| 2007-08-10 17:54:48 | ** DENIED 3RD REVIEW ** |
| | |
| | 1) NOTE: *** PLEASE SEE THE EXACT SAME COMMENTS FROM |
| | PREVIOUS REVIEW ARE STILL OUTSTANDING. |
| | PLEASE SEE THAT IN FACT THE SAME PLANS WITH OUT ANY |
| | CORRECTIONS TO ELECTRICAL WERE SUBMITTED BACK WITH A |
| | NEW REVISED DATE FROM THE ENGINEER OF RECORD. |
| | PLEASE SEE THAT THE PREVIOUS REVIEW COMMENTS ARE BEING |
| | PLACED BELOW FOR CONVENIENCE OF READING. |
| | |
| | 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE |
| | COMPLIANCE. |
| | PLEASE SEE A COPY OF THIS STATUTE IS ATTACHED. |
| | PLEASE KNOW AS THE INITIAL REVIEW WAS DONE WITHOUT |
| | SUFFICIENT PLANS ANY REPEAT COMMENTS ON THE NEXT REVIEW |
| | WOULD HAVE THE FEE ASSESSED. |
| | THIS IS ONLY NOTICE GIVEN AT THIS TIME. ONE COPY OF |
| | EACH SET SUBMITTED IS NOW BEING RETAINED BY THE OFFICE |
| | |
| | ** PREVIOUS REVIEW NOTES **** |
| | |
| | 1** UNSAT 2ND REVIEW ** |
| | |
| | *** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW HAVE NOT |
| | BEEN ADDRESSED FULLY. |
| | *** PLEASE ALSO SEE NEW COMMENTS BASED ON THE FACT THAT |
| | PLANS ARE NOW BEING SUBMITTED FOR THE FIRST REVIEW. |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-110 |
| | ** PLEASE SEE OTHER CODES WHICH MAY BE NOTED FROM OTHER |
| | TRADES. |
| | |
| | 2) NOTE: PLEASE SEE NFPA-72 AND REQUIRED NEW OR |
| | EXISTING SMOKE ALARMS OR DETECTORS DEPENDING ON THE |
| | SYSTEM BEING INSTALLED. PLEASE SEE FBC R313 AS THE |
| | SMOKE DEVICES IS REQUIRED TO BE BROUGHT UP TO THE |
| | CURRENT CODE. PLEASE SEE NFPA-72 11.5.1.1.1 AND 11.8.3 |
| | FOR LOCATION, TYPE REQUIREMENTS. INSIDE AND OUTSIDE ALL |
| | SLEEPING ROOMS, INTERCONNECTED ETC. |
| | THIS WAS REQUIRED ON PREVIOUS REVIEW: |
| | PLEASE SEE THE FOLLOWING COMMENT; |
| | |
| | 3) NOTE: PLEASE KNOW IF THESE DEVICES ARE NEW BEING |
| | ADDED TO THE EXISTING BEDROOMS/SLEEPING ROOMS, THEN |
| | PLEASE SEE 210.12 OF THE NEC FOR REQUIRED AFCI |
| | PROTECTION. |
| | |
| | 4) NOTE: PLEASE SHOW AND INDICATE ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH A PANEL SCHEDULE AND LOAD |
| | CALCULATIONS FOR NEW AND EXISTING LOADS. |
| | THIS WAS REQUESTED ON PREVIOUS REVIEW AND THIS WAS NOT |
| | DONE. |
| | PLEASE SEE 408.4, 310.16, 24.4 ETC. |
| | PLEASE COMPLETE THE MINIMUM REQUIRED DEDICATED CIRCUITS |
| | PER NEC. |
| | |
| | 5) NOTE: PLEASE SEE MISSING LOAD CALCULATIONS PER |
| | 220.83. |
| | PLEASE SEE MISSING SMALL APPLIANCE CIRCUITS ETC. |
| | 220.52 |
| | PLEASE SEE MISSING REQUIRED DEDICATED BATH CIRCUITS PER |
| | 210.11C3 |
| | PLEASE SEE OTHER DEDICATED CIRCUITS AS SHOWN ON PLANS |
| | WHICH NEED TO BE ON PANEL SCHEDULE AS WELL AS IN LOAD |
| | CALCULATIONS.220.54, 220.55 ETC |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE 210.4B FOR POSSIBLE |
| | DISHWASHER/DISPOSAL TO SAME YOKE. |
| | |
| | 7) NOTE: PLEASE SHOW THE LOCATION OF THE ELECTRICAL |
| | PANEL PER 110.26, 408.7, 240.24. |
| | LOCATION CAN NOT BE VERIFIED AT THIS TIME. |
| | |
| | ** PLEASE KNOW AT THIS TIME AS MUCH OF THE NEEDED |
| | INFORMATION HAS NOT BEEN SUBMITTED, THERE MAY BE |
| | COMMENTS ON THE FOLLOWING REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |