Plan Review Notes
Plan Review Notes For Permit 07050092
Permit Number 07050092
Review Stop P
Sequence Number 1
Notes
Date Text
2007-05-09 13:21:44DENIED
 REFERENCE: FBC-2004 SECTION 424.2 AND 4101 SWIMMING
 POOLS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1) FBC-2004 SEC. 424.6.6 OR FBC-2004
 RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. PLEASE
 SUBMIT AN ENGINEERED TABLE FOR "VENT
 PIPE MAXIMUM LENGTH" INDICATING PUMP
 SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH
 OF THE 1-1/2" PVC VENT PIPE, FROM
 WHERE IT STARTS TO WHERE IT ENDS UP,
 COMPLYING WITH THE THREE SECOND RELEASE.
 NOTE: THE SUBMITTED 1-1/2" ATMOSPHREIC VENT LENGTH
 TABLE DOES NOT REFLECT THE PROPOSED 2-1/2 HP SPA PUMP.
 PLEASE REVISE THE VENT TABLE TO REFLECT THE 2-1/2 HP
 PUMP ON THE RESUBMITTAL.
  
 2) FBC-2004 SEC. 424.2.6.6.5, OR
 FBCR-2004 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPERATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER. (PLEASE SUBMIT ADETAIL OF
 THE SKIMMER ON THE RESUBMITTAL)
  
 3) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 4) FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 END OF COMMENTS:
  