| Date |
Text |
| 2007-07-02 10:19:07 | DENIED 2ND TIME |
| | REFERENCE: FBC-2004 SECTION 424.2 AND 4101 SWIMMING |
| | POOLS. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| | MADE ON PREVIOUS REVIEWS. |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| | PREVIOUS REVIEW NOTES. |
| | |
| | A **NO** IS IF THE COMMENT WAS NOT FULLY ADDRESSED |
| | AND/OR FURTHER EXPLANATION OR CHANGES IN PLANS OR |
| | DOCUMENTS ARE STILL NEEDED. THIS REVIEWER WILL TRY TO |
| | BETTER EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| | |
| | AN **OK** WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| | |
| | A **NO/OK** MEANS PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| | COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| | |
| | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| | |
| | 1) **OK** |
| | |
| | 2) **NO** FBC-2004 SEC. 424.2.6.6.5, OR |
| | FBCR-2004 SEC. R4101.6.6.5 WHERE |
| | PROVIDED, THE VACUUM OR PRESSURE CLEANER |
| | FITTING SHALL BE LOCATED AT LEAST 6" AND |
| | NOT GREATER THAN 12" BELOW THE MINIMUM |
| | OPERATING WATER LEVEL OR AS AN |
| | ATTACHMENT TO THE SKIMMER. (PLEASE SUBMIT ADETAIL OF |
| | THE SKIMMER ON THE RESUBMITTAL) |
| | NOTE: A DETAIL OF THE SKIMMER WAS ASKED FOR ON THE |
| | PREVIOUS PLUMBING PLAN REVIEW AND ONE WAS NOT PROVIDED |
| | ON THE RESUBMITTAL. A DETAIL IS REQUIRED, PLEASE SUBMIT |
| | ONE ON THE NEXT RESUBMITTAL. |
| | |
| | 3) **NO** FBC-2004 SEC. 424.2.14.1, OR |
| | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. (MANUFACTURE |
| | SHEETS REQUIRED, PLEASE SUBMIT) |
| | NOTE: THE SUBMITTED MANUFACTURER SHEET DOES NOT |
| | INDICATE THAT IT IS LISTED BY A NATIONALLY RECOGNIZED |
| | TESTING LABORATORY (NRTL). THE SUBMITTED SHEET DOES NOT |
| | CLEARLY INDICATE THE POOL HEATER MAKE. PLEASE COMPLY ON |
| | THE RESUBMITTAL. |
| | |
| | 4) **NO** FBC-2004 SEC. 424.2.14.2, OR |
| | FBCR-2004 SEC. R4101.14.2 WATER |
| | RETENTION, PROVIDE A POSITIVE MEANS OF |
| | RETAINING WATER IN THE HEATER WHEN PUMP |
| | IS SHUT OFF.(MANUFACTURE SHEETS |
| | REQUIRED, PLEASE SUBMIT) |
| | NOTE: THE SUBMITTED MANUFACTURER SHEET DOES NOT CLEARLY |
| | INDICATE THE MAKE OF THE POOL HEATER. PLEASE COMPLY ON |
| | THE RESUBMITTAL. |
| | |
| | ******NEW ITEM****** |
| | |
| | 5) THE ORIGINAL PERMIT APPLICATION IS MISSING FROM THE |
| | RESUBMITTAL, ONE IS REQUIRED TO PROCESS PERMIT. PLEASE |
| | PROVIDE ONE FOR THE NEXT RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |