Plan Review Notes
Plan Review Notes For Permit 07050089
Permit Number 07050089
Review Stop FIRE
Sequence Number 5
Notes
Date Text
2008-09-09 11:20:33*****DENIED*****
  
 WHY WERE AS-BUILT PLANS SUBMITTED AFTER THIS PERMIT HAS
 BEEN CLOSED? PLANS TURNED OVER TO LUIS MARTINEZ.
 A MEETING WAS CONDUCTED ON MONDAY SEPTEMBER 15TH, 2008
 AT 1000 HRS WITH REPS FROM MORGAN ELECTRIC, MOSS &
 ASSOCIATES, AND (CSD'S ELECTRICAL PLAN EXAMINER DEWEY
 PALMER) IN REFERENCE TO THE SUBMITTED AS-BUILTS /
 REVISED PLANS. IT WAS DETERMINED THAT:
  
 1. THE PLANS SHOULD HAVE BEEN SUBMITTED AS REVISIONS
 INSTEAD OF AS-BUILTS.
  
 2. SUBMIT ONLY THE AFFECTED REVISED SHEETS.
  
 3. THE SUBMITTED SHEETS SHALL BE SIGNED AND SEALED AS
 LIKE THOSE OF THE PLAN SET ON FILE WITH THE CITY OF
 WEST PALM BEACH.
  
 4. INDICATE THE REVISION(S) WITH A CLOUD AND
 CORRESPONDING REVISION NUMBER SHOWN IN THE TITLE BLOCK.
  
 5. ALL SUBMITTED PLAN SHEETS SHALL BE DIMENSIONED AND
 DRAWN OF SUFFICIENT CLARITY. PLEASE BE ADVISED THAT IN
 ONE OF THE THREE SUBMITTED SETS, THIS IS NOT THE CASE.
  
  
  
 CAPT. MICHAEL A.WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722