| 2008-02-15 10:51:42 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | ** MECHANICAL REVISION ** | | | *** DENIED *** | | | 1) AS THE REVISION SHOWS TWO A/C SYSTEMS TOTALING 6.5 | | | TONS IS NOW BEING INSTALLED THE COOLING LOAD | | | CALCULATIONS AND ENERGY CALCULATIONS WILL NEED TO BE | | | REVISED, SEE 2004 FBC 13-103.1.2. | | | | | | 2) WHEN SUBMITTING REVISED ENERGY CALCULATIONS PLEASE | | | HAVE THEM SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC | | | 13-600.3.ABC.2. | | | | | | 3) PLEASE PROVIDE COMBUSTION AIR AND MAKE UP AIR | | | CALCULATION AND/OR COMBUSTION AND MAKE UP AIR FOR THE | | | GAS CLOTHES DRYER IN THE UTILITY ROOM AS IT APPEARS TO | | | BE A CONFINED SPACE, SEE 2004 FBC/R G2407.1 AND | | | G2407.4. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|