Plan Review Notes
Plan Review Notes For Permit 07050064
Permit Number 07050064
Review Stop E
Sequence Number 4
Notes
Date Text
2007-08-14 16:37:25*** DENIED 4TH REVIEW ***
  
  
 **THE FOLLOWING ITEMS HAVE BEEN GONE OVER WITH PHIL
 FROM BRENNAN ARCHITECTURE.
 NEW SHEET WITH CORRECTIONS IS TO BE BROUGHT IN.
 PLEASE SEE SOME ITEMS STILL NEED TO BE ADDRESSED FROM
 PREVIOUS REVIEW ALONG WITH NEW ITEMS DUE TO THE NEW
 PANEL SCHEDULE AND LOAD CALCULATIONS SUBMITTED. THESE
 WERE NOT SUBMITTED ON PREVIOUS REVIEW FOR REVIEW.
  
 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE NOT
 SHOWN ON PLANS AS PREVIOUSLY REQUIRED.
 2005 NFPA-70, 2002 NFPA-72
  
 2) NOTE: PLEASE SEE 210.52C1 FOR MISSING KITCHEN
 COUNTER SPACE GFI RECEPTACLES.
 210.8A6 (WITHIN 2FT OF THE END OF ANY COUNTER SPACE,
 COUNTER SPACE ABOVE DISHWASHER NONE SHOWN ETC)
  
 3) NOTE: PLEASE SEE THE PANEL SCHEDULE AND LOADS SHOWN
 FOR SMALL APPLIANCE CIRCUITS AND LAUNDRY CIRCUITS.
 PLEASE SEE THE MINIMUM LOADS MUST BE FIGURED FOR THESE
 CIRCUITS. MAY NOT USE THE VA AS SHOWN. SOME ARE SHOWN
 AT .9, 1.0 ETC. MINIMUM OF 1500VA PER CODE FOR ONE OR
 MORE OF THE SMALL APPLIANCE AND LAUNDRY/WASHER
 CIRCUITS.
 PLEASE VERIFY NEW SUB-ZERO AS THIS IS BEING INDICATED
 ON ONE OF THE SMALL APPLIANCE CIRCUITS.
 PLEASE SEE 210.52B1, 210.11C1, C2, 220.53.
 PLEASE REVISE LOAD CALCULATIONS AS SHOWN AS THESE DO
 NOT MEET NEC 220.87
  
 4) NOTE: PLEASE SEE MASTER BATH NEW SINK MISSING GFI
 PER 210.8A1, 210.52D.
  
 5) NOTE: PLEASE KNOW AS PER ELECTRICAL CONTRACTOR AND
 PHIL FROM BRENNAN ARCHITECTURE, THE OLD CIRCUIT FOR THE
 OVEN WAS 30AMPS WHICH IS TOO SMALL AND OVERLOADED WITH
 THE NEW DOUBLE OVEN OF 8KW. A NEW CIRCUIT IS NOTED ON
 PANEL SCHEDULE HOWEVER THE PLANS STILL INDICATE THE OLD
 RELOCATED CIRCUIT BEIGN USED.
 240.4, 310.16 ETC.
  
 6) NOTE: PLEASE REVISE SMOKE DEVICES AS THESE ARE
 INDEED SMOKE ALARMS AND NOTE SMOKE DETECTORS PER
 DEFINITIONS IN NFPA-72.
 PLEASE SEE IF THESE WERE SMOKE DETECTORS THEN HORN
 DEVICES AND FA PANEL WOULD BE NEEDED.
 PLEASE REVISE TO SA.
  
 7) NOTE: PLEASE SEE THE LOAD CALCULATIONS NEED TO MEET
 NEC 220.87. PLEASE SEE THE A/C HEAT LOADS ARE BEING
 FIGURED INTO THE GENERAL LIGHTING AND RECEPTACLE LOADS
 WHICH IS NOT PERMITTED.
  
 8) NOTE: PLEASE SEE AFCI PROTECTION IS STILL NOTED IN
 NOTES PER 2002 NEC WHEN IT SHOULD BE 2005 NEC>
  
  
 ** ALL OF THE ABOVE ITEMS WERE GONE OVER ONE BY ONE AND
 NEED CORRECTED SHEETS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 561-805-6717
 [email protected]
  
  