| 2007-05-07 07:53:43 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} LOCATE THE NEW WATER HEATER AND DISCONNECTON THE |
| | PLAN SO THAT COMPLIANCE WITH 110.26 AND 240.24 CAN BE |
| | DETERMINED. |
| | |
| | 2} THE 2 #4 FEEDERS TO THE WATER HEATER DISCONNECTON |
| | THE RISER DO NOT CORRELATE WITH THE #8CONDUCTORS IN |
| | THE PANEL SCHEDULE, AND A #6 ON A NOTE ON THE PLAN. |
| | CORRELATE SAME.REMOVE ALL NOTES AND CALCULATIONS NOT |
| | PERTINENT FOR RECORD KEEPING FROM THE PLAN FOR |
| | CLARITY. |
| | |
| | 3} THE FEEDER FOR THE WATER HEATER MUST GROUNDED PER |
| | 250.110 SIZED PER 250.122. |
| | |
| | 4} THE CIRCUIT NUMBERS ON THE PANEL SCHEDULE ARE |
| | INCORRECT AND ARE DUPLICATED. SEE 408.4 2005 NEC |
| | REGARDING"SPECIFIC PURPOSE OR USE". |
| | |
| | 5} THE FACT THAT THE 60 AMP DISCONNECT IS SHOWN "DOUBLE |
| | LUGGED" FROM THE METER, REQUIRES THAT IT BE SERVICE |
| | RATED PER 225.36. |
| | |
| | 6} 225.34(A) GENERAL THE TWO TO SIX DISCONNECTS AS |
| | PERMITTED IN 225.33 SHALL BE GROUPED. EACH DISCONNECT |
| | SHALL BE MARKED TO INDICATE THE LOAD SERVED. ALSO SEE |
| | 230.72(A) |
| | |
| | 7} THE WATER HEATER IS LISTEDIN THE PANEL SCHEDULE ON |
| | A 40 AMP BREAKER, BUT INDICATED AS HAVING A SEPARATE |
| | DISCONNECT ON THE RISER, CORRELATE SAME. |
| | |
| | 8} THE ADDITION TO THE BEDROOMS DO NOT COMPLY WITH |
| | 210.52(A)(1) & (2) FOR RECEPTACLE SPACING. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW. |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |