| 2007-08-15 10:13:39 | REVISION DENIED; | | | 1. THE SANITARY DRAINAGE SYSTEM IS AN ALTERNATIVE | | | ENGINEERED DESIGN. (SOVENT SYSTEM). WHAT IS THIS WASTE | | | STACK USED FOR IN THE BUILDING? IN WHAT LOCATION IS THE | | | AERATOR AND DE-AERATOR? MORE INFORMATION REQUIRED. | | | 2. A MECHANICAL VENT IS NOT PERMITED IN SOLVENT | | | SYSTEMS, AND CAN ONLY BE USED IN THE TOP 4 BRANCH | | | INTERVALS OF A BUILDING BRANCH. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|