Plan Review Notes
Plan Review Notes For Permit 07050091
Permit Number 07050091
Review Stop B
Sequence Number 1
Notes
Date Text
2007-06-19 16:58:58BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 2- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY(2300 N. JOG RD (561)233-5115)TO PAY IMPACT
 FEES.BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT.
  
 3- DECLARED VALUATION IN PERMIT APPLICATION IS TOO LOW.
 SEC. 108.3 CITY AMENDMENTS TO FBC 2004.PLEASEUPDATE
 VALUATION AND INCLUDE ALSODEMOLITION AND PROFESSIONAL
 ARCHITECT/ENGINEER SERVICES.
  
  
 4-CLARIFY WHY DEMOLITION PLAN CALLS FOR "CUT EXISTING
 TIE BEAM" AT OPENING AREAS.HOW IS THE TIE BEAM
 REINFORCED IF IT'S CUT DOWN?. SEC. 106.1.2 CITY
 AMENDMENTS STO FBC 2004.
  
 5- SPECIFY ATTIC ACCESS SIZE. SEC. R807 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) 18" DIAMETER SUNTUBE SKYLIGHTS.
  
 B) SLIDING GLASS DOORS. NOA 05-0112.02 SUBMITTED WAS
 SUPERSEDED ACCORDING TO DADE COUNTY PRODUCT APPROVAL
 WEBSITE. SEE ATTACHED COPY.PROVIDE COPIES OF CURRENT
 NOA.
  
 C) METAL ROOF PANEL. NOA 06-0317.05 SUBMITTED IS
 GOOD FOR UP TO -45PSF MAXIMUM ALLOWABLE UPLIFT
 PRESSURE.UPLIFT PRESSURES CAN'T BE UPGRADED. SEE
 SYSTEM LIMITATIONS ON PAGE 4 OF NOA SUBMITTED.NEED TO
 PROVIDE PRODUCT APPROVAL THAT WILL RESIST THE UPLIFT
 LOADS AT PERIMETER AND CORNER AREAS AS INDICATED ON
 REVISED TABLE 1609.6.2.1(2) OF FBC 2004. (10PSF
 MINIMUM TRIBUTARY AREA).
  
 D) GARAGE DOOR AS SHOWN ON PLANS.
  
 E) ALL USP CONNECTORS SPECIFIED ON PLANS.
  
 F) ALL EXTERIOR SWING DOORS AS SHOWN ON
 PLANS/ELEVATIONS.AND, CLEARLY IDENTIFY WHICH ONE IS
 ENTRY DOOR, GARAGE SIDE DOOR, ETC.
  
 G) GLASS BLOCK.
  
 H) PRECAST LINTELS.
  
 ***NOTE:PROVIDE ONLY PRODUCT APPROVALS THAT APPLY TO
 THIS PROJECT. THERE IS A PRODUCT APRPOVAL SUBMITTED FOR
 CASEMENT WINDOWS. PLANS DON'T SHOW ANY CASEMENT
 WINDOWS.
  
 7- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 8-STRUCTURAL BUCK DETAILS FOR DOORS AND WINDOWS TO
 MATCH INFORMATION GIVEN ON FASTENER SCHEDULE. ALSO, SEE
 WINDOWS AND DOORS PRODUCT APPROVALS TO VERIFY MINIMUM
 BUCK SIZE REQUIRED AND COORDINATE DETAILS/SPECS
 ACCORDINGLY.
  
 9- ENERGY CALCULATIONS:
 A) OWNER/AGENT TO SIGN AND DATE AT BOTTOM OF FORM.
  
 B) ARCHITECT TO PROVIDE HIS NAME AND LICENSE NUMBER
 ON ALL SHEETS THAT HE'S SIGNING AND SEALING AS REQUIRED
 BY CHAPTER 481 FLORIDA STATUTE AND SEC. 61G1-16.004 OF
 FLORIDA ADMINISTRATIVECODE.
  
 10- SHEET A2:
 A) FLOOR PLAN CALLS FOR "HOR SLDR"WINDOWS BY
 LIBRARY AREA, WHILE LEFT SIDE ELEVATION SHOWS FIXED
 WINDOWS. CLARIFY/REVISE AS REQUIRED.
  
 B) SPECIFY TYPE OF CONSTRUCTION AS REQUIRED BYSEC.
 602.1 FBC 2004."CONCBLK"CONSTRUCTION IS NOT A
 COMPLETE DESCRIPTION.
  
 11- SHEET A4:
 A) SPECIFY CONNECTORS AT THE ENDS AND CORNERS OF
 (3)2X12 BEAMS AT NEW ENTRY PORCH. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 B) MINIMUM ROOF SHEATHING TYPE OF NAIL IS 8D RING
 SHANK NAILS AS REQUIRED BYSEC. R803.2.3.1 OF 2004
 FLORIDA RESIDENTIAL CODE. REVISE ROOF SHEATHING NOTE AS
 REQUIRED.
  
 C) WALL SECTION G/4:SPECIFY 12" MIN. FOOTING DEPTH
 BELOW GRADE AS REQUIRED BY SEC. R403.1.4OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 ***NOTE:
 PLEASE DON'T STAPLE PRODUCT APPROVALS TO PLANS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712