| 2007-07-27 18:43:43 | BUILDING REVIEW 3RD CHECKLIST: |
| | 1- DRAWINGSA2 AND A3 ARE NOT SIGNED, SEALED AND DATED |
| | BY THE ARCHITECT AS REQUIRED BY CHAPTER 481 FLORIDA |
| | STATUTE. |
| | |
| | 2- ARCHITECT NEEDS TO REVIEW TABLE ONPAGE 45 OF ASCE |
| | 7-02 OR REVISED TABLE 1609.6.2.1(2) OF FBC 2004 TO SEE |
| | THE DESIGN PRESSURES AT CORNER AREAS.PRODUCT |
| | APPROVAL NOA 07-0301.01 FOR METAL ROOF PANELS SUBMITTED |
| | STILL DOESN'T MEET THE DESIGN PRESSURES AT CORNER |
| | AREAS. THEREFORE IT CAN'T BE USED IN THIS AREA. NEED TO |
| | PROVIDE PRODUCT APPROVAL THAT MEETS THE DESIGN |
| | PRESSURES FOR ALL ZONES. |
| | |
| | 3- NOTICE OF COMMENCEMENT SUBMITTED WAS RECORDED ON |
| | 03/29/2007.NOTICE OF COMMENCEMENT IS EXPIRED AFTER |
| | 90 DAYS IF WORK IS NOT STARTED. SEE SEC. 713.13 FLORIDA |
| | STATUTE. NEED TO PROVIDE RE-RECORDED NOTICE OF |
| | COMMENCEMENT. |
| | |
| | 4- PROVIDE PRODUCT APPROVALSAS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A)ALL USP STRUCTURAL CONNECTORSSPECIFIED ON |
| | PLANS.SEE TRUSS ANCHOR SCHEDULE, COLUMN CONNECTORS |
| | AT TOP AND BOTTOM,ETC. |
| | |
| | B) EXTERIOR SWING DOORS AS SHOWN ON PLANS.ONLY ONE |
| | PRODUCT APPROVAL WAS SUBMITTED AND IT WAS ASSUMED THAT |
| | IT WAS FOR THE GARAGE SIDE DOOR SINCE IS THE ONLY ONE |
| | THAT MATCHES THE SIZE SPECIFIEDON PLANS. IT WAS |
| | REQUESTED ON PREVIOUS CHECKLIST TO IDENTIFY IF PRODUCT |
| | APPROVAL WAS FORENTRY DOOR, REAR DOOR OR SIDE GARAGE |
| | DOOR. |
| | NEED TO PROVIDE PRODUCT APPROVAL FOR ENTRY DOOR AND |
| | REAR DOOR. SEE PLANS FOR SPECIFIED SIZE. |
| | |
| | 5- REMAINDER: ARCHITECT TO REVIEW AND APPROVE IN |
| | WRITING ALL PRODUCT APPROVALS PRIOR TO SUBMITTAL TO |
| | THIS OFFICE. SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 6- STRUCTURAL BUCK DETAILS TO MATCH INFORMATION GIVEN |
| | ON FASTENER SCHEDULE ON SHEET A3. |
| | |
| | 7- SHEET A2: THERE ARE TWO DIFFERENT TYPES OF |
| | CONSTRUCTION TYPES SPECIFIED ON WIND DESIGN |
| | INFORMATION. REVISE AS REQUIRED AND PROVIDE CORRECT |
| | INFORMATION. SEE SEC. 602.1 FBC 2004.ALSO, BE |
| | SPECIFIC IF CONSTRUCTION TYPE IS A OR B. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |