| Plan Review Notes For Permit 07050064 |
| Permit Number |
07050064 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2007-08-20 10:23:31 | *** PROVISO *** | | | **5TH REVIEW** | | | | | | 1) NOTE: PLEASE REVISE PLANS SHOWING COMPLETE | | | CIRCUITING WHICH IS TO COORDINATE WITH THE SUBMITTED | | | PANEL SCHEDULE BEFORE FINAL ELECTRICAL INSPECTION. | | | 408.4 | | | FBC 106.3.5.1.2 | | | | | | 2) NOTE: PLEASE SEE GFI IN MASTER BATH MUST BE WITHIN | | | 3FT OF THE LAVATORY EDGE PER 210.52D | | | | | | 3) NOTE: PLEASE SEE THE COUNTER SPACE IN KITCHEN NEEDS | | | TO MEET 210.52C1 | | | | | | 4) NOTE: ADOPTED CODES REDLINED AS 2002 IS SHOWN FOR | | | NFPA-72, 70 AND 101 | | | THE CORRECT DATED CODES ARE AS FOLLOWS. | | | 2002 NFPA-72 | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | | | | 5) NOTE: PANEL SCHEDULE AND MANY PLACES IN NOTES STILL | | | STATE *SMOKE DETECTORS* INSTEAD OF SMOKE ALARMS. | | | NFPA-72 | | | | | | ** THE ABOVE NEEDS TO BE REVISED BEFORE FINAL. | | | ANY OTHER CHANGES NEED TO BE REVISED BEFORE ROUGH | | | ELECTRICAL INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|