Plan Review Notes
Plan Review Notes For Permit 07050064
Permit Number 07050064
Review Stop E
Sequence Number 5
Notes
Date Text
2007-08-20 10:23:31*** PROVISO ***
 **5TH REVIEW**
  
 1) NOTE: PLEASE REVISE PLANS SHOWING COMPLETE
 CIRCUITING WHICH IS TO COORDINATE WITH THE SUBMITTED
 PANEL SCHEDULE BEFORE FINAL ELECTRICAL INSPECTION.
 408.4
 FBC 106.3.5.1.2
  
 2) NOTE: PLEASE SEE GFI IN MASTER BATH MUST BE WITHIN
 3FT OF THE LAVATORY EDGE PER 210.52D
  
 3) NOTE: PLEASE SEE THE COUNTER SPACE IN KITCHEN NEEDS
 TO MEET 210.52C1
  
 4) NOTE: ADOPTED CODES REDLINED AS 2002 IS SHOWN FOR
 NFPA-72, 70 AND 101
 THE CORRECT DATED CODES ARE AS FOLLOWS.
 2002 NFPA-72
 2005 NFPA-70
 2003 NFPA-101
  
 5) NOTE: PANEL SCHEDULE AND MANY PLACES IN NOTES STILL
 STATE *SMOKE DETECTORS* INSTEAD OF SMOKE ALARMS.
 NFPA-72
  
 ** THE ABOVE NEEDS TO BE REVISED BEFORE FINAL.
 ANY OTHER CHANGES NEED TO BE REVISED BEFORE ROUGH
 ELECTRICAL INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]