| 2007-08-16 13:42:37 | ADDITION BUILDING REVIEW SECOND CHECKLIST: |
| | REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC |
| | 2004. |
| | |
| | 1- PROVIDE COPY OF IMPACT FEES PAID RECEIPTAS |
| | REQUESTED ON PREVIOUS CHECKLIST: |
| | |
| | 2- PLANS NEED TO SPECIFY ALL DESIGN LOADS, INCLUDING |
| | THE ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2004 |
| | FLORIDA RESIDENTIAL CODE AND AS REQUESTED ON PREVIOUS |
| | CHECKLIST. |
| | |
| | 3- SPECIFY TYPE OF CONSTRUCTION AS REQUIRED BY SEC. |
| | 602.1 FBC 2004 AND SEC. 106.3.5.4 OF CITY AMENDMENTS TO |
| | FBC 2004. THIS ITEM WAS ALSO REQUESTED ON PREVIOUS |
| | CHECKLIST. |
| | |
| | 4- STORM SHUTTERS: |
| | A) INSTALLATION SCHEDULE SUBMITTED: |
| | (1) PROVIDE COMPLETE AND CORRECTINSTALLATION |
| | SCHEDULE. |
| | (2)REVISE PRODUCT APPROVAL NUMBERS ON TOP OF FORM. |
| | SEE SUBMITTED PRODUCT APPROVAL FOR CORRECT NUMBERS.. |
| | (3) REVISE DESIGN PRESSURES. SEE ARCHITECTURAL PLANS |
| | FOR CALCULATED DESIGN PRESSURES. |
| | (4) REVISE INFORMATION GIVEN ON SHUTTER MOUNTING |
| | COLUMN (COLUMN 4). LOOK AT SHUTTERS DRAWINGS AND |
| | SPECIFY TYPE OF MOUNTING. EG: WALL MOUNTED, BUILT OUT |
| | MOUNT, ETC.SPECIFIC MOUNTING CONDITION IS REQUIRED |
| | SINCE THERE ARE MANY DIFFERENT MOUNTING CONDITIONS AND |
| | TO VERIFY COMPLIANCE WITH PROPOSED INSTALLATION. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | (5) WHAT'S THE SHUTTER GLASS SEPARATION.SEE |
| | SHUTTERS DRAWINGS FOR REQUIRED SEPARATION. |
| | (6) SPECIFY ANCHOR SPACING. |
| | |
| | B) CIRCLE ON SHUTTERSDRAWINGS SPECIFIC MOUNTING |
| | CONDITIONS AND ANCHOR TYPE AND SPACING TO BE USED. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | C) PROVIDE LEGIBLE DRAWINGS. DRAWING SUBMITTED ARE |
| | NOT LEGIBLE. |
| | |
| | 5- TRUSS PACKAGE: |
| | A) COMPLETE PACKAGE NEEDS TO HAVE ALL THE ENGINEER'S |
| | INFORMATION AND ALL DRAWINGS TO BE SIGNED AND SEALED AS |
| | REQUIRED BY SEC. 61G15-23.002 AND CHAPTER 471 FLORIDA |
| | STATUTE. |
| | NOTE: COPY OF SIGNATURE IS NOT ALLOWED. |
| | |
| | B) COMPLETE TRUSS PACKAGE NEED TO BE REVIEWED AND |
| | APPROVED BY THE ARCHITECT OF RECORD. NOT SIGNED AND |
| | SEALED BY HIM. |
| | NOTE: ARCHITECT CAN'T SIGN AND SEAL THESE DRAWINGS |
| | BECAUSE THEY WERE NOT DONE BY HIM. SEE CHAPTER 481 |
| | FLORIDA STATUTES. |
| | |
| | 6- SHEET 1 OF 4: |
| | A) THIS IS AN ADDITION, NOT ALTERATION TYPE 2.SEE |
| | CHAPTER 9 OF EXISTING FBC 2004 AND REVISE AS REQUIRED. |
| | |
| | |
| | B) TOTAL ROOF DEAD LOAD LINE SHOWS 30PSF, WHILE DEAD |
| | LOAD LINE SHOWS 25PSF. REVISE AND COORDINATE AS |
| | REQUIRED.ALSO SEEITEM#2ABOVE. |
| | |
| | 7- REVISE GABLE END WALL SECTION. |
| | A) ROOF SHEATHING NAIL SPACING NEEDS TO BE REVISED |
| | FOR ROOF ZONE 3. SEE SEC. R803.2.3.1 OF 2004 FLORIDA |
| | RESIDENTIAL CODE AND REVISE AS REQUIRED. |
| | |
| | B) USP CONNECTORSPECIFIED DOESN'T MATCH CONNECTOR |
| | SPECIFIED ON ROOF FRAMING PLAN AND TRUSS ANCHOR |
| | SCHEDULE. REVISE AS REQUIRED. |
| | |
| | 8- REVISE ROOF SHEATHING NAIL SPACING SPECIFIED ON |
| | TYPICAL WALL SECTION.SEE SEC. R803.2.3.1 OF 2004 |
| | FLORIDA RESIDENTIAL CODE FOR NAIL SPACING AT ROOF ZONE |
| | #3 AND REVISE AS REQUIRED. |
| | |
| | 9- TYPICAL WALL SECTION TITLE CALLS FOR 1'-6" O.H. |
| | WHILE TYP. WALL SECTION DRAWINGS SHOW 24" OVERHANG. |
| | REVISE AS REQUIRED TO MATCH. |
| | |
| | 10- CLARIFY WHY ARCHITECT REVIEWED AND APPROVED PRECAST |
| | LINTEL PRODUCT APPROVAL FOR 4", 6 AND 12" PRECAST |
| | LINTELS IF THERE ARE NOT LINTELS THIS SIZE?. SEE |
| | PLANS. |
| | |
| | 11- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |