| 2007-08-14 16:37:25 | *** DENIED 4TH REVIEW *** |
| | |
| | |
| | **THE FOLLOWING ITEMS HAVE BEEN GONE OVER WITH PHIL |
| | FROM BRENNAN ARCHITECTURE. |
| | NEW SHEET WITH CORRECTIONS IS TO BE BROUGHT IN. |
| | PLEASE SEE SOME ITEMS STILL NEED TO BE ADDRESSED FROM |
| | PREVIOUS REVIEW ALONG WITH NEW ITEMS DUE TO THE NEW |
| | PANEL SCHEDULE AND LOAD CALCULATIONS SUBMITTED. THESE |
| | WERE NOT SUBMITTED ON PREVIOUS REVIEW FOR REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE NOT |
| | SHOWN ON PLANS AS PREVIOUSLY REQUIRED. |
| | 2005 NFPA-70, 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE 210.52C1 FOR MISSING KITCHEN |
| | COUNTER SPACE GFI RECEPTACLES. |
| | 210.8A6 (WITHIN 2FT OF THE END OF ANY COUNTER SPACE, |
| | COUNTER SPACE ABOVE DISHWASHER NONE SHOWN ETC) |
| | |
| | 3) NOTE: PLEASE SEE THE PANEL SCHEDULE AND LOADS SHOWN |
| | FOR SMALL APPLIANCE CIRCUITS AND LAUNDRY CIRCUITS. |
| | PLEASE SEE THE MINIMUM LOADS MUST BE FIGURED FOR THESE |
| | CIRCUITS. MAY NOT USE THE VA AS SHOWN. SOME ARE SHOWN |
| | AT .9, 1.0 ETC. MINIMUM OF 1500VA PER CODE FOR ONE OR |
| | MORE OF THE SMALL APPLIANCE AND LAUNDRY/WASHER |
| | CIRCUITS. |
| | PLEASE VERIFY NEW SUB-ZERO AS THIS IS BEING INDICATED |
| | ON ONE OF THE SMALL APPLIANCE CIRCUITS. |
| | PLEASE SEE 210.52B1, 210.11C1, C2, 220.53. |
| | PLEASE REVISE LOAD CALCULATIONS AS SHOWN AS THESE DO |
| | NOT MEET NEC 220.87 |
| | |
| | 4) NOTE: PLEASE SEE MASTER BATH NEW SINK MISSING GFI |
| | PER 210.8A1, 210.52D. |
| | |
| | 5) NOTE: PLEASE KNOW AS PER ELECTRICAL CONTRACTOR AND |
| | PHIL FROM BRENNAN ARCHITECTURE, THE OLD CIRCUIT FOR THE |
| | OVEN WAS 30AMPS WHICH IS TOO SMALL AND OVERLOADED WITH |
| | THE NEW DOUBLE OVEN OF 8KW. A NEW CIRCUIT IS NOTED ON |
| | PANEL SCHEDULE HOWEVER THE PLANS STILL INDICATE THE OLD |
| | RELOCATED CIRCUIT BEIGN USED. |
| | 240.4, 310.16 ETC. |
| | |
| | 6) NOTE: PLEASE REVISE SMOKE DEVICES AS THESE ARE |
| | INDEED SMOKE ALARMS AND NOTE SMOKE DETECTORS PER |
| | DEFINITIONS IN NFPA-72. |
| | PLEASE SEE IF THESE WERE SMOKE DETECTORS THEN HORN |
| | DEVICES AND FA PANEL WOULD BE NEEDED. |
| | PLEASE REVISE TO SA. |
| | |
| | 7) NOTE: PLEASE SEE THE LOAD CALCULATIONS NEED TO MEET |
| | NEC 220.87. PLEASE SEE THE A/C HEAT LOADS ARE BEING |
| | FIGURED INTO THE GENERAL LIGHTING AND RECEPTACLE LOADS |
| | WHICH IS NOT PERMITTED. |
| | |
| | 8) NOTE: PLEASE SEE AFCI PROTECTION IS STILL NOTED IN |
| | NOTES PER 2002 NEC WHEN IT SHOULD BE 2005 NEC> |
| | |
| | |
| | ** ALL OF THE ABOVE ITEMS WERE GONE OVER ONE BY ONE AND |
| | NEED CORRECTED SHEETS. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |