| 2007-08-10 11:57:52 | | | | | | | REVISION DENIED/INCOMPLETE INFORMATION | | | | | | 1} SUBMIT THE MANUFACTURERS SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE STEAM GENERATOR BEING | | | ADDED. | | | | | | 2} GIVEN THE FACT THE STEAM GENERATOR IS BEING | | | INSTALLED IN A CLOTHES CLOSET,PLEASE INDICATE | | | COMPLIANCE WITH 422.17, PROTECTION OF COMBUSTIBLE | | | MATERIAL | | | EACH ELECTRICALLY HEATED APPLIANCE THAT IS INTENDED BY | | | SIZE, WEIGHT, AND SERVICE TO BE LOCATED IN A FIXED | | | POSITION SHALL BE PLACED SO AS TO PROVIDE AMPLE | | | PROTECTION BETWEEN THE APPLIANCE AND ADJACENT | | | COMBUSTIBLE MATERIAL. ARCITECTURAL, MECHANICAL AND | | | PLUMBING REVISIONS MAY BE REQUIRED PENDING REVIEW OF | | | THE SPECIFICATIONS, IF SO THEY MUST ALL BE SUBMITTED AT | | | THE SAME TIME, IN THE SAME PACKAGE, FOR REVIEW BY THOSE | | | DISCIPLINES. | | | | | | 3} INDICATE THE LOCATION OF THE UNIT THE STEAM | | | GENERATOR IS SERVING. | | | | | | 4} ADJUST THE VALUE OF THE PERMITTO INCLUDE LABOR AND | | | MATERIAL FOR ALL THE EQUIPMENT AND LIGHTING, INCLUDING | | | THE LIGHTING CONTROL PANELS, AT THE PERMIT CLERK?S | | | DESK, AND PAY THE DIFFERENCE IN FEES PRIOR TO | | | RESUBMITTING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | |
|