| Date |
Text |
| 2007-05-17 10:50:57 | ** UNSAT** |
| | |
| | ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| | BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| | BY THE CITY OF WEST PALM BEACH. |
| | |
| | |
| | 1) NOTE: PLEASE SEE PLANS MUST REFLECT CURRENT CODES IN |
| | EFFECT AND ADOPTED BY THE STATE IN THE SCOPE OF WORK AS |
| | SHOWN. |
| | PLEASE KNOW HOWEVER AT THIS TIME AND AS OF DECEMBER |
| | 8TH, 2006 THE STATE IS UNDER THE 2004 FBC W/2006 |
| | REVISIONS. THESE ARE ONLY REVISIONS TO THE 2004 FBC. |
| | PLEASE ALSO SEE THE PLANS INDICATE * PALM BEACH COUNTY* |
| | LOCAL AMENDMENTS. |
| | SOME OF THESE ARE STATED ON ELECTRICAL HOWEVER SHOULD |
| | ALSO BE ON COVER SHEETS. |
| | WE ARE UNDER THE 2005 NFPA-70. (NEC). |
| | PLEASE ALSO LIST THE FOLLOWING. |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE VERIFY THE LOCATION OF PROJECT AS THE |
| | SITE/LOCATION PLAN INDICATES TWO LOCATIONS. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORK IS TO INCLUDE ALL LABOR AND MATERIALS EVEN IF ANY |
| | EQUIPMENT/MATERIALS ETC ARE OWNER SUPPLIED. |
| | FBC 108.3 |
| | |
| | 4) NOTE: PLEASE SEE 408.4 AS THE PANEL SCHEDULE |
| | SUBMITTED IS NOT COMPLETE AND NEEDS TO CONTAIN |
| | SPECIFICS FOR CIRCUITING TO ROOMS AND AREAS IN WHICH |
| | THEY FEED. |
| | PLEASE ALSO INCLUDE EXISTING CIRCUITING AS THERE ARE |
| | REQUIRED ITEMS MISSING NOT ON PANEL SCHEDULE. *SEE NOTE |
| | FOR LOAD CALCULATIONS. |
| | |
| | 5) NOTE: PLEASE SEE 600.5 FOR MISSING SIGN CIRCUIT. NEW |
| | ORE EXISTING? |
| | 408.4, 220, ETC. |
| | |
| | 6) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES PER |
| | 210.62. NEW OR EXISTING? |
| | PLEASE ALSO SEE 220.43 FOR LOADS. |
| | |
| | 7) NOTE: PLEASE COMPLETE AND COORDINATE LOAD |
| | CALCULATIONS. PLEASE SEE THE CODE SECTIONS REFLECTED |
| | ARE THAT FROM THE PREVIOUS CODE. PLEASE SEE THE |
| | RECEPTACLE LOAD MAY NOT BE USED AS 1VA PER FT, WHEN A |
| | KNOWN RECEPTACLE LOAD IS AVAILABLE. PLEASE SEE THAT THE |
| | PLANS MENTIONS ALL RECEPTACLES ARE EXISTING, HOWEVER |
| | NOT SHOWN, SO PLEASE CORRELATE. |
| | PLEASE SEE OTHER NOTES FOR RECEPTACLES. |
| | PLEASE SEE THAT LOADS SHOWN BELOW PANEL SCHEDULE DO NOT |
| | CORRELATE WITH THAT OF THE LOAD CALCULATIONS ON THE |
| | SAME SHEET. |
| | PLEASE SEE THE 2005 NEC.220. |
| | |
| | 8) NOTE: PLEASE CLARIFY THE BUILDING. AT THIS TIME THIS |
| | SPACE APPEARS TO BE PART OF A LARGER BUILDING AND MAY |
| | NOT MEET THE DEFINITION OF BUILDING. |
| | PLEASE SEE FBC CHAPTER 1313-415.1.ABC.1.1, .1.2 AND |
| | .1.3 FOR POSSIBLE LIGHTING CONTROLS REQUIRED. PLEASE |
| | SEE 13-415.2 AS PERFORMANCE CALCULATIONS ARE REQUIRED |
| | FOR ANY SIZE BUILDING. |
| | PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING LOADS TO |
| | BE SHOWN. (HIGHER OF THE TWO AS SHOWN BASED ON FIXTURES |
| | OR LINEAR FT OF TRACK) FOR 120V SYSTEMS. |
| | |
| | ** PLEASE KNOW AS SOME ITEMS ARE NOT CLEAR AT THIS |
| | TIME, ALL COMMENTS FOR CODE COMPLIANCE AND REVIEW CAN |
| | NOT BE DONE AT THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |