| Plan Review Notes For Permit 07050091 |
| Permit Number |
07050091 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-09 08:47:13 | | | | | | | | | | | | | PROVISO | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ROUGH | | | INSPECTION. | | | | | | NOTE: SEE 13-606.1.ABC.1.2.3 FBC FOR REQUIREMENTS FOR | | | RECESSED LIGHTING FIXTURES INSTALLED IN CEILINGS THAT | | | ABUT AN ATTIC SPACE. ALSO SEE THE DEFINITION OF "SMOKE | | | DETECTORS" 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS | | | OR ALARMS, TO AVOID CONFUSION IN THE FIELD. | | | | | | 1} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. | | | | | | 2} THE RISER DIAGRAM INDICATES A METER/MAIN | | | COMBINATION, AND AT THE SERVICE LOCATION ON THE | | | DRAWING, A DISCONNECT IS INDICATED SEPARATELY. PLEASE | | | CLARIFY. | | | | | | 2}A RECEPTACLE MUST BE ADDED TO THE MASTER BATH | | | COUNTER TO COMPLY WITH 210.53(D). | | | | | | 3} THE DINING ROOM RECEPTACLES NEED TO BE CIRCUITED ON | | | A 20 AMP CIRCUIT PER 210.52 (B)(1), AND SHALL HAVE "NO | | | OTHER OUTLETS", SEE 210.52(B)(2). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|