Plan Review Notes
Plan Review Notes For Permit 07050091
Permit Number 07050091
Review Stop B
Sequence Number 2
Notes
Date Text
2007-07-17 14:04:02BUILDING REVIEW SECOND CHECKLIST:
 1-PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 2- PERMIT VALUATION WAS UPDATED USING THE REVISED
 VALUATION SHOWN ON THE PERMIT APPLICATION.OWES
 $1026.14 FOR PERMIT VALUATION AND RADON FEES.
  
 3- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) METAL ROOF PANEL.NOA 06-0317.05 SUBMITTED IS
 GOOD FOR UP TO -45PSF ONLY.ACCORDING TO SYSTEM
 LIMITATION #1 ON PAGE 4 NAIL ENHANCING IS NOT ALLOWED.
 NEED TO PROVIDE PRODUCT APPROVAL THAT MEETS THE DESIGN
 PRESSURES AT PERIMETER AND CORNER AREAS.
 ***CLARIFY WHY ARCHITECT APPROVED THIS PRODUCT IF IT
 DOESN'T MEET THE DESIGN PRESSURES.
  
 B) GARAGE DOOR AS SHOWN ON PLANS.NOA03-0430.04
 SUBMITTED IS FOR 9'-0" WIDE DOORS. PLANS CALL FOR
 10'-0" WIDE DOORS.
 *** CLARIFY WHY ARCHITECT APPROVED THIS PRODUCT IF IT
 DOESN'T WORK FOR THE SIZE SPECIFIED ON PLANS. ALSO,
 PROVIDE 2 COPIES WITH LEGIBLE DRAWINGS.
  
 C) ALL USP STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS.
  
 PROVIDE PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING
 THE CONNECTORS ONLY. NOT NEED TO SUBMIT COMPLETE
 REPORT.
  
 D) EXTERIOR SWING DOORS. CLEARLY IDENTIFY PRODUCT
 APPROVAL FOR ENTRY DOOR,REAR DOOR AND GARAGE SIDE
 DOOR.
 ALSO, THERE IS ONLYONE COPY SUBMITTED FOR JELD-WEN
 DOOR.
 ALSO, CHECKDOOR SIZES SPECIFIED ON PLANS TO MAKE SURE
 CORRECT PRODUCT APPROVAL IS SUBMITTED.
  
 E) GLASS BLOCK.
  
 F) PROVIDE ONLY THE PRODUCT APPROVALS THAT APPLY TO
 THIS PROJECT. THERE ARE SOME PRODUCT APPROVALS FOR
 FIXED WINDOWS THAT DON'T APPLY TO THIS JOB.
 ALSO, REVISE DESIGN PRESSURES FOR COMPONENTS AND
 CLADDING SCHEDULE. IT DOESN'T MATCH PLANS SUBMITTED.
 NOTE: THIS SCHEDULE IS NOT REQUIRED. REQUIRED
 INFORMATIONIS ON SHOWN ON PLANS.THIS SCHEDULE JUST
 CONFUSES THE INFORMATION WHEN IT DOESN'T MATCH PLANS.
  
 4- GLASS BLOCK PRODUCT APPROVAL TO BE REVIEWED AND
 APPROVED IN WRITING BY ARCHITECT AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 5- STRUCTURALBUCK DETAILS FOR DOORS AND WINDOWS TO
 MATCH INFORMATION GIVEN ON FASTENER SCHEDULE SHOWN ON
 SHEET A3.
  
 6- REVISE INFORMATION GIVEN ON FASTENER SCHEDULE ON
 SHEET A3.NAIL SIZE SPECIFIED FOR WIRE LATH
 INSTALLATION ON SOFFIT IS INCORRECT.SEE ASTMC-926
 AND ASTM C1063FOR CORRECT SIZE AND SPACING TO BE
 SPECIFIED. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 7- ENERGY CALCULATIONS:
 A) ARCHITECT TO PROVIDE HIS NAME AS REQUIRED BY
 CHAPTER 481 FLORIDA STATUTE AND SEC. 61G1-16.004
 FLORIDA ADMINISTRATIVE CODE.
  
 B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM
 ALSO.
  
 8- TYPE OF CONSTRUCTION SPECIFIED BY THE ARCHITECT IS
 INCORRECT.THERE IS NOT TYPE VI ON FBC 2004. REVISE
 AS REQUIRED. SEE SEC. 602.1 FBC 2004.
  
 9- AREA CALCULATIONS FOR NEW PORCH IS INCORRECT. REVISE
 AS REQUIRED.ALSO, REVISE TOTAL AREA AS REQUIRED.
  
 10- SHEET A4:
 A) SPECIFYCOLUMN TOP CONNECTORS AT CORNER AREAS OF
 NEW PORCH. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 11- ROOF SHEATHING NOTE AND INFORMATION GIVEN ON
 FASTENER SCHEDULE SHEET A3 DON'T MATCH REVISE AS
 REQUIRED.ALSO, CLARIFY NOTE REGARDING ZONE 3 (GABLE
 END). ROOF ZONE 3 IS NOT ONLY FOR GABLE ENDS. REVISE AS
 REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712