2008-02-25 15:14:49PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** REVISION TO MECHANICAL PLAN **
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 2-15-08 NOTE #1 AS THE
 REVISION SHOWS TWO A/C SYSTEMS TOTALING 6.5 TONS IS NOW
 BEING INSTALLED THE COOLING LOAD CALCULATIONS WILL ALSO
 NEED TO BE REVISED, SEE 2004 FBC 13-103.1.2. COOLING
 LOAD CALCULATIONS ON FILE ARE CALLING FOR 47,052 TOTAL
 COOLING BTU'S, REVISED MECHANICAL PLAN IS CALLING FOR A
 TOTAL OF 76,700 COOLING BTU'S.THE PLANS CAN ONLY CALL
 FOR 15% MORE THAN THE COOLING LOAD CALCULATIONS, SEE
 2004 FBC 13-607.1.ABC.1.1.
  