| 2007-06-09 15:48:42 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL ARCHITECTURAL SHEETS. THE STATUS OF THE FIRM |
| | LICENSE NUMBER, (CERTIFICATE OF AUTHROIZATION), IS |
| | LISTED AS DELINQUENT. PLEASE HAVE STATUS UPGRADED PRIOR |
| | TO RESUBMITTING. FAC 61G1-16.004(4) & FS 481.219, |
| | 481.2055. |
| | |
| | 2. SHT A.O INDICATES A NEW DRINKING FOUNTAIN. PLEASE |
| | SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15 |
| | AND ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A) |
| | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | |
| | 3. SHT LS.1 DETAIL 2 KITCHENETTE SINK. SHOW COMPLIANCE |
| | FOR THE FOLLOWING: |
| | A. 11-4.24.3 KNEE CLEARANCE |
| | B. 11-4.24.4 SINK DEPTH |
| | C. 11-4.24.5 CLEAR FLOOR SPACE |
| | D. 11-4.24.7 FAUCETS |
| | |
| | 4. A TURNING AREA IS REQUIRED IN THE KITCHENETTE AREA |
| | PER SECTION 11-4.2.3. |
| | |
| | 5. SHT LS.1 DETAIL 2 CODE REFERENCE IS FBC-2001. THE |
| | CODE ADOPTED IS FBC-2004. PLEASE CORRECT CODE |
| | REFERENCE. |
| | |
| | 6. SUBMIT A SANITARY RISER ISOMETRIC DIAGRAM FOR THE |
| | DRAINAGE WASTE & VENT FOR THE NEW DRINKING FOUNTAIN PER |
| | SECTION 106.3.5.1.3(4)(6)(13). SHOW ALL PIPE SIZES, |
| | TRAPS, VENTS AND POINT OF CONNECTION. |
| | |
| | 7. SUBMIT A WATER RISER ISOMETRIC DIAGRAM FOR THE |
| | DRINKING FOUNTAIN. SHOW ALL PIPE SIZES, VALVES, AND |
| | INDICATE THE LOCATION OF THE REQUIRED RPZV BACKFLOW. |
| | SECTION 106.3.5.1.3(3)(8)(10)(13). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |