER | | | 301.5 FBC (EXISTING) | | | | | | 3)PER 106.1.3 FBC* THE BUILDING OFFICIAL MAY | | | ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR | | | PLANS AND SPECIFICATIONS "NO WHITE OUT, PENCIL OR INK" | | | | | | 4)PROVIDE DETAIL OF TIE IN FOR INFILL OF DOOR AND | | | WINDOW. | | | | | | 5)PLEASE CLARIFY, IS WORK ONLY TO THE FRONT FACADE OF | | | BUILDING AND WILL THIS PERMIT COVER INSTALLATION OF NEW | | | WINDOW. WINDOWS AND DOORS THAT ARE BEING REPLACED OR | | | NEW REQUIRE FLORIDA STATEWIDE PRODUCT APPROVALS | | | SUBMITTED. | | | | | | 6)PROVIDE DESIGN CRITERIA SHALL INCLUDE CODE CYCLE, | | | TYPE OF CONSTRUCTION, ETC. | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|