| Plan Review Notes For Permit 07050091 |
| Permit Number |
07050091 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-15 13:32:42 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 2) AS THEIR IS NO DOOR SCHEDULE PLEASE NOTE ON PLANS | | | DOOR TO THE AHU CLOSET NEEDS TO BE LOUVERED FOR RETURN | | | AIR. | | | | | | 3) THE RETURN AIR TRANSFER DUCT TO BEDROOM #3 NEEDS TO | | | BE SIZED. | | | | | | 4) PROVIDE FOR RETURN AIR TO THE LIBRARY AND MASTER | | | SUITE. | | | | | | INFORMATIONAL: BALANCED RETURN AIR MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS | | | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR | | | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO | | | ACHIEVE PROPER RETURN AIR BALANCE. | | | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET | | | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR | | | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY | | | ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE | | | SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|