| 2007-05-09 13:21:44 | DENIED |
| | REFERENCE: FBC-2004 SECTION 424.2 AND 4101 SWIMMING |
| | POOLS. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1) FBC-2004 SEC. 424.6.6 OR FBC-2004 |
| | RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT |
| | PROTECTION FOR SUCTION INLETS. PLEASE |
| | SUBMIT AN ENGINEERED TABLE FOR "VENT |
| | PIPE MAXIMUM LENGTH" INDICATING PUMP |
| | SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH |
| | OF THE 1-1/2" PVC VENT PIPE, FROM |
| | WHERE IT STARTS TO WHERE IT ENDS UP, |
| | COMPLYING WITH THE THREE SECOND RELEASE. |
| | NOTE: THE SUBMITTED 1-1/2" ATMOSPHREIC VENT LENGTH |
| | TABLE DOES NOT REFLECT THE PROPOSED 2-1/2 HP SPA PUMP. |
| | PLEASE REVISE THE VENT TABLE TO REFLECT THE 2-1/2 HP |
| | PUMP ON THE RESUBMITTAL. |
| | |
| | 2) FBC-2004 SEC. 424.2.6.6.5, OR |
| | FBCR-2004 SEC. R4101.6.6.5 WHERE |
| | PROVIDED, THE VACUUM OR PRESSURE CLEANER |
| | FITTING SHALL BE LOCATED AT LEAST 6" AND |
| | NOT GREATER THAN 12" BELOW THE MINIMUM |
| | OPERATING WATER LEVEL OR AS AN |
| | ATTACHMENT TO THE SKIMMER. (PLEASE SUBMIT ADETAIL OF |
| | THE SKIMMER ON THE RESUBMITTAL) |
| | |
| | 3) FBC-2004 SEC. 424.2.14.1, OR |
| | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. (MANUFACTURE |
| | SHEETS REQUIRED, PLEASE SUBMIT) |
| | |
| | 4) FBC-2004 SEC. 424.2.14.2, OR |
| | FBCR-2004 SEC. R4101.14.2 WATER |
| | RETENTION, PROVIDE A POSITIVE MEANS OF |
| | RETAINING WATER IN THE HEATER WHEN PUMP |
| | IS SHUT OFF.(MANUFACTURE SHEETS |
| | REQUIRED, PLEASE SUBMIT) |
| | |
| | END OF COMMENTS: |
| | |