Plan Review Notes
Plan Review Notes For Permit 07050091
Permit Number 07050091
Review Stop E
Sequence Number 2
Notes
Date Text
2007-07-09 08:47:13 
  
  
  
 PROVISO
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ROUGH
 INSPECTION.
  
 NOTE: SEE 13-606.1.ABC.1.2.3 FBC FOR REQUIREMENTS FOR
 RECESSED LIGHTING FIXTURES INSTALLED IN CEILINGS THAT
 ABUT AN ATTIC SPACE. ALSO SEE THE DEFINITION OF "SMOKE
 DETECTORS" 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS
 OR ALARMS, TO AVOID CONFUSION IN THE FIELD.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} THE RISER DIAGRAM INDICATES A METER/MAIN
 COMBINATION, AND AT THE SERVICE LOCATION ON THE
 DRAWING, A DISCONNECT IS INDICATED SEPARATELY. PLEASE
 CLARIFY.
  
 2}A RECEPTACLE MUST BE ADDED TO THE MASTER BATH
 COUNTER TO COMPLY WITH 210.53(D).
  
 3} THE DINING ROOM RECEPTACLES NEED TO BE CIRCUITED ON
 A 20 AMP CIRCUIT PER 210.52 (B)(1), AND SHALL HAVE "NO
 OTHER OUTLETS", SEE 210.52(B)(2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved