2007-05-17 16:07:03DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET A3 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. THE NEW LAUNDRY TRAY IN THE
 UTILITY ROOM INDICATED ON SHEETS A2 AND A3 IS MISSING
 FROM THE THE SANITARY RISER DIAGRAM AS WELL AS THE
 RELOCATION OF THE WASHING MACHINE. PER FBC-2004 CHAPTER
 1, SECTION 106.3.5.4 (9) PLUMBING, PLEASE INDICATE
 THOSE CHANGES ON THE RESUBMITTAL.
 NOTE: THE FOLLOWING IS REQUIRED FOR THE WASHING
 MACHINE.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
 NOTE: PLEASE INDICATE THE STANDPIPE ON THE RESUBMITTED
 DRAWINGS.
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE
 THREE INCH (3").
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE
 LOCATED AT FOUR FEET ABOVE FINNISH FLOOR (4'A.F.F.).
  
 2. SHEET A3 NEW KITCHEN SINK SANITARY ISOMETRIC RISER
 DIAGRAM PLEASE INDICATE THE DISHWASHER DISCHARGE INTO A
 WYE-BRANCH FITTING ON THE TAILPIECE OF THE KITCHEN SINK
 OR THE DISHWASHER CONNECTION OF A FOOD WASTE GRINDER
 PER FBC-2004 PLUMBING, SECTION 802.1.6 ON THE
 RESUBMITTAL.
  
 3. SHEET A3 WATER HEATER PIPING DIAGRAM: PLEASE
 INDICATE A MEANS OF CONTROLLING INCREASED PRESSURE
 CAUSED BY THERMAL EXPANSION AS REQUIRED IN ACCORDANCE
 WITH FBC-2004 PLUMBING, SECTIONS 607.3.1 AND 607.3.2 ON
 THE RESUBMITTAL.
  
 4. SHEET A3 FOUNDATION PLAN THE RANGE AND KITCHEN SINK
 WITH DISHWASHER AND DISPOSAL ARE INDICATED IN THE WRONG
 LOCATION PER SHEET A2 ARCHITECTURAL FLOOR PLAN. PLEASE
 CORRECT AND CORRELATE THIS ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721